• Title/Summary/Keyword: electric leakage

Search Result 584, Processing Time 0.041 seconds

Electric Fire Hazard in Low Voltage Distribution Circuits Protected by Electric Leakage Circuit Breaker(ELB) (누전차단기로 보호되는 저압선로에서의 발화위험성)

  • 홍성호;김두현
    • Journal of the Korean Society of Safety
    • /
    • v.15 no.1
    • /
    • pp.93-99
    • /
    • 2000
  • This paper presents a study on the assessment of electrical fire hazards by electric circuits with leakage. The hazards are evaluated with the energy supplied by earth-leakage currents which flow in the circuits simulating the actual circuit of domestic premises. Also, operating time and current of ELB are measured by an experimental approach. A common specification of ELB used in this paper has a sensitivity of 30[mA] for leakage current working on the current-balance principle. Total charges and energy of leakage currents are calculated quantitatively by a theoretical approach and compared with the results obtained from experiments.

  • PDF

The Effectiveness Analysis of the Resistive Leakage Current Monitoring by Analyzing the Phase of the Body Current (인체 통전전류 위상 분석을 통한 저항성 누설전류 감시의 유효성 분석)

  • Kim, Jae-Hyun;Lim, Young-Bea;Lee, Sang-Ick;Kim, Dong-Woo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.9
    • /
    • pp.90-99
    • /
    • 2013
  • To analyze the effectiveness of the resistive leakage current monitoring as a technology preventing electrical accidents, in this paper, we have estimated the phase of the body impedance by using the body impedance model and the body impedance data from IEC. We also have analyzed the phase of the electric body current in the case of 60Hz/220V. From these results, we concluded that deliberate researches about the phase of the electrical body current and related regulations must be carried out before the resistive leakage current monitoring unit is used to protect electric shock. And we concluded that the resistive leakage current monitoring unit can be utilized to prevent electrical fires caused by electric leakage current without unwanted circuit break due to capacitive leakage current flowing from line filter capacitors to the earth.

A Leakage Current Supervising Control and Data Acquision in the Building based on Embedded System (임베디드 시스템을 이용한 빌딩 누전감시 시스템)

  • Shin, Seung-Woo;Yu, Jong-Il;Chang, Kyung-Bae;Shim, Il-Joo;Park, Gwi-Tae
    • Proceedings of the KIEE Conference
    • /
    • 2004.07d
    • /
    • pp.2457-2460
    • /
    • 2004
  • As the usage of electron electricity is rapidly increasing, corresponding accidents also take place proportionately. Although various losses occur very often because of senility of system and maintenance, only a earth leakage current breaker by a leakage current alert is used. That means it is always fraught with dander. This paper, we propose to measure and cut a leakage current and method of taking a measurement current short circuit. Besides, through keeping watch communication with server, prevent electric loss and mishap in advance.

  • PDF

Development of Electric Instrument of Current and Leakage Current based on NI-9223 and Current Prove (NI-9223과 전류프로브를 이용한 전류 및 누설전류 측정장치 개발)

  • Kim, Sung-Chul;Kim, Un-Sul
    • Journal of the Korean Society of Safety
    • /
    • v.27 no.6
    • /
    • pp.48-53
    • /
    • 2012
  • This paper is purposed to develop portable electric instrument to select NI-9223(National instrument comp.) and clamp meter(HIOKI comp.), which can be used in developing electric instrument, to detect leakage current(ZCT) and current(CT) signals. In this paper, The electric instrument that can interface with current and leakage current instrument(HIOKI 9283), is developed by NI-9223 of NI comp.. HIOKI clamp meter can measure current signals certainly by high-sensitivity of 10 ${\mu}A$ resolution(leakage current : at 10 mA range) and current 1~200A range. The NI-9223 use four 16-bit analog-to-digital converters(ADCs) for true simultaneous sampling at up to 1 MS/s per channel. NI-9223 can synchronize all analog input modules installed in the same chassis to share the same start clock and/or sample clocks. The monitoring program is developed by SignalExpress of LabVIEW. The monitoring program are developed to analyze at simultaneous sampling on electrical signals such as leakage current(ZCT) and current(CT). The developed system verification tests were conducted, and portable electric instrument can be used in place which requires analysis of the actual electrical signal.

Analysis of Resistive and Capacitive Leakage Current according to Wiring Type and Length at Cattle Barn (우사(牛舍)에서 전기배선의 종류와 길이에 따른 저항성 및 용량성 누전전류 분석)

  • Yoo, Sang-Ok;Kim, Doo-Hyun;Kim, Sung-Chul
    • Journal of the Korean Society of Safety
    • /
    • v.29 no.6
    • /
    • pp.34-39
    • /
    • 2014
  • This paper is aimed to prevent danger of electrical fire at cattle barn to detect resistive and capacitive leakage current component for wiring type and length. In order to analysis for electric leakage component for cattle barn sizes and normal buildings, this paper was studied field state investigation which are at cattle barn companies(10 companies) in Cheong-won location and normal buildings at Nam-bu market in Jeon-ju location. Market to deduce the problems of electric leakage component is analyzed. The resistive and capacitive leakage current component for wiring type and length is analyzed at Beon-young cattle barn. Results show that electric leakage component suggested in this paper are valuable and usable to electrical fire in leakage current based on environment factor, which will prevent severe damage to human beings and properties and reduce the electrical fires in cattle barn. It is acceptable for electrical equipment use in an cattle barn.

A Simulation Modeling for Rail Potential and Leakage Current Analysis in DC Traction System (직류 전기철도에서의 레일전위 및 누설전류 해석을 위한 시뮬레이션 모델링)

  • Yoon, Yim-Joong;Lee, Jong-Woo
    • Proceedings of the KSR Conference
    • /
    • 2008.11b
    • /
    • pp.196-201
    • /
    • 2008
  • In DC traction systems, a part of feedback current returning through rails becomes leakage current, illumination on a metal laid underground results from the leakage current to ground. To prevent the leakage current on rails, feedback rails almost have insulated with the ground. Insulation between rails and the ground causes that the earth method changes a isolated method in DC traction systems. the rail potential rise results in the isolated method. the rail potential rise causes an electric shock when a person touches the ground and rolling stock. To decrease the rail potential rise and leakage current, there are methods for reducing the feedback resistance and current of rails, increasing the leakage resistance, decreasing the distance between substations. But it are necessary to forecast and analyze the rail potential and amplitude of leakage current. In this paper, we modeled DC traction systems and feedback circuit to simulate the rail potential and amplitude of leakage current using PSCAD/EMTDC that is power analysis program, forecasted the rail potential and amplitude of leakage current about changing various parameters in the electric circuit. By using the simulation model, we easily will forecast the rail potential and amplitude of leakage current in case of a level of basic design and maintenance in electric railway systems, valuably use basic data in case of system selection.

  • PDF

A New Method for Resistive Leakage Current Measurement (새로운 저항성 누전전류 측정 방법)

  • Ham, Seung-Jin;Hahn, Song-Yop;Koh, Chang-Seop
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.8
    • /
    • pp.1397-1404
    • /
    • 2007
  • It is important to measure the resistive component separately from the total leakage current at power distribution line. It is because electric disasters such as electric shock and fire are caused mainly by the resistive component of the total leakage current. In this paper, a new theory for measuring the resistive component separately from the total leakage current is suggested, and is embodied to an actual circuit using operational amplifiers, analog switch and R-C low pass filter. Through experiments for various cases containing both the resistive and capacitive leakage currents, the suggested algorithm is confirmed to be able to measure the resistive leakage current within 4.1% of error even when the capacitive leakage current is much bigger than the resistive one. The suggested method is expected to lower the total cost because it can be realized using simple and cheap devices, and implies the measuring time can be possibly reduced because the resistive leakage current is computed exactly from the signals during only a half period of power voltage.

Development of an Earth Leakage Breaker Operating by Resistive Leakage Current using a Resetable Integrator (적분기를 이용한 저항성 누전전류 작동방식 누전차단기 개발)

  • Ham, Seung-Jin;Hahn, Song-Yop;Koh, Chang-Seop
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.917-918
    • /
    • 2007
  • The former earth leakage breaker is operating by total leakage current which is the vector-sum of resistive leakage current and capacitive leakage current. However, the electric disaster like the electric shock and fire is caused mainly by resistive leakage current. Therefore, the earth leakage breaker is ideal when it is operating by resistive leakage current. In this paper, the theory for finding the component of resistive leakage current from total leakage current is suggested and it is embodied to actual circuit. The resistive leakage current can be found by integrating the total leakage current during half cycle of line voltage. Thus, we can simply find resistive leakage current by using OP-AMP integrators, and we can confirm that the resistive leakage current is computed exactly from total leakage current obtained by resistive leakage current and capacitive leakage current. The results that the earth leakage breaker is operating within regular interrupt time are verified when the former earth leakage breaker's controller circuit is replaced by the proposed controller circuit.

  • PDF

Implementation of Leakage Monitoring System Using ZigBee (ZigBee를 적용한 누전상태 모니터링시스템 구현)

  • Ju, Jae-han;Na, Seung-kwon
    • Journal of Advanced Navigation Technology
    • /
    • v.21 no.1
    • /
    • pp.107-112
    • /
    • 2017
  • In recent years, electric shock accidents due to electric leakage currents of household appliances such as computers, TVs, refrigerators, and LED lights are continuously occurring in homes and industrial buildings. And it is not easy to check the leakage current of each household appliances connected in parallel at the rear end of the module. In addition, the leakage current flowing through the path of the normal current other than the existing current leakage circuit breakers are installed in the distribution box, only the function to cut off the power when the leakage. Therefore, there are various disasters such as electric shock and fire caused by short circuit of household appliances, and the risk of such leakage current is seriously presented. In this paper, we propose a method to implement a leakage monitoring system that can be monitored at all times using Zigbee communication based on IEEE 80215.4, which has advantages in low power and low cost among short range wireless communication systems.