• Title/Summary/Keyword: electric wire

Search Result 744, Processing Time 0.032 seconds

Methodology of Parallel Ground Conductor Installation on Underground Transmission System (지중송전 시스템의 병행지선 설치 방안 연구)

  • Hong, Dong-Suk;Park, Sung-Min;Hahn, Kwayng-Hyun
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.470-471
    • /
    • 2008
  • SVL is installed at underground transmission system to protect cables and insulation joint-box from overvoltages caused by lightning, switching, and line-to-ground fault. Domestic underground power system adopts cross bonding type to reduce the induced voltage at sheath, but single-point bonding is required depending the system installation configuration. SVL can be easily broken by overvoltages induced at joint-box because single-point bonding has uneffective system structure to extract fault current. ANSI/IEEE recommends Parallel Ground Continuity Conductor(PGCC) to prevent SVL breakdown. In this paper, EMTP simulation is performed to analyze effects on SVL under PGCC installation when single-line-to-ground fault occurs. The result shows that PGCC and short single-point bonding distance can reduce overvoltages at SVL.

  • PDF

Application of 275kV XLPE Power Cables for Overseas Protect (275kV XLPE절연 전력케이블의 해외프로젝트 적용)

  • Kwon, B.I.;Seong, J.K.;Han, C.S.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07c
    • /
    • pp.1736-1738
    • /
    • 2002
  • Oil-filled power cables and XLPE power cables have been globally applied for extra-high-voltage underground power transmission lines. The application of XLPE cables for the transmission lines have been largely increased at the domestic and overseas projects because of some issues. O.F cables have some week points, related with the issues of the environmental pollution and the needed maintenance work, even though they have been applied for several ten years and their reliability has been proven. Meanwhile, the demands on XLPE power cables increase as their manufacturing technologies have been improved and their simplicity of installations has been focused on. In Korea, for the first time, the 275kV XLPE cable is to be applied at an overseas power plant project. This paper introduces the project profile, the design of the XLPE cable and its accessories, the cable system design and the installation design.

  • PDF

The characteristics of dispersion compensation in uniform fiber grating (일반광섬유격자의 분산보상 특성 분석)

  • Lee, J.H.;Song, J.H.;Lee, K.S.;Lee, Y.S.;Jeon, C.O.;Jeon, K.I.
    • Proceedings of the KIEE Conference
    • /
    • 1998.07e
    • /
    • pp.1834-1836
    • /
    • 1998
  • The characteristics of dispersion compensation in uniform fiber grating is studied according to grating length, the refractive index modulation depth, and Gaussian window parameter(G). A 50cm-long uniform grating apodized by Gaussian function(G=10) with bandwidth of ${\sim}0.8nm$ and small noise is designed.

  • PDF

Consideration of cable cross bonding and cable covering protection units (케이블 크로스본드 및 CCPU 적용검토)

  • Kim, Young;Kim, Jang-Woen;Seong, Jeong-Kue
    • Proceedings of the KIEE Conference
    • /
    • 1994.07b
    • /
    • pp.1646-1648
    • /
    • 1994
  • In the system of underground transmission line, the rate of electrical failure is very low, but, if once occuring, the failure evolves into a paralysis of the system, the time of restoration is very long, the damage from stopping of power supply is very serious, and the cost of restoration is very great. Because of these problems, you must try to protect the system and equipment from every electrical failure by contributing much carefulness to the design and operation of the underground system. This study summerizes the results of simmulation tests about the effect of installing this protection device on the insulated joint box and the terminal end box.

  • PDF

A Study on the Efficient Stabilization of Dropper Clamp for Messenger and Trolley Wire (전차선 및 조가선 접속지지용 드롭바크램프의 성능 안정화 연구)

  • Jung, Hyun-Soo;Lee, Seung-Hyuk;Ree, Cheol-Jick;Lee, Hyung-Kwon
    • Proceedings of the KIEE Conference
    • /
    • 2004.05b
    • /
    • pp.156-158
    • /
    • 2004
  • In the ATs(Auto-Transformers)-fed AC electric railroad system, the trolley wire with high power is supported with a messenger by the dropper. As the dropper maintains the height of the trolley wire and plays a role in distributing the supply power, it should be stabilized in that an electric and mechanical character accord ins the change of the open air circumstance and constructed easily. Consequently, this paper propose C5111 Sn(3.5$\sim$4.5%) and hexagonal round bolt for the way of the efficient stabilization as a result of the test that the correlation of the Sn content and the change of temperature affect a character of product.

  • PDF

STUDYING SOIL THERMAL RESISTIVITY ABOUT CABLE LAYING OF PIPE DUCTING, DIRECT BURYING (관로 및 직매 포설에 대한 토양열저항의 검토)

  • Kim, Y.;Kwon, B.I.;Kwon, S.C.
    • Proceedings of the KIEE Conference
    • /
    • 1993.07a
    • /
    • pp.174-176
    • /
    • 1993
  • Laying up homogeneous power cable in the earth. we sure that one of the most effectest fact is the rising of thermal resistivity. Today, system designing of in and outdoor project, calculating current carrying capacity totally depend on standard of JCS-168D and IEC-287 to applicate. Specially, the formula of calculating soil thermal resistivity is what is based on KENELLY,s is usually used. In this report, Let's study the formula of soil thermal resistivity which was born in the idea of KENELLY.

  • PDF

Development of Modular Scaffold for Overhead Transmission Line Wiring Work (송전선로 가선공사용 모듈형 발받침 개발)

  • Min, Byeong-Wook;Baik, Seung-Do;Kang, Dae-Eon;Bang, Hang-Kwon;Choi, Jin-Sung;Baek, Soo-Gon
    • Proceedings of the KIEE Conference
    • /
    • 2006.07a
    • /
    • pp.450-451
    • /
    • 2006
  • The method of conductor wiring is that a messenger wire is installed, the end of the wire is connected to the conductor and a engine puller pulls the conductor. The length of one section of wiring is $3{\sim}5km$ and one group messenger wire pulls simultaneously $2{\sim}4$ group conductor, while a tensioner maintains wiring tension to prevent the deflection of the conductor. However, there are many obstacles such as roads, power lines, communication lines, buildings, farms and crops. Therefore to prevent damage from conductor deflection a staging is used. The currently used staging is scaffolding lumber which is difficult to secure and it's construction efficiency is very low because it requires a lot of time and manpower. So this study developed a insulating defense tube and pipe connecting device, and a truss structure fabrication module using steel pipe which reduces construction time and cost through a compressive and dielectric strength test.

  • PDF

Present Development Trends of 345kV XLPE Cables (345kV XLPE 케이블의 개발 현황)

  • Kim, Y.;Park, K.R.;Lee, S.H.;Heo, K.D.;Lee, S.H.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07c
    • /
    • pp.1881-1883
    • /
    • 2002
  • Recently, 345kV XLPE Cable and Accessories have been developed and will be applied for Youngseo$\sim$Youngdeungpo project in Korea. So, let this project and the process of development introduce on this paper. The cable type and length of this project is 345kv XLPE 1C*$2000mm^2$ 66km and all cable will be pulled on cable tunnel. The diameter of cable insulation was designed as 27mm, we could reduce it by appling for hi-tech and super-clean system. Joints were developed by a pre-fabricated type which considered high safety and economic issues. We had also done Pre-Qualification test for verifying the reliance of cable and accessories before construction. As we developed this 345kV XLPE cable system including its accessories at the same time, we can have higher technologies and contribute safe power in transmission lines. In adtionally, we can have a stable status for suppling EHV cable systems to a variety foreign customers by ourselves.

  • PDF

Development of Stainless Steel Loose Tube Optical Ground Wire with 144 Single Mode Fibers (144심용 초다심 SSLT OPGW 개발)

  • Baik, S.Y.;Kim, K.M.;Kim, S.W.;Kim, D.W.;Lee, I.H.;Sohn, K.I.;Lee, S.C.
    • Proceedings of the KIEE Conference
    • /
    • 2001.11b
    • /
    • pp.395-398
    • /
    • 2001
  • Recently, the increasing need for internet and the activation of hiring business of communication line makes the demand for OPGW cable which can construct the optical communication network in the basis of existing overhead power transmission line. Especially, the demand is focused on the high fiber count OPGW due to high capacity transmission. In step with the trend toward high fiber count cable we have developed the Stainless Steel Loose Tube type OPGW within which have 144core firstly in KOREA. This paper describes the cable design and manufacturing process which gives the stable operation in very severe conditions and the long-term reliability test results conducted in according to dominant specification IEEE Std. 1138-1194.

  • PDF

Characteristics of Surface Roughness According to Wire Vibration and Wire-cut Electric Discharge Machining of Aluminum Alloy 6061 (III) (알루미늄 합금 6061에서 와이어 진동부가에 의한 와이어 컷 방전가공에 따른 표면 거칠기 특성 (III))

  • Ryu, Cheong-Won;Choi, Seong-Dae
    • Journal of the Korean Society of Manufacturing Process Engineers
    • /
    • v.15 no.1
    • /
    • pp.81-88
    • /
    • 2016
  • Recently, high-efficiency machining in the production of high-value products with complex shapes has constantly been required along with the need for hybrid machining. In this study, in addition to wire-cut Electric Discharge Machining (EDM) and vibration, we present the possibility of a hybrid process by carrying out an experiment with aluminum alloy, and the hybrid process determines the nature of the surface. The selected experimental parameters are waveform, amplitude, peak current, and two-dimensional (2D) vibration. The experimental results give the guideline for selecting reasonable machining parameters. The surface roughness was improved about 20% with increases in the amplitude of the vibration.