• Title/Summary/Keyword: electrical disaster

Search Result 281, Processing Time 0.027 seconds

A Study on the Electrical Fire Risk of Terminal Block Due to Single and Composite Cause (단일 및 복합 원인에 의한 단자대 전기화재위험성에 관한 연구)

  • Kim, Si-Kuk;Gum, Dong-Shin;Lee, Chun-Ha
    • Fire Science and Engineering
    • /
    • v.29 no.5
    • /
    • pp.57-66
    • /
    • 2015
  • This thesis is based on a research to investigate the electrical fire risk due to the single and composite cause in a terminal block. This paper analyzed the thermal characteristics depending on the screw torque change and contact resistance change to measure the fire risk due to the poor contact from single cause first. To measure the fire risk due to the composite cause, the acceleration tracking depending on the contact resistance change was experimented to check the correlation of poor contact and tracking to fire. The experiment result showed that the thermal characteristics were clearer as the screw torque in poor contact status and magnitude of contact resistance increased and that the thermal characteristics of terminal block depending on the contact resistance change was more reliable than the thermal characteristics depending on the screw torque change. Moreover, the terminal block poor contact and tracking were correlated in the case of the composite cause, and when two composite causes were interacted, the electrical fire risk was higher than the single cause.

TRAINING PROGRAM BASED ON DIGIEAL CONTENTS FOR PROTECTING CULTURAL ASSETS FROM FIRE (문화재 화재 대응훈련을 위한 시뮬레이터 개발)

  • Ki, Jaesug
    • Proceedings of the Korean Society of Disaster Information Conference
    • /
    • 2015.11a
    • /
    • pp.321-323
    • /
    • 2015
  • This study will build a prompt response system based on accurate information about the internal structure of cultural heritages, including the roof structure, to improve the ability to contain and respond to the fire of wooden structure for safe preservation of cultural heritages with historical and academic values that are very vulnerable to fire, and develop a training simulation program based on virtual reality by applying the concept of Edutainment for systemized and interesting training of trainees with a response manual.

  • PDF

A Study on the Necessary Spaces and Area Standards of Integration Facility for Early Childhood Education and Care (영유아 교육·보육 통합시설의 필요 공간과 면적기준에 관한 연구)

  • Cho, Jin Il;Choi, Hyeong Ju
    • The Journal of Sustainable Design and Educational Environment Research
    • /
    • v.17 no.2
    • /
    • pp.22-37
    • /
    • 2018
  • This study suggests desirable disaster safety education curriculum through analyzing the operational status of the school disaster safety management training course and demand survey of school staff. First, the problem of the disaster safety training course of the school is not connected with the lack of law and system and the school disaster safety job. Second, improvement of law and system and variety of training should be made to acquire professional knowledge. Third, it is necessary to divide curriculum into the following four categories, according to educational needs of public officials ; Educational administration officers course focused on facility safety, maintenance and disaster countermeasure. Educational officials in technical post course addressing approval and permission of school facility projects, seismic reinforcement of school building, etc. Educational supervisors course covering roles and responsibilities of the school safety supervisors in the event of disaster. Teaching staffs course focused on safety instructions for students. Fourth, it is found that lectures and experiential learning methods are the most desirable methods of teaching and learning, and the major ranks are earthquake disaster, fire, gas, typhoon, school road, and electrical safety.

A Study on the Change of Electrical Characteristics of Sand (모래지반에서의 전기적 특성 변화에 관한 연구)

  • Han, Yushik;Yoo, Ki Cheong
    • Journal of Korean Society of Disaster and Security
    • /
    • v.10 no.1
    • /
    • pp.61-66
    • /
    • 2017
  • It is very important to understand the electromagnetic characteristics of underground media in GPR (Ground Penetrating Radar) survey. Depending on the electrical characteristics of the underground medium, the energy of the electromagnetic wave becomes relatively small, and reflection from the interface may become difficult. In this study, electrical characteristics of sandy soils under various (loose and dense) conditions were analyzed. As a result, In dry sand is the dielectric constant increased as the relative density increased, and the dielectric constant and electrical conductivity increased as the moisture content of the sand increased.

The Investigation of Alluvium by Using Electrical Resistivity, Seismic Survey and GPR (전기비저항, 탄성파 그리고 GPR 탐사를 활용한 충적층 탐사)

  • Park, Chung-Hwa;Won, Kyung-Sik;Byun, Ji-Hwan;Min, Dae-Hong;Yoon, Hyung-Koo
    • Journal of the Korean Geotechnical Society
    • /
    • v.29 no.9
    • /
    • pp.17-29
    • /
    • 2013
  • The geophysical methods have an advantage for investigating the wide area with low cost, and thus the application of these methods has been increased. The objective of this paper estimates the characteristics of alluvium through the geophysical methods including elastic wave, electrical resistivity and ground penetration radar. And the standard penetration test is also carried out for verifying the geophysical data with comparison. The sources of elastic wave method are divided into hammer and sissy and the electrical resistivity method is applied with different sizes, shapes and arrays of electrode for deciding the effective way. The center frequency is determined to be 270 MHz for considering the characteristics of soil. The results of ground penetration radar are also compared with those of standard penetration test. The high resolution shows when the source is a sissy in elastic wave method, however, the water level is not identified. In the electrical resistivity method, the non-polarizable electrode and schlumberger array show highly reliable data and the resolution of ground penetration radar is low. Thus, the results of this study are widely applied for determining the appropriate method when investigating the characteristics of alluvium.

Electrical Fire Disaster Prevention Device of Double Protection using a High Precision Current Sensor in Low Voltage Distribution System (고정밀 전류센서를 이용한 저압배전계통 이중 보호용 전기화재 방재장치)

  • Kwak, Dong-Kurl;Jung, Do-Young
    • Fire Science and Engineering
    • /
    • v.23 no.3
    • /
    • pp.40-47
    • /
    • 2009
  • Nowadays the diversity and large-capacity of electric appliances are strong effect on electrical fires augment in an alarming way. But, as the inactive response characteristics of the existing RCD (Residual Current protective Device) used on low voltage power distribution system, so control of overload and electric short circuit faults, major causes of electrical fires, are not enough. Therefore, this paper is confirmed the unreliability of the existing RCD by electrical fault simulator and is proposed a Electrical Fire Disaster Prevention Device (EFDPD) by using a high precision current sensor (namely, reed switch) for the prevention of electrical disasters in low voltage power distribution system caused by overload or electric short circuit faults. The sensitive reed switch in the proposed EFDPD exactly detects the increased magnetic flux with the overload or the short current caused by a number of electrical faults, and the following, the EFDPD has double protection function which operates self circuit breaker or rapidly cuts off the existing RCD. The proposed EFDPD is confirmed the excellent characteristics in response velocity and accuracy in comparison with the conventional circuit breaker through various operation performance analysis. The proposed EFDPD can also prevent electrical disaster, like as electrical fires, which resulted from the malfunction and inactive response characteristics of the existing RCD.

Development of Electrical Fire Detection System Applying Fuzzy Logic for Main Causes of Electrical Fire in Traditional Market Shops

  • Kim, Doo Hyun;Hwang, Dong Kyu;Kim, Sung Chul;Kim, Sang Ryull;Kim, Yoon Bok
    • International Journal of Safety
    • /
    • v.11 no.2
    • /
    • pp.15-21
    • /
    • 2012
  • This paper is aimed to develop an electrical fire detection system (EFDS) which can analyze the possibility of electrical fire for overcurrent, leakage current and arc signals of panel board in traditional market shop. The EFDS adopted fuzzy logic and precursory data for overcurrent, leakage current and arc signals to evaluate the possibility of electrical fire. The signals are obtained directly from panel board in traditional market shops and fuzzy membership function is obtained from experiment, simulation, expert's advice. The overcurrent data is acquired by thermal data of normal and abnormal states (partial disconnection) on the insulated electrical wire, in accordance with the increase of the current signal, The leakage current data is obtained under various environments. The arc signal is acquisited by waveforms of instantaneous value in time domain and frequency band in frequency domain. The Fuzzy algorithm for DB of EFDS consists of fuzzification, inference engine by Mamdani's method and defuzzification by center of gravity method. In order to verify the performance and reliability of EFDS, it was applied to Jeon-Ju traditional market shops (90 shops) in Korea. Results show that EFDS in this paper is useful in alarming the fire case, which will prevent severe damage to human beings and properties, and reduce the electrical fires in a vulnerable area of electrical disaster.

Analysis of administration system for lightning damage in developed countries (선진국의 낙뢰피해 관리운영체제 분석)

  • Cho, Sung-Chul;Lee, Tae-Hyung;Eom, Ju-Hong
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2009.05a
    • /
    • pp.340-343
    • /
    • 2009
  • Recently, the lightning damage to human and structure is increasing steadily and many countries try to reduce lightning-caused casualties and economical loss through special disaster management system. The organization of warning system and management system for lightning damage in developed countries were investigated in this paper. The organization of central government for disaster management and cooperation system with local government in USA, Japan, the Britain, and Germany were introduced and the division of roles with meteorological administration were described.

  • PDF

BCP utilizing Disaster Recovery-System for the Protection of the Information System Design (효율적인 정보자산 보호를 위한 BCP 활용 재해복구시스템 설계)

  • Kim, Hyun-Joo;Lee, Soo-Jong;Shin, In-Chul
    • Journal of the Korea Society of Computer and Information
    • /
    • v.18 no.7
    • /
    • pp.93-100
    • /
    • 2013
  • The ensuing disaster brought by the massive earthquake and tsunami in the northeastern region of Japan in 2011 placed Japan, one of the three most advanced economic powers in the world, in a defenseless state. With the rising interest in disaster recovery, Korea is also making efforts to provide technological support for barrier-free system operation 24 hours a day, 365 days a year. To protect intelligence assets efficiently, this study draws a job performance plan to prepare for disasters, which systemizes methodical coping capabilities into business plans when disasters occur. Moreover, this study systemizes the job performance plan to allow members easy access to information that will help them proceed without confusion in emergencies. This plant is intended to protect intelligence assets of an organization clearly and promptly.

A Study on the Fire Risk of High-voltage Cables for Electrical Vehicles (전기차용 고전압 케이블의 화재 위험성에 관한 연구)

  • Sin Dong Kang;Ye Jin Park;Si Hyun Kim;Jae-Ho Kim
    • Journal of the Korean Society of Safety
    • /
    • v.38 no.4
    • /
    • pp.8-14
    • /
    • 2023
  • This study presents the characteristics of short circuits (SCs) caused by excessive currents in high-voltage cables used in electric vehicles and emphasizes the need to calculate the cross-sectional areas of these cables according to the SC current. Three direct current power supplies were connected in parallel to test the SC characteristics caused by excessive currents, and a timer and a magnetic contactor were used to deliver the conduction time and SC current. A circular infrared-radiation heater was used to test the temperature-dependent SC characteristics, a thermocouple was used to measure the temperature, and a shunt resistor was used to measure the current. As the SC current increased, the fusing time of the cable decreased. Additionally, a high-voltage cable (with an area of 16 mm2 ) used in electric vehicles fused when a current (approximately equal to 55 times the allowable current) flowed for 0.2 s (operating time of the protective device). When the SC current is 10 kA, the cable may fuse during the operating time of the protective device, thus creating a fire hazard. In electric vehicles, the size of the SC current increases in proportion to the capacity of the battery. Thus, the cross-sectional areas of the cables used should be calculated accordingly, and cable operations should be properly coordinated with the surrounding protective devices.