• Title/Summary/Keyword: characteristics of current limiting

Search Result 323, Processing Time 0.027 seconds

Analysis on Current Limiting and Magnetizing Characteristics Due to Winding Locations of Superconducting Fault Current Limiter Using E-I Core (E-I철심을 이용한 변압기형 초전도한류기의 권선 위치에 따른 전류제한 및 자화특성 분석)

  • Kim, Bo-Hee;Choi, Sang-Jae;Lim, Sung-Hun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.30 no.2
    • /
    • pp.106-110
    • /
    • 2017
  • This paper compared current limiting characteristics of superconducting fault current limiter (SFCL) using E-I core due to the location of windings. Since E-I core has three legs and two magnetic paths, the current limiting characteristics of SFCL were expected to be affected by the installation location of windings, either center leg or right/left leg. To analyze its characteristics, the electrical equivalent circuit of the SFCL were derived and the electromagnetic analysis for the SFCL with the designed structure were performed. From the short-circuit tests, the hysteresis curve and the voltage-current trajectory of the SFCL due to the installation location of windings were extracted and compared each other. The SFCL with windings in the center leg of E-I core was shown to be larger magnetizing inductance compared to the one with windings in the right or left leg of E-I, which was analyzed from the hysteresis curve. In addition, larger decreased fault current right after the fault occurrence in the SFCL with windings in the center leg of E-I core was confirmed than the SFCL with windings in the right or left leg of E-I.

Analysis on Current Limiting and Recovery Characteristics of a SFCL Dependent on Magnetic Coupling of Shunt Reactors (션트리액터의 자기결합유무에 따른 초전도전류제한기의 전류제한 및 회복특성 분석)

  • Lim, Sung-Hun;Ahn, Jae-Min;Kim, Jin-Seok;Moon, Jong-Fil;Kim, Jae-Chul
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.10a
    • /
    • pp.277-279
    • /
    • 2008
  • The current limiting and recovery characteristics of a superconducting fault current limiter (SFCL) using shunt reactors were analyzed. Generally, the shunt reactor has a role to distribute the even voltage drop between high-Tc superconducting (HTSC) elements comprising the SFCL. However, the shunt reactors magnetically separated was not contributed to the equal voltage distribution between the HTSC elements. Through the experiments for the SFCL with both the magnetically coupled and magnetically uncoupled shunt reactors, the magnetically coupled shunt reactors were confirmed to improve the current limiting and recovery characteristics of the SFCL.

  • PDF

EMTDC simulation for current limiting characteristics of the resistive and inductive SFCL (저항형과 유도형 한류기의 전류제한특성에 대한 EMTDC 해석)

  • 최효상;황시돌;현옥배
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1999.05a
    • /
    • pp.255-258
    • /
    • 1999
  • We investigated the current limiting characteristics of resistive and inductive SFCLs with 100 $\Omega$ of quench impedance for a single line-to-ground fault. which accounts for about 70% of the total power line faults, in the 154 kV transmission system. The fault simulation at the phase angles 0$^{\circ}$, 45$^{\circ}$, and 90$^{\circ}$ showed that the resistive SFCL limited the fault current less than 15 kA without any DC component after one half cycle from the instant of the fault. On the other hand, the inductive SFCL suppressed the current below 12 KA, but with 3 kA of DC component which decreased to zero in 5 cycles. We concluded that the inductive SFCL had higher performance in current limiting but the resistive SFCL was better from the view point of DC components.

  • PDF

Fabrication and characterization of fault current limiting devices made of stabilizer-free coated conductors (Stabilizer-free 초전도 선재를 이용한 한류 소자 제작 및 특성 시험)

  • Yim, Seong-Woo;Park, Chung-Ryul;Yu, Seong-Duck;Kim, Hye-Rim;Hyun, Ok-Bae
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2009.06a
    • /
    • pp.371-371
    • /
    • 2009
  • For the application of superconducting wires to fault current limiting devices, it is required that they have a high rated voltage when a fault occurs. Stabilizer-free coated conductors, particularly, shows a good performance for the high rated voltage, which is beyond 0.6 V/cm. In this study, using the stabilizer-free coated conductors, we made fault current limiting devices and examined their characteristics. Fault current limiting devices were fabricated with a shape of the cylinder of a mono-filar coil winding. Stabilizer-free coated conductors were wound along the mono-filar coil line and the terminal parts between the wire and metal were soldered using In solder. Two kinds of devices were fabricated by a different method in the terminal joint, one was made by a soldering and the other was made by a soldering-free joint. Critical currents and resistance at the joint parts were measured. In addition, long-time current flowing tests were also carried out for the characterization of the fault current limiting devices.

  • PDF

Quench Behaviors of Superconducting YBCO Films for Fault Current Limiter Using Magnetic Fields (자기장이 인가된 YBCO 박막형 한류기의 ?치 특성)

  • 박권배;이방욱;강종성;오일성;최효상;현옥배
    • Proceedings of the Korea Institute of Applied Superconductivity and Cryogenics Conference
    • /
    • 2002.02a
    • /
    • pp.365-367
    • /
    • 2002
  • A serious problem in using YBCO films for fault current limiter is inhomogeneities caused by imperpect manufacturing. So simultaneous quenches are a difficult problem which elements for current limiting are connected in series for increasing voltage ratings. We investigated extended electric field - current characteristics for current limiting element of YBCO film when 0-130mT magnetic field is applied. And quench characteristics were investigated in over all element and between elements of YBCO films. From the experiments, it was shown that applied magnetic fields using solenoid coil induced uniform quench distribution for over all stripes and simultaneous quench in all elements for current limiting of YBCO film was realized.

  • PDF

Simulation for current limiting characteristics of the resistive and inductive SFCL with line-to-ground fault

  • Choi, Hyo-Sang;Hwang, Si-Dole;Kim, Sang-Joon;Han, Byoung-Sung
    • Progress in Superconductivity
    • /
    • v.1 no.1
    • /
    • pp.73-80
    • /
    • 1999
  • We investigated the current limiting characteristics of resistive and inductive SFCLs with 100 $\Omega$ of impedance for line-to-ground faults in the 154 kV transmission system. The fault simulation at the phase angles $0^{\circ}$, $^45{\circ}$, and $90^{\circ}$ showed that the resistive SFCL limits the fault current less than 17 kA without any DC component after one half cycle from the instant of the fault. On the other hand, the inductive SFCL suppresses the current below 14 kA, but with 5 kA of DC component which decreases to zero in 5 cycles. We concluded that the inductive SFCL has higher performance in current limiting effect, but the resistive SFCL was better from the viewpoint of less DC components.

  • PDF

Analysis on Fault Current Limiting Characteristics of a Flux-Lock Type HTSC Fault Current Limiter with Hysteresis Characteristic (히스테리시스 특성을 고려한 자속구속형 고온초전도 사고전류 제한기의 사고전류 제한특성 분석)

  • Lim, Sung-Hun;Choi, Myoung-Ho
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.2
    • /
    • pp.94-98
    • /
    • 2007
  • The fault current limiting characteristics of a flux-lock type superconducting fault current limiter (SFCL) considering hysteresis characteristics of a flux-lock reactor, which is an essential component of the flux-lock type SFCL, were investigated. In the normal state, the hysteresis loss of iron core in the flux-lock type SFCL does not happen due to its winding's structure. From the equivalent circuit for the flux-lock type SFCL and the fault current limiting experiments, the hysteresis curves could be drawn. Through the hysteresis curves together with the fault current level due to the inductance ratio between the primary and the secondary windings, the increase of the number of turns in the secondary winding of the flux-lock type SFCL made the fault current level increase. On the other hand, the saturation of iron core was prevented.

Current Limiting Characteristics of Flux-Lock Type High-TC Superconducting Fault Current Limiter According to Fault Angles (사고각에 따른 자속구속형 전류제한기의 전류제한특성)

  • Park, Hyoung-Min;Lim, Sung-Hun;Cho, Yong-Sun;Park, Chung-Ryul;Han, Byoung-Sung;Choi, Hyo-Sang;Hyun, Ok-Bae
    • Proceedings of the KIEE Conference
    • /
    • 2004.10a
    • /
    • pp.12-14
    • /
    • 2004
  • We investigated current limiting characteristics of the flux-lock type high-Tc superconcting fault current limiter(HTSC-FCL) according to fault angles. The Flux-lock type HTSC-FCL consists of primary and the secondary copper coils that are wound in parallel each other through the iron core and YBCO thin flim. In this paper, the current limiting characteristics of the flux-lock type HTSC-FCL according to fault angles in case of the subtractive and additive polarity windings were compared and analyzed. From the results, the flux-lock type HTSC-FCL could limit more quickly fault current as the fault angles increased irrespective of the fault angles. On the other hand, the initial power burden of HTSC element after a fault happened increased as the fault angles increased. In addition, it was confirmed that the resistance of flux-lock type HTSC-FCL in case of subtractive polarity winding was more increased than that of additive polarity winding and that the peak current of fault current in case of subtractive polarity winding was larger than that of the additive polarity winding case.

  • PDF

Hysteresis Characteristics of a SFCL using a Magnetic Coupling of Coils with an Iron Core of Two Magnetic Paths (두 개의 자기경로 철심을 갖는 코일의 자기결합을 이용한 초전도 전류제한기의 히스테리시스 특성)

  • Lim, Sung-Hun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.22 no.12
    • /
    • pp.1073-1077
    • /
    • 2009
  • The iron core, which comprises the superconducting fault current limiter (SFCL) using magnetic coupling of coils, can be operated in the saturation region, especially at the initial fault period. This operation of the iron core in the saturation region deteriorates the fault current limiting operation of the SFCL. To solve the saturation problem of the SFCL using magnetic coupling of coils, the iron core with two magnetic paths, which has an air-gap in one of them, was adopted. In this paper, the hysteresis characteristics of SFCL using magnetic coupling of coils, which were wound in the iron core with two magnetic paths, were analyzed. Through comparative analysis on the hysteresis characteristics of the iron core comprising SFCL, the hysteresis characteristics of the iron core with two magnetic paths were confirmed to be kept in the non-saturation region during the fault period and thus, the effective fault current limiting operation of the SFCL using the magnetic coupling of coils could be performed.

The Analysis of Characteristics of Flux-Lock Type SFCL with Adjustable Inductance Level in Current Limiting Operation (인덕턴스 조정에 따른 자속구속형의 전류제한특성분석)

  • Lee, Na-Young;Choi, Hyo-Sang;Park, Hyoung-Min;Cho, Yong-Sun;Nam, Gueng-Hyun;Lim, Sung-Hun;Park, Chung-Ryul
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.157-158
    • /
    • 2005
  • Superconducting fault currents(SFCLs) are expected to improve not only reliability but also stability of real power systems. The analysis on the single line-to-ground fault of the integrated three phase flux-lock type SFCL, which consists of three flux-lock reactor wound on an iron core in each single phase and three YBCO thin films, was investigated in current limiting operation characteristics. We compared 21turn numbers with 42turn numbers according to wound turn numbers each the coil 2 under the additive polarity winding operation between coil 1 and coil 2. The three phase flux-lock type SFCL using an iron core differently operates general three phase resistive SFCLs. When a single line-to-ground fault occurred, the SFCL's three units were quenched after fault onset. We confirmed effective current limiting operation characteristics with adjustable inductance level.

  • PDF