• Title/Summary/Keyword: clean room

Search Result 287, Processing Time 0.029 seconds

A study on the food clean room system observing the regulations of HACCP (HACCP의 환경 최적화를 위한 식품 클린룸 설계에 관한 연구)

  • Won, Young-Jae;Suh, Kee-Won
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.520-526
    • /
    • 2009
  • This study proposed the optimum design values for the biological clean room system observing the regulations of Hazard Analysis Critical Control Point (HACCP). Even though the standard for industrial clean room system has been well established, the basis for biological food clean room system is the first stage. In order to prevent the contaminations in advance for food storages, processes, and distributions, the criterion of Hazard Analysis Critical Control Point is positively required. This study also suggested the possible ways of how to avoid the hazardous contaminations.

  • PDF

A study on the design and construction of operating room (병원 수술실 설계 및 시공에 관한 연구)

  • Jung, Eul-Kyu;Oh, Jung-Keun
    • Journal of the Korea Institute of Building Construction
    • /
    • v.3 no.2
    • /
    • pp.103-110
    • /
    • 2003
  • In the early 1990's the clean room system was a new trend of the operating room. This is the concept using in seminconductor plants. That is what the space around the operating table so clean as it remove contaminations with circulation of interior air. These articles describe the standard of interior construction and drawing details.

Estimation Model of Energy Expenditure of Working in a Clean Room for Manufacturing Embedded Needles by Ergonomic Programs (인간공학 프로그램에 의한 매선 제작 청정실작업의 에너지소모량 예측 모델)

  • Chung, Tae-Eun
    • Korean Journal of Computational Design and Engineering
    • /
    • v.21 no.1
    • /
    • pp.69-77
    • /
    • 2016
  • The purpose of this study is to estimate the energy expenditure of working in a clean room for manufacturing embedded needles by ergonomic programs. Embedding needle is one of medical devices and it should be manufactured in a clean room. 3D static strength prediction program was used to analyze the slow movements during embedding needle manufacturing in a clean room. Also the energy expenditure prediction program was used to estimate energy expenditure rates for materials handling tasks to help assure worker safety and health in clean room. The energy expenditures of the tasks were calculated using prediction equations derived from empirical data. The energy expenditure rate of 3.09 kcal/min in a clean room didn't exceed the 3.5 kcal/min action limit guideline for an average 8-hour day set by the National Institute for Occupational Safety and Health (NIOSH). Energy consumption was calculated on the same working conditions as EEPP program, using an average body weight of female 20 years old to 59 years who would be the candidates of the real workers.

A Study on the appliance of performance based design to the automatic fire alarm system in clean room facility (클린룸 자동화재탐지설비의 성능위주 방재설계 적용에 관한 고찰)

  • Kim, Dong-Sung;Hwang, Cheol-Seung;Lee, Sang-Gon;Cho, Cheol-Won;Lee, Te-Shik
    • 한국방재학회:학술대회논문집
    • /
    • 2007.02a
    • /
    • pp.513-517
    • /
    • 2007
  • This study is to establish the appliance model for the automatic fire alarm system in clean room within the framework of the performance based design. Because of the environmental and dimensional characters of clean room, this space is exposed to fire and toxic damage, so it is very important to notify the occupants of these dangerous situations.

  • PDF

HACCP의 환경 최적화를 위한 식품 클린룸 설계에 관한 연구

  • Won, Yeong-Jae
    • Air Cleaning Technology
    • /
    • v.23 no.3
    • /
    • pp.1-9
    • /
    • 2010
  • This study proposed the optimum design values for the biological clean room system observing the regulations of Hazard Analysis Critical Control Point (HACCP). Even though the standard for industrial clean room system has been well established, the basis for biological food clean room system is the first stage. In order to prevent the contaminations in advance for food storages, processes, and distributions, the criterion of Hazard Analysis Critical Control Point is positively required. This study also suggested the possible ways of how to avoid the hazardous contaminations.

  • PDF

On the Characteristics of the Flow with Opening and Shutting of Access Panels in a Clean Room (Access Panel 개폐에 따른 청정실내 유동특성)

  • Park, M.S.;Lee, Jae-Heon;Ahn, K.H.;Kim, J.H.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.5 no.1
    • /
    • pp.55-64
    • /
    • 1993
  • A numerical investigation has been carried out for the two-dimensional flow and pressure characteristics in a clean room equipped with two kinds of filters and four access panels. The distributed pressure resistance concept was applied to describe the momentum loss in filters and access panels. As a result, the velocity profile in the clean room became rather smooth by the presence of access panels. Furthermore, the average pressure drop of each access panel reached the same value so that the ratio of the flow rate should be the same at any zone. The closing of an access panel with maintaining the other access panels being opened had influenced on the velocity distribution in lower two thirds of left half space of the clean room.

  • PDF

Airflow Characteristic Experiments for the Upper Plenum Design of Clean Room (클린룸의 상부 플레넘 설계를 위한 유동특성 실험)

  • Oh, M.D.;Bae, G.N.;Kim, S.C.;Lee, C.S.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.1 no.4
    • /
    • pp.276-289
    • /
    • 1989
  • The airflow characteristics in both the upper plenum and the clean space of clean room are investigated by measuring the pressure distribution of the upper plenum and the velocity profile in the clean space, at the various conditions of the supplied airflow rate, the volume of upper plenum and the air supply type. The performance of vertical air supply type and horizontal air supply type is analyzed in terms of the airflow uniformity which is frequently used in indicating the clean room performance, and the relations among the volume of upper plenum, the supplied airflow rate and the airflow uniformity are confirmed. The results of this experimental study can be applied to the designing of the upper plenum of clean room.

  • PDF

A Study on the Pattern for the Clean Room Garment of the Overall Type (오버롤(Overall)형 방진복의 패턴설계에 관한 연구)

  • Na, Mi-Hyang;Jang, Kyung-Jin;Lee, Yeun-Soon
    • Korean Journal of Human Ecology
    • /
    • v.6 no.2
    • /
    • pp.121-131
    • /
    • 1997
  • This study was to design the clean room garment which fits for a body and adjusts well to the action. We examined the body's changes in action through a body measurment and made a sample of the clean room garment to which had adapted the body's changes in action and evaluated the function and the appearance compared with the existing the clean room garment. The followings were summery of the results : 1. Back intersyce breadth decreased, trunk length increased and the other parts were not change. At a posture of raising hands($M_3$) in comparison with an upright posture($M_0$). Back intersyce breadth, hip length and knee length increased and the other parts were a little change. At a bowing posture($M_2$) in comparison with an upright posture($M_0$). Back hip girth, knee length, hip length and leg length increased and the other parts were not change. At a working posture on a chair($M_1$) in comparison with an upright posture($M_0$). 2. The overall clean room garment was made increasing on the changes of part of a body through measuring and body measurement. 3. From the test of the function, it became known that the devised clean room garment was superior to the existing one in the parts of neck, shoulder, armpit and elbow at a working posture on a chair($M_1$), in the parts of neck, shoulder, and armpit at a bowing posture($M_2$), and the armpit at a posture of raising hands($M_3$). The appearance was better on the whole. 4. From the examination of photographs, the waist line of the devised clean room garment was not so much pulled up as that of the existing one on moving. And when sitting down on a chair, the waist line of the existing one was pulled down while that of the devised one had no change. As above, we investigated the actual conditions of wearing the clean room garment and measured the body's changes according the various actions. So we applied these results to the devised clean room garment but we couldn't research the clean mom effect of it owing to not obtaining the measuring instrument. The aspect of ergonomics liked the feeling of wearing and fitted to the action must be given consideration to the clean room garment, and simultaneously the dust-resistant effect must be taken into consideration in order to improve the quality of the goods. Therefore, we think it should be continued the research on the dust-resistant effect, material, washing method, quality control, and size along with the aspect of ergonomics.

  • PDF

A Survey on the Actual Wearing Condition of Clean Room Wears (Clean Room Wear의 착용실태에 관한연구)

  • 김경화
    • Journal of the Korean Society of Costume
    • /
    • v.48
    • /
    • pp.117-132
    • /
    • 1999
  • This study is focused on the questionaries regarding the physiological comfort and body fitness and freedom of movement for clean room smock and intended to present the basic information in designing more comfortable clean room wear through seizing the discomfort of wearet. The study is designed to survey and analyze the actual wearing condition and its problem applied to 400 workers assigned with two semiconductors manufacturing plants. The result of survey are as follows. 1. Clean room workers bras panties running shirts and 내찬 the as basic underwear since they absorb sweat protect their bodies and make them feel safe and comfortable throughtout the whole year. 2. With regard to body fitness most of the subject assessed it to be suitable but the girth of neck waist and hood is founded to be tight in many cases. 3. Most important selecting criteria of clean room smocks are adaptability of movement body fitness and carrying-ability. Most of repondents prefer side zipper and rib-knitted fabric as the fastening system. 4. As for freedom of movement it is disclosed that the subjects showed more or less of their complaints against its wearing easiness for parts of waist neck armpit and slacks adaptability and adaptability of movement.

  • PDF

A Study on the Phenomena of Dust Removal by the Layout Changes in the Turbulent Type Clean Room (난류형 클린룸내의 Layout 변화에 따른 분진제거 특성에 관한 연구)

  • Kim, Yeon-Hui
    • Journal of the Korea Construction Safety Engineering Association
    • /
    • s.41
    • /
    • pp.80-87
    • /
    • 2007
  • The purpose of this paper is to investigate the removal efficiency of fine dusts as the configuration condition of machinery and equipments in Clean Room and to analyze the flowing behaviors of fine dusts as the layout of Clean Room. The layout of the Clean Room was classified into side layout type, 2 center line type and center concentration type layout, and the flow rates used in this research were 0.22m/s, 0.44m/s and0.80m/s. Dust removal efficiency as layout change was decreased 37% for side layout type, 31% for 2 centerline type and 20% for center concentration type layout at the flow rate of 0.22m/s, compared with the state without machinery and equipments in Clean Room. The efficiency was decreased 42% for side layout type,22% for 2 center line type and 8% for center concentration type layout at the flow rate of 0.44m/s, and decreased 20% for side layout type, 18% for 2 center line type and 10% for center concentration type layout at the flow rate of 0.80m/s. According to the result of dust removal behavior, $0.3\mum$, $1\mum$and $3\mum$dust except for $5\mum$showed the higher change of the behavior in side layout type than in center concentration type layout due to the change of air flow. It was confirmed that removal behavior depends on the layout of machinery and equipments as the dust size decreases.

  • PDF