• Title/Summary/Keyword: extinguishing agents

Search Result 55, Processing Time 0.028 seconds

Extinguishing Concentration of Inert Gases in Heptane Pool Fires (헵탄 풀화재에서 불활성기체 소화농도)

  • Jung, Tae-Hee;Lee, Eui-Ju
    • Journal of the Korean Society of Safety
    • /
    • v.27 no.3
    • /
    • pp.71-76
    • /
    • 2012
  • The coflow velocity effect on the minimum extinguishing concentration(MEC) was investigated experimentally in heptane cup-burner flames. Various inert gases($N_2$, Ar, $CO_2$, He) were added into the oxidizer to find the critical concentration and the effectiveness of the agents on flame extinction. The experimental results showed that the MECs were increased with increasing coflow velocity for most inert gases except helium, but the higher coflow velocity induced the lower burning rates of heptane. This indicated that the increase of coflow velocity resulted in the decrease of fuel velocity evaporated from fuel surface, and hence the stain rate on the reaction zone was also decreased. In the case of helium as a additive, the extinguishing concentration was independent of the coflow velocity because the heat conductivity was ten times larger than the other inert gases and flow effect by a strain rate might be compensated for heat loss to the surroundings.

EXPERIMENTAL STUDY ON PEAK CONCENTRATIONS OF HALON ALTERNATIVES AT ELEVATED TEMPERATURE

  • Ohtani, Hideo;Washimi, Akiko;Uehara, Yoichi
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 1997.11a
    • /
    • pp.550-557
    • /
    • 1997
  • Production of so-called Halon fire extinguishing agents has been prohibited since January 1994 because of their ozone depletion potential, To replace them, several hydrofluorocarbons and fluorocarbons have been developed and utilized. A number of studies on flame extinguishing concentrations and flammability peak concentrations of them have been done. Although there was enough information for practical purpose, more knowledge on fire extinguishing characteristics of them should be attained for efficient use of them. In this study, peak concentrations of methane/air mixtures with gaseous halogenated hydrocarbons were measured at elevated temperature, because the former studies were done at room temperature and temperature of a fire room can be higher than usual. Measurement was done at $200^{\circ}C$, because measuring system could not endure higher temperature. This study revealed that peak concentrations of halogenated hydrocarbons differed little at elevated temperature. The halogenated hydrocarbons have almost the same fire extinguishing ability as Halon 1301.

  • PDF

A Study of Fire Extinguishment Characteristic for the Real Scale Deap-Seated Fire (실규모 심부화재 소화특성에 관한 연구)

  • Kim, Nam-Kyun;Rie, Dong-Ho
    • Fire Science and Engineering
    • /
    • v.29 no.2
    • /
    • pp.13-19
    • /
    • 2015
  • Real scale fire tests was carried out for extinguishing performance evaluation of the wetting agent. The experiment was conducted in accordance with a Class A fire extinguishing test methods specified in the 'Type Approval of the Manual System Fire Extinguisher and Technical Standards of Test'. In addition, the subjects of this experiment were the wood flour and rice husk. Fire-fighting water, the three kinds of wetting agents used in the country and this study was used, was undertaken to determine a clear discrimination of the water and wetting agent. In the experimental results, it was confirmed that the internal temperature is maintained long time in the case of water. The internal temperature were rapidly lowered in the experiment of wetting agents. Therefore, the discrimination of extinguishing ability was confirmed by the temperature distribution in accordance with time. Based on the results of this experiment, this study is expected to be used as a underlying material on presenting a method of optimized performance evaluation of wetting extinguishing agent.

A Study On The Development Of An Automatic Fire Extinguishing System For The Engine Compartment Use Of Automobiles (자동차 엔진 화재용 자동 소화 시스템 개발에 관한 연구)

  • Lim, Sung-Muk;Jung, Ki-Chang;Kim, Hong;Kang, Young-Goo;Lee, Chang-Sub
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 1996.11a
    • /
    • pp.57-61
    • /
    • 1996
  • Our goal was to make a cost-effective automatic fire extinguishing system for the engine compartment use of automobiles. We designed this system for the engine compartment. This system consists of 1)foam extinguisher, 2)four nozzles, 3)a pipe arrangement, and 4)an extinguishing device which is equipped with a glass bulb as detector. First and foremost, the extinguishing device was carefully designed to keep the system cost to a minimum. Second, a AFFF foam extinguisher was used because no other fire-fighting agents proved effective against fire in the engine compartment. The AFFF(Aqueous Film Forming Foam) agent which was used in the extinguisher is the 3M company's Light Water. We sought, however, to make other foams by using Halon 1301 and Halon alternatives such as HCFC Blend A, HFC-227ea. We selected these alternatives instead of air in order to raise the expansion ratio of the AFFF agent. By these means we discovered that it is possible to increase the expansion ration of the AFFF agent up to 44:1. We then demonstrated that our automatic fire extinguishing system is the most effective and lowest cost-system yet devised for passenger cars.

  • PDF

Example of Air Exposure Assessment for Fire Extinguishing Agent Residues (소화약제 잔류물질에 대한 공기 중 노출평가 사례)

  • Daesung Lim
    • Journal of Korean Society of Occupational and Environmental Hygiene
    • /
    • v.34 no.1
    • /
    • pp.14-17
    • /
    • 2024
  • Objectives: This is a case of air exposure assessment conducted after researchers complained of headaches and odor due to residual substances from fire extinguishing agents spread throughout the laboratory due to a malfunction of the fire extinguishing facility. Methods: A component analysis was conducted on the residual substances of a fire extinguishing agent spread in a laboratory using Py-GC-MS (pyrolysis gas chromatography mass spectrometry) at the research institute's own central equipment research center. As a result of the component analysis, several types of substances were detected. Among these, five types of substances subject to work environment measurement in the aromatic hydrocarbon series, which can affect headaches and odor, were selected as substances subject to exposure assessment in the air, and the measurement and analysis methods of the target substances were conducted in accordance with the KOSHA Guide for each substance. Conclusions: The measurement results showed that all 5 types of substances were not detected at locations A, B, and C. This is believed to be the result of the residual substances in the fire extinguishing agent being measured when approximately two months had elapsed after being exposed to the test bench, and the substances already exposed had volatilized and disappeared. In this survey, it is believed that the measurement process is more important than the measurement results.

Wetting Agent Performance Evaluation Using Scale Model (축소모형 실험을 통한 침윤소화약제 소화성능 평가)

  • Kim, Nam-Kyun;Lim, Kyung-Bum;Rie, Dong-Ho
    • Fire Science and Engineering
    • /
    • v.28 no.2
    • /
    • pp.20-25
    • /
    • 2014
  • In this study, the extinguishing performance evaluation of wetting agent for wood crib was conducted by using a scale model equipment that we designed. To confirm the optimal conditions of the experiment, a test was changed amount of fire extinguishing water and the number of timber. As a result, the discrimination of the fire extinguishing performance was seen only when 20 pieces of wood and the extinguishing water of 100 mL were used. After evaluating the extinguishing performance of domestic and foreign wetting extinguishing agents under these conditions, a reignition was occurred in only when we used water. In addition, the discrimination of extinguishing performance was seen through the temperature distribution according to the time of watering. Based on the results of this experiment, this study is expected to be able to use as a basis on presenting a method of optimized performance evaluation of wetting extinguishing agent.

THE DEVELOPMENT OF FOAMING AGENTS USING SLES & DH-109EX

  • Hu Rui;Kim, Jeong-Hun;Kim, Min-Kyn;Kang, Young-Goo;Kim, Hong
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 1997.11a
    • /
    • pp.582-589
    • /
    • 1997
  • Experiments were conducted to develop foaming agents by using SLES and DH-l09EX as raw material. PG (Propylene glycol) and BC (Butyl cellusolve) were adopted as subsidiary material. The undiluted foam solution was produced with these materials. This solution determined the expansion ratio, viscosity, drainage time and extinguishing ability of the final product. The results indicate that the expansion ratio is over 16 and drainage time is over one minute. The extinguishing ability for SLES system was succeeded in the unit of B-0.5.

  • PDF

SOLUBILITY OF NITROGEN IN CLEAN EIRE EXTINGUISHING AGENTS AT HIGH PRESSURE

  • Kim, Jae-Duck;Lim, Jong-Sung;Lee, Youn-Woo;Lee, Youn-Yong
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 1997.11a
    • /
    • pp.534-541
    • /
    • 1997
  • Isothermal solubilities of nitrogen in clean fire extinguishing agents, such as bromotrifluoromethane (Halon-1301), bromochlorodifluoromethane (Halon-121 t), 1,1,1,2,3,3,3- heptafluoropropane (HFC-227ea), and trifluoroiodomethane (FIC-13I1) were measured in a circulation-type equilibrium apparatus. The temperature range was (293.2 to 313.2) K and the pressure range was (30 to 100) bar. The experimental data were well correlated with the Peng- Robinson equation of state using the Wong and Sandier mixing rules, and the relevant parameters are presented.

  • PDF

A Study on the Development of Fire Extinguishing Agent and Extinguishing System for ESS Fire (ESS 화재전용 소화약제 및 소화시스템 개발에 관한 연구)

  • Lee, Yeon-Ho;Lee, Joo-Hyung;Kim, Soo-Jin;Chon, Sung-Ho;Choi, Byoung-Chul;Oh, Seung-Ju;Kim, Si-Kuk
    • Fire Science and Engineering
    • /
    • v.34 no.2
    • /
    • pp.147-155
    • /
    • 2020
  • This paper presents a study on the development of a fire extinguishing agent and extinguishing system for an energy storage system (ESS) fire. The fire extinguishing agent designed to extinguish an ESS fire is a highly permeable fire extinguisher that reduces the surface tension and viscosity while bringing about cooling action. This is the main extinguishing effect of this type of wetting agent, which displays the characteristics of fire extinguishing agents used for penetrating the battery cells inside the ESS module. For the fire extinguishing system, a local application system was designed to suppress fire on a rack-by-rack basis. A 360° rotating nozzle was inserted into the rear hall of the ESS module, and general nozzles were installed in the rack to maximize the fire extinguishing effect. The fire extinguishing agent was strongly discharged by virtue of the gas release pressure. Experiments on fire suppression performance with ESS module 1 unit and module 3 units showed that all visible flames were extinguished in 8 s and 9 s, respectively, by the fire extinguishing agent. In addition, based on confirming reignition for 600 s after the fire extinguishing agent was exhausted, it was confirmed that the ESS fire was completely extinguished without reignition in all fire suppression performance experiments.