An Enhanced Zone 3 Algorithm of a Distance Relay using Transient Components and State Diagram

과도성분과 상태도를 이용한 거리 계전기의 향상된 Zone 3 알고리즘

  • 허정용 (성균관대학교, 차세대전력기술연구센터) ;
  • 김철환 (성균관대학교, 차세대전력기술연구센터) ;
  • 박남옥 (한국전기연구원)
  • Published : 2003.11.13

Abstract

Zone 3 of the distance relay is used to provide the remote back-up protection in case of the failure of the primary protection. However, the risk for mal-operations under stressed conditions such as heavy loading, voltage and transient instability is usually high. Zone 3 is used in combination with the derivatives of the voltage, and current, etc to prevent mal-operations. Sometimes, the impedance characteristics that restrict the tripping area of relay are used to avoid the mal-operations due to load encroachment. This paper presents a novel zone 3 scheme based on combining the steady-state components(i.e. 60Hz) and the transient components(TCs) using a state diagram that visualizes the sequence of studies that emanate from the sequence of events. The simulation results show that the novel zone 3 distance relay elements using the proposed method operates correctly for the various events.

Keywords