• Title/Summary/Keyword: gas circuit breakers

Search Result 61, Processing Time 0.027 seconds

A Study On The Arc Resistance of $SF_6$ Gas Circuit Breaker ($SF_6$ 가스차단기의 아크저항에 관한 연구)

  • Chong, Jin-Kyo;Lee, Woo-Young;Kim, Gyu-Tak
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.9
    • /
    • pp.1566-1570
    • /
    • 2007
  • [ $SF_6$ ] gas circuit breakers are widely used for short circuit current interruption in EHV(Extra High Voltage) or UHV(Ultra High Voltage) power systems. To develop $SF_6$ gas circuit breakers, the arc resistance value is necessary to compare experimental results to numerical ones. The arc resistance value can be obtained from a breaking test with a $SF_6$ gas circuit breaker. The direct testing or synthetic testing facility is widely used to verify the breaking ability for $SF_6$ gas circuit breakers. We employed the simplified synthetic testing facility to test a $SF_6$ gas circuit breaker prototype. The arc resistance characteristic was measured and calculated under the various experimental conditions. This arc resistance value can be used for verifying the numerical results from arc simulation in a circuit breakers.

Evaluation Method I of the Small Current Breaking Performance for SF(sub)6-Blown High-Voltage Gas Circuit Breakers (초고압 $SF_6$ 가스차단기의 소전류 차단성능 해석기술 I)

  • 송기동;이병운;박경엽;박정후
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.50 no.7
    • /
    • pp.331-337
    • /
    • 2001
  • With the increasing reliability of analysis schemes and the dramatically increased calculating speed, the computer simulation has become and indispensable process to predict the interruption capacity of circuit breakers. Generally, circuit breakers have to possess both the small current and large current interruption abilities and the circuit breaker designers need to evaluate its capacities to save the time and the expense. The analysis of small current and the large current interruption performances have been considered separately because the phenomena occurring in a interrupter are quite different. To analyze the dielectric recovery after large current interruption many physical phenomena such as heat transfer, convection and arc radiation, the nozzle ablation, the ionization of high temperature SF(sub)6 gas, the electric and themagnetic forces and so forth mush be considered. However, in the analysis of small current interruption performance only the cold gas flow analysis needs to be carried out because the capacitive current is to small that the influence from the current can be neglected. In this paper, an empirical equation which is obtained from a series of tests to estimate the dielectric recovery strength has been applied to a real circuit breaker. The results of analysis have been compared with the test results and the reliability has been investigated.

  • PDF

Influence of SF6/N2 Gas Mixture Ratios on the Lightning Streamer Propagation Characteristics of 22 kV MV Circuit Breaker

  • Gandhi, R.;Chandrasekar, S.;Nagarajan, C.
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.4
    • /
    • pp.1663-1672
    • /
    • 2018
  • In recent times, gas insulated medium voltage (MV) circuit breakers (CB) form a vital component in power system network, considering its advantages such as reduced size and safety margins. Gas insulation characteristics of circuit breakers are generally measured by lightning impulse (LI) test according to IEC standard 60060-1 as a factory routine test. Considering the environmental issues of $SF_6$ gas, many research works are being carried out towards the mixture of $SF_6$ gases for high voltage insulation applications. However, few reports are only available regarding the LI withstand and streamer propagation characteristics (at both positive and negative polarity of waveform) of $SF_6/N_2$ gas mixture insulated medium voltage circuit breakers. In this paper, positive and negative polarity LI tests are carried out on 22 kV medium voltage circuit breaker filled with $SF_6/N_2$ gas mixture at different gas pressures (1-5 bar) and at different gas mixture ratios. Important LI parameters such as breakdown voltage, streamer velocity, time to breakdown and acceleration voltage are evaluated with IEC standard LI ($1.2/50{\mu}s$) waveform. Weibull distribution analysis of LI breakdown voltage data is carried out and 50% probability breakdown voltage, scale parameter and shape parameter are evaluated. Results illustrate that the $25%SF_6+75%N_2$ gas filled insulation considerably enhances the LI withstand and breakdown strength of MV circuit breakers. LI breakdown voltage of circuit breaker under negative polarity shows higher value when compared with positive polarity. Results show that maintaining the gas pressure at 0.3 MPa (3 bar) with 10% $SF_6$ gas mixed with 90% $N_2$ will give optimum lighting impulse withstand performance of 22 kV MV circuit breaker.

Effect of arcing time on the interruption Performance of EHV class GCB (아크시간이 초고압 가스차단기의 차단성능에 미치는 영향)

  • Park, K.Y.;Shin, Y.J.;Song, K.D.;Chong, J.K.;Song, W.P.;Kwon, K.Y.
    • Proceedings of the KIEE Conference
    • /
    • 1998.07a
    • /
    • pp.161-163
    • /
    • 1998
  • The interruption performance of EHV class gas circuit breakers critically depends on the flow conditions inside interrupter and the external circuit conditions. In case of puffer type gas circuit breakers the flow conditons are significantly influenced by arcing time. In this paper the calculated results of RRRV and pressure rise at current zero with varying arcing time are presented and the effect of arcing time on the thermal interruption performance of EHV class gas circuit breakers is analyzed.

  • PDF

Evaluation Method II of the Small Current Breaking Performance of SF$_6$-Blown High-Voltage Gas Circuit Breakers (초고압 $SF_6$가스차단기의 소전류 차단성능 해석기술 II)

  • 송기동;이병윤;박경엽;박정후
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.50 no.8
    • /
    • pp.384-391
    • /
    • 2001
  • The insulation strength between contacts after current interruption to the transient recovery voltage i.e., the dielectric recovery strength should be estimated for the evaluation of the small capacitive current interruption capability. Many authors have used theoretical and semi-experimental approaches to evaluate the transient breakdown voltage after the current interruption. Moreover, an empirical equation, which is obtained from a series of tests, has been used to estimated the dielectric recovery strength. Un this paper, the theoretical method which is generated from the streamer theory has been applied to real circuit breakers in order to evaluated the interruption capability. The results of analysis have been compared with the test results and the reliability has been investigated.

  • PDF

A Study on A Gas Circuit Breaker Development Using Simplified Synthetic Testing Facility (간이합성시험설비를 이용한 가스차단기 개발에 관한 연구)

  • Chong, Jin-Kyo;Kim, Gyu-Tak
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.902-904
    • /
    • 2007
  • A $SF_6$ gas circuit breakers are widely used for short circuit current interruption in EHV or UHV power system. During a $SF_6$ gas circuit breaker development, Simplified synthetic testing facility is used. This paper shows how simplified synthetic testing facility is used for a SF6 gas circuit breaker development.

  • PDF

Flow Analysis of Gas Circuit Breakers for Developing the Small Current Interruption Performance (가스차단기의 소전류 차단성능 향상을 위한 유동해석)

  • Lee, Jong-Chul;Choi, Jong-Ung;Kang, Sung-Mo;Kim, Youn-Jea
    • Proceedings of the KSME Conference
    • /
    • 2003.04a
    • /
    • pp.1961-1965
    • /
    • 2003
  • The flow analysis is needed to verify the physical phenomena through interruption processes for improving the capacity and the reliability of gas circuit breakers. Moreover the small current interruption performance of GCBs could be predicted by coupling the flow characteristics with the electric field one. In this paper, the unsteady flow characteristics and the traveling trajectory are depicted with a commercial CFD code, PHOENICS, programmed for moving motion of objects. In order to validate computational results, the measured pressure data in cylinder and in front of arcing contact are compared with the test results of small current interruption.

  • PDF

Comparison of Evaluation Methods of the Small Current Breaking Performance for $SF_{6}$ Gas Circuit Breakers

  • Song, Ki-Dong;Lee, Byeong-Yoon;Park, Kyong-Yop;Park, Jung-Hoo
    • KIEE International Transaction on Electrical Machinery and Energy Conversion Systems
    • /
    • v.11B no.4
    • /
    • pp.129-136
    • /
    • 2001
  • In order to evaluate the dielectric recovery strength for GCBs, two equations have been usually utilized. One is the empirical formula obtained from a series of tests and the other is the theoretical formula obtained from the streamer theory. In this paper, both methods were applied to predict the small capacitive current interruption capability of model circuit breakers and were investigated in terms of the reliability by comparing the simulation results with test ones.

  • PDF

A Study on A Hot Gas Velocity Measurement in GCB Using Small-Gap (Small-Gap을 이용한 가스차단기에서의 열가스 속도측정에 관한 연구)

  • Kim, Hong-Kyu;Song, Ki-Dong;Park, Kyong-Yop;Hong, Jung-Pyo;Chong, Jin-Kyo
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.55 no.3
    • /
    • pp.155-158
    • /
    • 2006
  • $SF_6$ gas circuit breakers we widely used for short circuit current interruption in EHV or UHV power system. For a $SF_6$ gas circuit breaker development, the hot gas velocity measurement is necessary during $SF_6$ gas circuit breaker's trip operation. Small-gap flashover characteristics are used for this hot gas velocity measurement. This study sho was the hot gas velocity measurement results during $SF_6$ gas circuit breaker' trip operation.

Study on The Small-Gap Measuring System for Gas Velocity Measurement of $SF_6$ Gas Circuit Breaker ($SF_6$ 가스차단기에서 가스 속도측정을 위한 Small-Gap 측정시스템에 관한 연구)

  • Kim Hong-Kyu;Dong Song-Ki;Lee Woo-Young;Park Kyong-Yop;Chong Jin-Kyo
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.54 no.3
    • /
    • pp.139-144
    • /
    • 2005
  • [ $SF_6$ ] gas circuit breakers are widely used short circuit current interruption in EHV or UHV power system. For a $SF_6$ gas circuit breaker development, the $SF_6$ gas velocity measurement is necessary during $SF_6$ circuit breaker's trip operation. Small-gap flashover characteristics are used for this measurement. So, small-gap measuring system which will be used to develope GCB should be developed. This study shows the characteristic analysis and experimental results of small-gap measuring system.