• 제목/요약/키워드: distance relay algorithm

검색결과 71건 처리시간 0.025초

퍼지추론 시스템을 이용한 지중송전계통 보호용 디지털 거리계전 알고리즘 개발 (Development of Digital Distance Relay Algorithm Using Fuzzy Inference System on Underground Power Cable Systems)

  • 정채균;이종범
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 A
    • /
    • pp.502-503
    • /
    • 2006
  • If the fault occurs on the underground Power cable system, the fault current on the sheath has the influence on all sections because it's returned through earth at the directly grounded point and operation point of SVL(Sheath Voltage Limiter) at joint box. Therefore, the earth resistance and the operation of SVL have an effect on the zero-sequence current. Then the impedance between relaying point and fault point is Increased. That causes the overreach of distance relay. For these reasons, the distance relay algorithm for protecting of the underground power cable systems was developed. It effectively advance the errors using ACI(Advanced Computing Intelligence) technique. In this algorithm, the optimization was performed by fuzzy inference system and genetic algorithm.

  • PDF

웨이브렛을 이용한 혼합송전선로에서의 거리계전 알고리즘 개선 (Improvement of Digital Distance Relaying Algorithm Using Wavelet Transform in Combined Transmission Line)

  • 정채균;김경호;하체웅;이종범;윤양웅
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제52권10호
    • /
    • pp.593-601
    • /
    • 2003
  • Distance realy is tripped by the line impedance calculated at the relay point. Accordingly the accurate operation depends on the precise calculation of line impedance. Impedance can be accurately calculated in case of overhead line. However, in case of power cables or combined transmission lines, impedance can not be accurately calculated because cable systems have the sheath, grounding resistance, and sheath voltage limiters(SVLs). There are also several grounding systems in cable systems. Therefore, if there is a fault in cable systems, these terms will severely be caused much error to calculation of impedance. Accordingly the proper compensation should be developed for the correct operation of the distance relay. This paper presents the distance calculating algorithm in combined transmission line with power cable using wavelet transform. In order to achieve such purpose, judgement method to discriminate the fault section in both sections was proposed using D1 coefficient summation in db4. And also, error compensation value was proposed for correct calculation of impedance in power cables section.

D2D 광고 확산을 위한 최대거리 기반 알고리즘과 최대효율 기반 알고리즘의 성능 분석 (Performance Evaluation of D2D Advertisement Dissemination Algorithms with Maximum Distance and Transmission Efficiency Based Relay Selections)

  • 김준선;이호원
    • 한국정보통신학회논문지
    • /
    • 제19권2호
    • /
    • pp.287-292
    • /
    • 2015
  • 본 논문에서는 사용자들의 밀집도 정보를 기반으로 설정된 목표지역과 릴레이 단말의 수를 제한한 환경에서 광고 확산을 위한 최대 거리 기반 릴레이 단말 선택 알고리즘과 최대 효율 기반 릴레이 단말 선택 알고리즘의 성능을 비교 분석하였다. 최대 거리 기반 릴레이 단말 선택 알고리즘은 단말간의 거리 정보만을 이용하여 릴레이 단말을 선택하고, 최대 효율 기반 릴레이 단말 선택 알고리즘은 설정된 목표지역들을 활용하여 최대 광고 효율을 위한 광고 확산 루트를 설정하였다. 시뮬레이션을 통해 광고를 섹터 수의 변화에 따른 성공적으로 수신한 전체 사용자 수와 전송 효율에 대한 성능을 비교하여, 최대 거리 기반 릴레이 단말 선택 알고리즘 보다 최대 효율 기반 릴레이 단말 선택 알고리즘 성능의 우수성에 대해 분석하였다.

Wavelet 변환을 이용한 디지털 거리계전 알고리즘 (A Digital Distance Relaying Algorithm using a Wavelet Transformation)

  • 강상희;이주훈;남순열;박종근
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제48권10호
    • /
    • pp.1215-1221
    • /
    • 1999
  • A high speed digital distance relaying algorithm based on a Wavelet Transformation is proposed. To obtain stable phasor values very quickly, first, a lowpass filter which has low cutoff frequency is used. Secondly, db2(Daubechies 2) Wavelet which has the data window of 4 samples is used. A FIR filter which removes the DC-offset component in current relaying signals is applied. In accordance with a series of tests, the operation time of the relaying algorithm is less than 3/4 cycles after faults in a 80 [km], 154[kV], 60[Hz] over-head transmission line system.

  • PDF

MATLAB을 이용한 GUI 소프트웨어 개발에 관한 연구 (A Study on the Development of GUI Software using MATLAB)

  • 김병천;김철환
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 A
    • /
    • pp.449-451
    • /
    • 2000
  • Arcing fault on overhead lines can be detected by amplitude of the arc voltage using numerical algorithm. In the case of transient fault, the arc voltage has any high value. In the case of permanent fault, the arc voltage is near zero. Thus, fault distance estimation should be performed by digital distance relay algorithm[3]. The purpose of this study is to build a structure for modeling of arcing fault detection and fault distance estimation algorithm using Matlab programming. Additionally, this algorithm has been designed in Graphical User Interface(GHI). So, this method using GUI interface of Matlab can reduce the number of simulation steps in modeling the distance relay.

  • PDF

과도성분과 상태도를 이용한 거리 계전기의 향상된 Zone 3 알고리즘 (An Enhanced Zone 3 Algorithm of a Distance Relay using Transient Components and State Diagram)

  • 허정용;김철환
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제53권3호
    • /
    • pp.161-167
    • /
    • 2004
  • Zone 3 of the distance relay is used to provide the remote back-up protection in case of the failure of the primary protection. However, the risk lot mal-operations under stressed conditions such as heavy loading, voltage and transient instability is usually high. Zone 3 is used in combination with the derivatives of the voltage, and current, etc to prevent mal-operations. Sometimes, the impedance characteristics that restrict the tripping area of relay are used to avoid the mal-operations due to load encroachment. This paper presents a novel Zone 3 scheme based on combining the steady-state components (i.e. 60Hz) and the transient components (TCs) using a state diagram that visualizes the sequence of studies that emanate from the sequence of events. The simulation results show that the novel zone 3 distance relay elements using the proposed method operates correctly for the various events.

실시간 데이터를 이용한 선로 위험도 산출 알고리즘 및 거리계전기 Zone 3 동작 예측 알고리즘 (Algorithm of Line dangerous Index and Predicting Distance Relay Zone 3 acting time by using real time data)

  • 김진환;이승재;최면송;임일형;임성일;김상태
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.278_279
    • /
    • 2009
  • Nowaday, many people study about Black-Out. In this paper, I introduce how to calculate the Dangerous Index against Black-Out, and prediction of Distance relay error action on Zone 3. we consider the real data by I-PIU which will be set on the system. The dangerous Index is calculated three index about Cascading. The prediction of Distance relay is considered by other facilities of power system. This two algorithm can be used on the center system, when the system is on danger, also on the normal states for security.

  • PDF

최소자승법을 이용한 고속 거리계전 알고리즘 (A High Speed Distance Relaying Algorithm Based on a Least Square Error Method)

  • 강상희;권태원
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제48권7호
    • /
    • pp.855-862
    • /
    • 1999
  • A high speed digital distance relaying algorithm based on a least square error method is proposed. To obtain stable phasor values very quickly, first, a lowpass filter which has very short transient period and no overshoot is presented. Secondly, the least square error method having the data window of 3 samples is used by applying a FIR filter which removes the DC-offset component in current relaying signals. Test results show that the proposed distance relaying algorithm detects most of internal faults within a half cycle after faults in a 154[kV] overhead transmission line system.

  • PDF

리액턴스 효과를 최소한 병행 2회선 송전선로 보호 거리계전 알고리즘 (A Distance Relaying Algorithms Immune to Reactance Effect for Double-Circuit Transmission Line Systems)

  • 안용진;강상희;이승재
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제50권1호
    • /
    • pp.38-44
    • /
    • 2001
  • For double-circuit transmission line systems, an accurate digital distance relaying algorithm immune to the reactance effect is proposed. The apparent impedance calculated by the distance relay is influenced by the combined reactance effect of the fault resistance and the load current as well as the mutual coupling effect caused by the zero-sequence current of the adjacent parallel circuit. To compensate the magnitude and phase of the estimated impedance, this algorithm uses phase angle difference between the zero(positive) sequence of the both side of the system seperated by the fault point. The impedance measuring algorithm presented used a current distribution factor to compensate mutual coupling effect instead of the collected zero-sequence current of the adjacent parallel circuit.

  • PDF

과도성분과 상태도를 이용한 거리 계전기의 향상된 Zone 3 알고리즘 (An Enhanced Zone 3 Algorithm of a Distance Relay using Transient Components and State Diagram)

  • 허정용;김철환;박남옥
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.245-247
    • /
    • 2003
  • Zone 3 of the distance relay is used to provide the remote back-up protection in case of the failure of the primary protection. However, the risk for mal-operations under stressed conditions such as heavy loading, voltage and transient instability is usually high. Zone 3 is used in combination with the derivatives of the voltage, and current, etc to prevent mal-operations. Sometimes, the impedance characteristics that restrict the tripping area of relay are used to avoid the mal-operations due to load encroachment. This paper presents a novel zone 3 scheme based on combining the steady-state components(i.e. 60Hz) and the transient components(TCs) using a state diagram that visualizes the sequence of studies that emanate from the sequence of events. The simulation results show that the novel zone 3 distance relay elements using the proposed method operates correctly for the various events.

  • PDF