• Title/Summary/Keyword: burner tilt

Search Result 4, Processing Time 0.017 seconds

Study on application of domestic development DCS for S/H temp in the power plant (발전소 과열증기 온도제어 시스템의 국산 DCS 적용에 관한 연구)

  • 박익수;김은기;박성혁;이기원
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 1992.10a
    • /
    • pp.292-296
    • /
    • 1992
  • There are lots of disturbance in the super heater temperature control system of power plant boiler as follows. 1.Burner light off. 2.Excess Air. 3.Burner tilt. 4.G.R fan flow. Temperature control system of super heater in the power plant has delay time about 5 min. So it is difficult to control the super heater temperature in the power plant. This paper show us the application of domestic development DCS to control the super heater temperature in seoul #5 thermal power plant unit.

  • PDF

Conceptual designs and characteristic of the fuel handling and transfer system for 150 MWe PGSFR and 1400 MWe SFR burner reactor

  • Kang-Soo Kim;Jong-Bum Kim;Chang-Gyu Park
    • Nuclear Engineering and Technology
    • /
    • v.54 no.11
    • /
    • pp.4125-4133
    • /
    • 2022
  • KAERI (Korea Atomic Energy Research Institute) developed the conceptual design of PGSFR (Prototype Gen-IV Sodium Cooled Fast Reactor) and Burner Reactor. Since the reactor characteristics of the PGSFR and Burner Reactor are different, the shape, size and the arrangement of the main components in the reactors must be different. Therefore, the conceptual design for the fuel handling and transfer systems needs to be performed coinciding with the structure of the reactor. Especially, because a redan structure dividing hot and cold pool is installed in the reactor vessel, the conceptual design of the fuel handling and transfer system largely changes depending on the location of the redan structure. Various elements of the conceptual design and an integral arrangement for the fuel handling and transfer system were arranged according to the characteristics, sizes and shapes of the reactors. In this paper, the conceptual designs of the fuel handling and transfer system for PGSFR and Burner Reactor are described. Especially, an A-frame method is selected as the fuel handling and transfer system for the Burner Reactor, considering the layout of the internal structure. The tilt angle, diameter and length of A-frame is determined and the strength evaluation of the A-frame is performed.

A Study on Heat Trasfer Characteristics of Smooth and Ribbed Tubes for Boiler (보일러용 裸管 및 리브붙이管 의 熱傳達 特性 에 관한 硏究)

  • 김종보;한승탁
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.9 no.6
    • /
    • pp.699-705
    • /
    • 1985
  • Heat transfer characteristics in terms of the tube wall-temperature and the enthalpy have been investigated utilizing ribbed (rifled) tubes in order to enhance heat transfer performance. Considerations were given for the cases of smooth tubes in order to compare with the case of ribbed tubes. The tilt angle of the experimental tubes are from 0.deg. to 90.deg. , in order to simulate the boiler water tubes having 15.deg.-90.deg. inclined angle in boiler nose and studded tubes (burner zones), Natural convection and forced convection (Re=1810) conditions were considered in the experiments. The experimental results for the effect for the tube inclination through a natural convection and forced convection are presented and it is shown that ribbed tubes permit an appreciable increase in heat transfer coefficients and consequently it means substantial reductions in boiler water wall tubes and heat exchanger surface areas.

Reduction of the Reheater Spray for Coal Fired Thermal Power Plant (석탄화력발전소의 재열저감수 저감방안)

  • Kim, Hyung-Deok;Koh, Churl-Kyun;Moon, Seung-Jae
    • Plant Journal
    • /
    • v.9 no.2
    • /
    • pp.46-50
    • /
    • 2013
  • When four operation parameters are adjusted, the temperature of reheater steam is around the designed operator temperature and the decrease of reheater spray flow rate is achieved. As a result, the decrease of thermal efficiency also can be prevented. To keep the reheater exit temperature on the designed value and decrease the use of reheater spray flow rate, the control of four operation parameters is considered and applied in the operation of a thermal power plant.

  • PDF