• 제목/요약/키워드: contamination control system

검색결과 254건 처리시간 0.03초

Contamination Control of Optical Observation Satellite

  • Lee, Chang-Ho;Lee, Choon-Woo;Cho, Young-Jun;Whang, Do-Soon
    • 한국우주과학회:학술대회논문집(한국우주과학회보)
    • /
    • 한국우주과학회 2008년도 한국우주과학회보 제17권2호
    • /
    • pp.28.3-28.3
    • /
    • 2008
  • Contamination has the potential for degrading the performance of the optical payload beyond the limits defined by mission requirements, therefore it must be considered a risk to system performance and must be mitigated. To mitigate contamination problem, contamination budget is allocated according to the contamination requirements which is derived from contamination effect analysis. Once the contamination budget is allocated, prediction for on-ground and in-orbit contaminants amounts and cleanliness control is performed. In this article, typical contamination control for observation satellite is described.

  • PDF

반도체 클린룸용 증기가습 및 수분무가습 외기공조시스템의 에너지소비량 평가 (An Assessment of Energy Consumption in Steam-Humidification- and Water-Spray-Humidification-Type Outdoor Air Conditioning Systems for Semiconductor Manufacturing Clean Rooms)

  • 김기철;송근수;김형태;유경훈;신대건;박덕준
    • 설비공학논문집
    • /
    • 제25권2호
    • /
    • pp.55-63
    • /
    • 2013
  • For a large-scale semiconductor manufacturing clean room, the energy consumed in an outdoor air conditioning system to heat, humidify, cool and dehumidify incoming outdoor air is very large. In particular, the energy requirement to humidify outdoor air in the winter season is generally known to be high. Recently, in order to overcome the high energy consumption nature of a steam generator in a conventional steam humidification type outdoor air conditioning system, an air washer is often introduced instead of the steam generator in the outdoor air conditioning system, which can be called a water spray humidification type outdoor air conditioning system. Therefore, the assessment and comparison of the annual energy consumed in the steam humidification type and the water spray humidification type outdoor air conditioning systems deserves to be examined in order to reduce the outdoor air conditioning load of a clean room. In the present study, a numerical analysis was conducted to obtain the annual electric power consumption of the two outdoor air conditioning systems. It was shown from the comparison of the numerical results that the water spray humidification type outdoor air conditioning system can reduce about 30% of annual electric power consumption of the steam humidification type outdoor air conditioning system.

종합병원 영상의학과의 감염관리 대한 분석 (Analysis on infection control of general hospital radiology)

  • 신정섭;박철우;전병규
    • 한국방사선학회논문지
    • /
    • 제6권5호
    • /
    • pp.335-342
    • /
    • 2012
  • 경상북도에 소재한 5개 종합병원 영상의학과의 오염도를 계수하고, 오염 원인균을 배양하여 동정하고 이를 토대로 지역사회 영상의학과의 효율적인 감염관리 방안을 모색하고자 하였다. 확인된 표면오염 균주는 Staphylococcus, Micrococcus, Pseudomonas stutzeri, Pseudomonas oryzihabitans로 병원 감염의 원인균으로 알려진 균주였고 영상의학과의 오염원으로 특이성을 가진 균주는 없었다. 조사대상 병원은 비슷한 감염관리교육을 실시하고 있었으나 병원별 오염도의 차이는 유의한 차이를 보였다. 조사대상 병원별 접촉원에 따른 오염도의 차이는 방사선사 사용, 환자사용, 공통사용으로 구분하여 분석한 결과 환자사용이 방사선사사용, 공통사용에 비해 유의하게 높은 오염도를 보였다(p<0.001). 병원별 월평균 검사건수의 차이가 적은 장치는 모든 병원에서 유의한 차이를 보이지 않았으나 이에 비해 촬영건수가 가장 많은 일반촬영장치, 흉부전용촬영대의 오염도가 다른 촬영장치에 비해 오염도가 높았다. 또한 월평균 촬영건수가 많은 A, B, C 병원은 방사선사가 단독으로 사용하거나 또는 환자와 공통으로 사용하는 방사선조사장치, 사무용책상, 출입문 손잡이에서 비교적 높은 오염도를 보였다.

클린룸 국소환경에서 오염원의 위험율에 대한 수치해석적 평가 (Numerical evaluation of risk rates for contamination sources in a minienvironment)

  • 노광철
    • 한국입자에어로졸학회지
    • /
    • 제14권4호
    • /
    • pp.181-189
    • /
    • 2018
  • In this study, the risk rates of different contamination sources of the contaminant in a minienvironment were analyzed through Computational Fluid Dynamics (CFD) simulation. The airflow pattern characteristics can only predict the qualitative variation of contaminant concentration, but cannot evaluate the quantitative variations in the risk rate of sources. From the results, the ambient contamination sources mainly affect wafers in the Front Opening Unified Pod (FOUP), whereas the internal contamination sources mainly affect wafers laid on the robot arm in the minienvironment. And the purging plenum system is very useful in protecting the wafers in the FOUP from contaminants transferred from the Fan Filter Unit (FFU). However, this system is unable to protect the wafers on the robot arm from internal contaminants and the wafers in the FOUP from sources of the interface between the FOUP and the minienvironment.

The AS4059 Hydraulic System Cleanliness Classification System: Replacement of NAS1638

  • 마이크 데이;홍정희
    • 드라이브 ㆍ 컨트롤
    • /
    • 제9권2호
    • /
    • pp.39-45
    • /
    • 2012
  • The NAS 1638 cleanliness classification system was originally developed in 1966 by the US Aircraft Industries of America to both simplify reporting of particle count data and to control the introduction of dirt during the assembly of aircraft fluid systems. The numbers of particles at stated sizes are represented by broad bands where the interval was generally a doubling of contamination. A number of systems have been introduced since this to suit differing requirements. NAS 1638 and AS4059 are used in other industrial sectors such as the Off-shore & Sub-Sea and the Primary Metal Industries. The changes to ISO contamination measurement standards controlled by ISO/TC131/SC6 in 1999 meant that a revision of most of these classification systems was necessary. The body responsible for NAS 1638 decided to withdraw it for new installations and replace it with an update of an existing standard, SAE AS 4059. This paper details the philosophy behind the contamination coding systems, the reasons for the changes to the ISO contamination standards and explains the workings of AS 4059, the replacement for NAS 1638. It goes on to detail the latest changes to this standard.

The Effects of Slider Design on Thermal Asperity Rejection Capability

  • Choa, Sung-Hoon;Vinod Sharma;Kim, Seong-Hoon
    • Journal of Mechanical Science and Technology
    • /
    • 제15권3호
    • /
    • pp.281-290
    • /
    • 2001
  • Particle contamination has been an ongoing problem affecting the reliability of the magnetic hard disk drives. Especially the recent use of MR head requires much tighter control of particle contamination due to thermal asperity (TA) phenomenon. In this study, the effects of slider air bearing surface design of TA reduction capability were investigated by manufacturing two types of sliders. Numerical methods were used to simulate the motion of particles in the head/media interface. Experiments were conducted to verify the results predicted by the numerical simulation. Drives were built and exposed to particle contamination using a particle injection chamber, which turned out to be a very simple and reliable particle generation method over conventional aerosol technique. Then the number of TA generated in the drives was recorded and compared. Also the contacts between slider and particles were investigated by acoustic emission study. It was found that a new ABS design, which has aerodynamic U-shaped rail and central flow passage, was beneficial in reducing the particle contamination on the slider.

  • PDF

A SE Approach to Designing and Developing of Motion Control for Radioactive Waste Decontamination

  • Ngbede, Utah Michael;Olaide, Oluwasegun Adebena;Jung, Jae Cheon
    • 시스템엔지니어링학술지
    • /
    • 제17권1호
    • /
    • pp.11-20
    • /
    • 2021
  • Decontamination of systems, structures and components (SSC) during the decommissioning of a Nuclear Power Plant (NPP) can be for a variety of reasons. The main reasons for decontamination are: to reduce the contamination of SSC to a reasonably low level, to reduce the potential for the spread of contaminants into the environment and to reduce the cost of disposal due to the reduced level of contamination in a particular SSC. The decontamination technique can be aggressive or non-aggressive depending on the intent after the decontamination process. Aggressive decontamination technique is used when the intent is not to reuse the SSC while a non-aggressive decontamination technique is used with the intent of SSC reuse. For different SSCs there are different decontamination techniques that can be used, each having its own advantages and drawbacks. Metal components such as pipes in the nuclear power plant account for a large amount of nuclear wastes generated. Some of these wastes can be reused if the contaminant level is reduced to an acceptable level. Laser ablation is a non-aggressive decontamination technique that can be used to reduce the contamination in pipes to an acceptable level with no secondary waste generated during the process. The operation and control of a laser ablation device must be precise to achieve a high decontamination factor. This precision can be achieved by a well-designed motion control system. For this purpose, a motion control system was developed consisting of two parts: the first part being the precise control of the laser ablation device inside the pipe and the second part is the control of the laser ablation device outside the pipe. This paper describes the Systems Engineering approach for the development process of a motion control system for the Laser decontamination system.

반도체 클린룸용 배기 열회수식 외기공조시스템의 에너지소비 수치해석 (Numerical Analysis on Energy Consumption of an Exhaust Air Heat Recovery Type Outdoor Air Conditioning System for Semiconductor Manufacturing Clean Rooms)

  • 송근수;유경훈;김형태
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.1306-1311
    • /
    • 2009
  • In recent semiconductor manufacturing clean rooms, in order to improve clean room air quality, air washers are used to remove airborne gaseous contaminants such as $NH_3$, SOx and organic gases from the outdoor air introduced into clean room. Meanwhile, there is a large amount of exhaust air from a clean room. From an energy conservation point of view, heat recovery is therefore useful for reducing the outdoor air conditioning load for a clean room. Therefore it is desirable to recover heat from the exhaust air and use it to reheat the outdoor air. In the present study, numerical analysis and experiment was conducted to simulate the amount of energy reduction of exhaust air heat recovery type air washer system. The present numerical results showed good agreement with the results of the experimental data.

  • PDF

반도체 클린룸용 배기 열회수식 에어와셔 시스템의 에너지절감에 관한 수치해석 (Numerical Analysis on Energy Reduction of an Exhaust-Air-Heat-Recovery Type Air Washer System for Semiconductor Manufacturing Clean Rooms)

  • 송근수;김형태;유경훈;손승우;신대건;김영일
    • 설비공학논문집
    • /
    • 제22권10호
    • /
    • pp.697-703
    • /
    • 2010
  • In recent semiconductor manufacturing clean rooms, air washers are used to remove airborne gaseous contaminants from the outdoor air introduced into a clean room. Meanwhile, there is a large amount of exhaust air from a clean room. From an energy conservation point of view, heat recovery is useful for reducing the outdoor air conditioning load required to maintain a clean room. Therefore it is desirable to recover heat from the exhaust air and use it to cool or heat the outdoor air. In the present study, numerical analysis was conducted to evaluate the recovered heat of an exhaust air heat recovery type air washer system, which is the key part of an energy saving outdoor air conditioning system for semiconductor clean rooms. The present numerical results showed relatively good agreement with the available experimental data.