• Title/Summary/Keyword: drinking water distribution pipe

Search Result 39, Processing Time 0.029 seconds

Comparison of Biofilm Formed on Stainless Steel and Copper Pipe Through the Each Process of Water Treatment Plant (정수처리 공정 단계별 스테인리스관과 동관에 형성된 생물막 비교)

  • Kim, Geun-Su;Min, Byung-Dae;Park, Su-Jeong;Oh, Jung-Hwan;Cho, Ik-Hwan;Jang, Seok-Jea;Kim, Ji-Hae;Park, Sang-Min;Park, Ju-Hyun;Chung, Hyen-Mi;Ahn, Tae-Young;Jheong, Weonhwa
    • Korean Journal of Microbiology
    • /
    • v.49 no.4
    • /
    • pp.313-320
    • /
    • 2013
  • Biofilm formed on stainless and copper in water treatment plant was investigated for sixteen weeks. Biofilm reactor was specially designed for this study. It was similar to that of a real distribution pipe. Raw water, coagulated, settled, filtered and treated water were used in this study. The average number of heterotrophic bacteria counts was $1.6{\times}10^4CFU/ml$, $5.8{\times}10^3CFU/ml$, $1.8{\times}10^3CFU/ml$, $1.3{\times}10^2CFU/ml$, 1 CFU/ml, respectively. Density of biofilm bacteria formed on stainless and copper pipes in raw, coagulated and settled water increased above $2.9{\times}10^3CFU/cm^2$ within second weeks while more biofilm bacteria counts were found on the stainless pipe than on the copper pipe. In case of filtered water (free residue chlorine 0.44 mg/L), there was no significant difference in the number of biofilm bacteria on both pipes and biofilm bacteria below $18CFU/cm^2$ were detected on both pipe materials after fifth weeks. Biofilm bacteria were not detected on both pipe materials in treated water (free residue chlorine 0.88 mg/L). According to the results of DGGE analysis, Sphingomonadacae was a dominant species of biofilm bacteria formed on the stainless pipe while the copper pipe had Bradyrhizobiaceae and Sphingomonadaceae as dominant bands. In case of filtered water, a few bands (similar to Propionibacterium sp., Sphingomonas sp., Escherichia sp., and etc.) that have 16S rRNA sequences were detected in biofilm bacteria formed on both pipes after fifth weeks. Stainless pipe had higher species richness and diversity than the copper pipe.

CLPP of Biofilm on Different Pipe Materials in Drinking Water Distribution System (수돗물속에서 관재질에 따른 생물막의 CLPP)

  • Lee Dong-Geun;Lee Jae-Hwa;Lee Sang-Hyeon;Ha Bae-Jin;Ha Jong-Myung
    • Journal of Life Science
    • /
    • v.14 no.6 s.67
    • /
    • pp.891-894
    • /
    • 2004
  • The effect of pipe materials on biofilm communities were investigated by CLPP (community level physiology profile) using Biolog GN plates. Heterotrophic bacterial concentrations were $10^4\;-\;10^6\;CFU/cm^2$ and there was no differences between galvanized iron and carbon steel. Average optical density of Biolog plate was similar between two pipe materials. However, CLPP was different according to the type of pipe materials and exposed times to tap water, and CLPP was independent of bacterial concentration. This represents the differences of bacterial communities with pipes and water contact times.

Numerical Analysis of Mixing Flow in a Small-Scale Water Supply System (간이상수도에서의 혼합유동에 대한 수치해석)

  • Yoo, Young-Hyun;Ki, Hyun;Choi, Jong-Wook;Kim, Sung-Cho;Kim, Yong-Seon;Lee, Yong-Ho
    • Journal of Korean Society of Environmental Engineers
    • /
    • v.31 no.6
    • /
    • pp.460-466
    • /
    • 2009
  • The mixing method of water and chemicals is significant in a small-scale water supply system because drinking water should be supplied with a certain quantity of remaining chemicals maintained. In the present study, the concentration distribution and the mixing index were obtained from four models, which were to find out the optimal mixing method of water and chemicals. The two models brought the good mixing effects out of the four, one for providing chemicals from the center of water supply pipe and the other for setting up the semicircle block at the downstream of the chemicals-providing pipe. As a result, the mixing effect was found out to be increased due to the diffusion and the disturbance of flows. In conclusion, these numerical results are expected to contribute to designing the optimal mixing system.

Internal Corrosion Control of Drinking Water Pipes by pH and Alkalinity Control and Corrosion Inhibitor (수질제어 및 부식억제제에 의한 상수도관의 내부부식 제어)

  • Kuh, Sungeun;Woo, Dalsik;Lee, Doojin;Kim, Juwhan;Ahn, Hyowon;Moon, Kwangsoon
    • Journal of Korean Society of Water and Wastewater
    • /
    • v.20 no.2
    • /
    • pp.215-223
    • /
    • 2006
  • The internal corrosion of water distribution systems is the main cause for the problem of the public health threat as well as water leakage in the damaged pipeline, red water, and odor and taste of the tap water. This study was examined the effect of chemicals used for pH and alkalinity control and corrosion inhibitors for producing the optimal corrosion control method. Corrosion study at different pH and alkalinity indicated that these control using alkaline chemicals was effective in corrosion rate, Fe release reduction, but examined to be increased in turbidity and corrosion-by-products(TTHMs) problems. The turbidity was slightly increased, requiring caution in controlling corrosion with $Ca(OH)_2$. At pH 9.0, TTHMs concentration is increased two times corn pared with non-control of pH. Using the pipe which had experienced 28 years of exposure, iron release was decreased with the corrosion inhibitor. Consequently, pH, Alkalinity control method using alkaline chemicals must be complemented by corrosion inhibitor application for efficient corrosion control.

Correlation between Corrosion Rate and Red Water on Application of Corrosion Inhibitor in Drinking Water Distribution System (배급수 계통에서 부식억제제 적용에 따른 부식과 적수와의 상관관계)

  • Woo, Dal-Sik;Ku, Sung-Eun;Lee, Byung-Doo;Kim, Ju-Hwan;Moon, Kwang-Soon
    • Journal of Korean Society of Water and Wastewater
    • /
    • v.19 no.1
    • /
    • pp.68-77
    • /
    • 2005
  • This study was performed to evaluate the application of corrosion inhibitor and to examine the correlation between corrosion rate and red water in a series of batch tests and a test using auto corrosion monitoring system at A water treatment plant in Gyeonggido. The corrosion study in the auto corrosion monitoring system indicated that Fe concentration decreased by 30~50% and corrosion rate also reduced remarkably with corrosion inhibitor at $1.8mg\;PO_4/L$. After addition of corrosion inhibitor, it was indicated the effective adsorption of the inhibitor on the surface of the pipe line forming a protective film. The corrosion rate increases with the increase in Fe concentration. With $1.8mg\;PO_4/L$ of corrosion inhibitor, the corrosion rate decreased remarkably. Fe concentration had correlation to not only red water problems but also the corrosion rate that actually dissolved into the water, primarily due to the deposition of oxidized iron or other compounds as a scale, which serves as a large reservoir of corrosion by-product. Therefore, corrosion rate can be estimated by Fe concentration. For these reasons, an effective corrosion inhibitor is also an effective red water control reagent. The effect of the corrosion inhibition can last for some time even the application the corrosion inhibitor is discontinued. For the cost effective and efficient corrosion control, the concentration and timing of corrosion inhibitor addition must be determined properly.

The Effects of pH and Alkalinity Adjustment on Internal Corrosion Control and Water Quality in Drinking Water Pipelines (정수의 pH 및 알칼리도 동시 조절이 상수도관의 내부부식 제어 및 수질에 미치는 영향)

  • Lee, Hyun-Dong;Jung, Hae-Ryong;Kwak, Phill-Jae;Chung, Won-Sik
    • Journal of Korean Society of Environmental Engineers
    • /
    • v.22 no.4
    • /
    • pp.661-669
    • /
    • 2000
  • This research was carried out to evaluate effect of metallic release and change of water corrosive indices by the pH and alkalinity adjustment using the SDLS (Simulated Distribution Loop System) which consist of six types of pipe loop with DCIP, PVC, PE, STS304, CP, GSP, respectively, and its effects on water quality changes which were microbes quality(SPC), residual chlorine. THMs and other parameters. And it was to propose optimal criteria of water quality control for the field application. According to the results, water control system by pH and alkalinity adjustment showed the changing of corrosive water and reducing of metallic release rate and it was not affects of THMs formation, microbes regrowth and variation of other parameters. Water quality stability and corrosion control were due to calcium carbonate precipitation film formation of pipe inner by water quality control. Therefore, corrosive water control system by pH and alkalinity adjustment can be attributed to effective water quality management in water distribution system according to water quality stability of pH and TIC(Total Inorganic Carbonate concentration) that affect the precipitation and dissolution of solids.

  • PDF

Comparative study on cleaning effects of air scouring and unidirectional flushing considering water flow direction of water pipes (상수도관의 물 흐름 방향을 고려한 공기주입 세척 및 단방향 플러싱 공법의 세척 효과 비교 연구)

  • Seo, Jeewon;Lee, Gyusang;Kim, Kibum;Hyung, Jinseok;Kim, Taehyeon;Koo, Jayong
    • Journal of Korean Society of Water and Wastewater
    • /
    • v.33 no.5
    • /
    • pp.353-366
    • /
    • 2019
  • This research proposes an optimal flushing operation technique in an effort to prevent secondary water pollutions and accidents in aged pipes, and to improve the cleaning effect of unidirectional flushing. Water flow directions were analyzed using EPANET 2.0, while flushing and air scouring experiments in forward and reverse directions were performed in the field. In 42 experiments, average residual chlorine concentration and turbidity were improved after cleaning compared to before cleaning. It was found that even when the same cleaning method was used, further improvement of cleaning effect was possible by applying air injection and reverse direction cleaning techniques. By means of one-way ANOVA(Analysis of variance), it was also possible to statistically verify the need of actively utilizing air injection and reverse direction cleaning. Based on correlation between turbidity and TSS, the total amount of suspended solids removal was estimated for 874 flushing operations and 194 air scouring operations. The result showed that air scouring used more discharge water than flushing by an average of $4.9m^3$ yet with larger amounts of suspended solids removal by an average of 145.9 g. The result of analysis on turbidity values from 887 flushing operations showed low cleaning effect of unidirectional flushing for the pipes with diameters over 300 mm. In addition, the turbidity values measured during cleaning showed an increasing tendency as pipe age increased. The methodology and results of this research are expected to contribute to the efficient maintenance and improvement of water quality in water distribution networks. Follow-up research involving the measurement of water quality at regular time intervals during cleaning would allow a more accurate comparison of discharge water quality characteristics and cleaning effects between different cleaning methods. To this end, it is considered necessary to develop a standardized manual that can be used in the field and to provide relevant trainings.

The Component Analysis of Foreign Substance Occurred in Water Distribution Networks (상수관망에서 발생하는 이물질의 성분분석)

  • Choi, Min-Ah;Kim, Do-Hwan;Bae, Chul-Ho;Lee, Doojin;Choi, Doo Yong
    • Journal of Korean Society of Environmental Engineers
    • /
    • v.36 no.9
    • /
    • pp.614-623
    • /
    • 2014
  • Customers water quality complaints by foreign substance in local water service can be able to call the main cause bring the distrust for tap water and inhibiting the rate of drinking water. In this study, foreign substances were collected in the target region. Foreign objects were subjected to qualitative and quantitative analysis of compounds and elements components to reveal the cause of detection. Also, resolve the complaints by foreign substance and improve the reliability for tap water providing high quality water supply scheme. Collected substances at the water quality complaint area were included in inorganic compounds due to internal corrosion and aging pipeline, as well as organic compounds containing a large amount of carbon (C) and oxygen (O) component. To decide and reduce for foreign substance, objective assessment of pipe condition in target area was required.

Development of CCPP(Calcium Carbonate Precipitation Potential) calculating program for corrosion control of drinking water distribution system (상수도관 부식방지를 위한 CCPP(Calcium Carbonate Precipitation Potential) 산정 프로그램 개발)

  • Hwang, Byung-Gi
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.9 no.1
    • /
    • pp.170-175
    • /
    • 2008
  • In this study, we developed the CCPP calculating program, which is a kind of index and can determine whether calcium carbonate would precipitate or not in pipe line of water distribution system. Through 9 complicated procedures, CCPP can be calculated. Assuming pH of equilibrium as a first trial, compare the right-hand-side result with left-hand-side result. If the percentage difference between the two results is less than a prescribed tolerance, the initial assumption for the assumed equilibrium pH is adequate. If the difference is too large, make a different assumption and repeat until a result within the prescribed tolerance is achieved. Plugging the intermediate results into the final equation, we could compute the CCPP. Using Fortran and Visual Basic languages, we developed the program. As a result of application of the program, the water quality of intaking water of Han River is highly corrosive by the index of CCPP.