기존 학교 건물의 외피 성능 개선 방안에 관한 연구 (The Improvement of Building Envelope Performance in Existing School Building)

  • 방아영;박세현;김진희;김용재;김준태
    • KIEAE Journal
    • /
    • 제15권4호
    • /
    • pp.69-76
    • /
    • 2015
  • Purpose: This study is to investigate the effects of facade insulation and window remodeling of an existing old middle school building on the reduction of energy consumption. Method: To analyze energy performance of building, using DesignBuilder v3.4, building energy simulation tool based EnergyPlus engine. Energy consumption and problem of target building was analyzed based on data and survey. Based on building energy simulations it analyzed the variation of energy demand for the building according to U-value of wall, glazing properties and external shading devices. Result: When insulation of building was reinforced, cooling and heating load was decreased. Glazing properties that minimize cooling and heating energy consumption were analyzed. In conclusion, it is important to choose SHGC and U-value of window fit in characteristic of target building. Setting external blind for cooling load decreases 5%.

공동주택 외피의 열교영향을 고려한 상당열관류율 및 연간 에너지소비성능 평가 연구 (A study on the annual energy performance of apartment building with the equivalent U-value of envelope considering the effect of thermal bridges)

  • 김동수;윤종호;신우철;곽희열
    • KIEAE Journal
    • /
    • 제12권3호
    • /
    • pp.41-46
    • /
    • 2012
  • The building envelope is important specially for saving energy consumption of residential buildings. but Apartment houses in Korea commonly have inside insulation system which have constantly arisen thermal bridges, the risk of heat loss, as a necessity. This study aims to evaluate integrated insulation performance according to the different shapes of external walls, adjacent to windows. The thermal performance analysis was carried out by Equivalent U-value and using the three-dimensional heat transfer computer simulation (TRISCO-RADCON), under nine different cases of comparing among three each of different bases(current standard model, 30percent energy saving model and 60percent energy saving model). The heating and the cooling load were also compared between two cases (standard U-value and Equivalent U-value) of three each of different bases, using the Building energy simulation which is based on DOE-2.1 analysis. As results, it turns out that if the Equivalent U-value is considered on the envelope analysis, the heat flow loss will be increasing more than the standard U-value, and if heat insulation property of the residential building reinforced rather than current, the rate of influences on the thermal bridges would be extremely expanded. In addition, it is shown that annual heating loads of the apartment house with applied Equivalent U-value substantially increased by more than 15 percent compared to those with the existing U-value, but annual cooling loads were negligibly affected.

Energy Sustainability of an Integrative Kinetic Light Shelf Unit

  • Han, Seung-Hoon
    • KIEAE Journal
    • /
    • 제15권3호
    • /
    • pp.15-20
    • /
    • 2015
  • Purpose: Suggesting a working prototype of a kinetic light shelf unit and revealing its energy efficiency by a series of building performance simulations were presented. Recently, kinetic building envelope has been an emerging technology as an innovative way to control exterior building environment, but products from many researches about the facade could not been reached to the industrialization so far. That is because its initial installation, operation and maintenance costs are still too high to use for the practical field, although buildings using kinetic envelopes could decrease their energy consumption significantly. This narrow point of view needs to be reconsidered, since buildings require great amount of energies to run their functions through the whole life and using better building components can lead to achieve much more benefits in aspects of the lifecycle cost (LCC). Method: A series of certified simulation tools like Ecotect and Green Building Studio that are normally used for researches and developments in the field of architecture were utilized. Result: Based on simulation analyses, the result of the study has showed that the proposed system definitely has adaptability to the professions and positively shows practicability as advanced integrative building envelopes with renewable energy association.

동적열해석프로그램을 이용한 대형할인매장의 에너지 소비 특성 분석 (The Energy Performance Analysis of Large Scale Store Using Dynamic Thermal Analysis Simulation Program)

  • 김병수;홍원표
    • 한국태양에너지학회 논문집
    • /
    • 제30권6호
    • /
    • pp.44-49
    • /
    • 2010
  • The purpose of this study is to analyze the situation of energy consumption and its characteristics in large scale store. The related survey is carried out in large scale store to investigate the energy consumption and energy use trend of heating, cooling, hot water, lighting, ventilation, equipments and others. The area of large scale discount store is about $65000m^2$, located in Daejeon. For Annual Energy Analysis of building, We surveyed used energy for 1 year and simulated using a building energy simulation(TRNSYS 16). The results of this study are as follows. 1)The amount of annual total energy consumption are 18615.244MWh/yr(286.4KWh/$m^2yr$), The rate of heating, cooling and base energy(for hot water, lighting, ventilation, equipments, cooking and others) is 3054MWh/yr(47kWh/$m^2yr$), 5660.09MWh/yr(87.08kWh/$m^2yr$), 9900.47MWh/yr(152.31KWh/$m^2yr$) respectively. The total used energy is higher than others building in Korea. Especially, The energy consumption of large scale store is very depends on operating period and pattern such as space temperature, occupancy, lighting system, equipments operating schedule and etc.

Sensitive analysis of design factor for the optimum design of PVT system

  • Jeong, Yong-Dae;Nam, Yujin
    • KIEAE Journal
    • /
    • 제15권4호
    • /
    • pp.5-11
    • /
    • 2015
  • Purpose: Recently, renewable energy system has been widely used to reduce the energy consumption and CO2 emission of building. A photovoltaic/thermal(PVT) system is a kind of efficient energy uses, which is combined with photovoltaic module and solar thermal collector. PVT system removes heat from PV module by through thermal fluid to raise the performance efficiency of the PV system. However, though PVT system has the merit of the improved efficiency in theoretical approach, there have been few performance analysis for PVT system using the dynamic energy simulation. In this study, in order to establish the optimum design method of this system, simulation was conducted by using individual system modules. Method: For the dynamic simulation, TRNSYS17 was used and local weather data was utilized. Furthermore, the system performance in various installation condition was calculated by case studies. Result: As a result, the amount of electric generation and heat production in each case was found by the simulation. The gap of system performance was also evident according to the installation condition.

시뮬레이션을 통한 에너지파일 적용 지열 히트펌프 시스템의 성능 예측 (Performance Prediction of Geothermal Heat Pump(GHP) System with Energy Piles Using Simulation Approach)

  • 손병후;최종민
    • 설비공학논문집
    • /
    • 제24권2호
    • /
    • pp.155-163
    • /
    • 2012
  • The aim of this study is to evaluate the performance of the GHP system with 150 energy piles for a commercial building. In order to demonstrate the feasibility of a sustainable performance of the system, simulations were conducted over 1-year and 20-year periods, respectively. The 1-year simulation results showed that the maximum and minimum temperatures of brine returning from the energy piles were $23.80^{\circ}C$ and $7.90^{\circ}C$, which were in a range of design target temperatures. In addition, after 20 years' operation, these returning temperatures decreased slowly to $23.05^{\circ}C$ and $6.98^{\circ}C$, and finally reached to stable state. The results also showed that the energy piles injected heat of 65.6 MWh to the ground and extracted heat of 96.0 MWh from the ground, respectively. Also, it is expected this GHP system with energy piles can operate with average SPF of more than 4.15 for long term.

공공기관 건물의 에너지 성능개선을 위한 패시브 요소 적용의 에너지 절감율 분석 연구 (A Study on Energy Reduction of Passive Factor Apply for the Improvement of Energy Performance in Public Building)

  • 손지훈;김삼열
    • 한국태양에너지학회:학술대회논문집
    • /
    • 한국태양에너지학회 2011년도 추계학술발표대회 논문집
    • /
    • pp.196-201
    • /
    • 2011
  • The energy used in Korea is strongly dependent on that produced by foreign countries. Accordingly, saving energy is more important than ever, because of the rise of international oil prices and depletion of oil resources. The development of energy efficient buildings is required especially for public buildings in Korea. In this study, the energy use of public buildings is identify. Then, the analysis of energy usage through regional offices in Busan City offers energy performance for public buildings.

  • PDF

건물냉방부하에 대한 동적 인버스 모델링기법의 EnergyPlus 건물모델 적용을 통한 성능평가 (Performance Evaluation of a Dynamic Inverse Model with EnergyPlus Model Simulation for Building Cooling Loads)

  • 이경호
    • 설비공학논문집
    • /
    • 제20권3호
    • /
    • pp.205-212
    • /
    • 2008
  • This paper describes the application of an inverse building model to a calibrated forward building model using EnergyPlus program. Typically, inverse models are trained using measured data. However, in this study, an inverse building model was trained using data generated by an EnergyPlus model for an actual office building. The EnergyPlus model was calibrated using field data for the building. A training data set for a month of July was generated from the EnergyPlus model to train the inverse model. Cooling load prediction of the trained inverse model was tested using another data set from the EnergyPlus model for a month of August. Predicted cooling loads showed good agreement with cooling loads from the EnergyPlus model with root-mean square errors of 4.11%. In addition, different control strategies with dynamic cooling setpoint variation were simulated using the inverse model. Peak cooling loads and daily cooling loads were compared for the dynamic simulation.

Tilt & Sliding 시스템창호의 단열성능 실측과 시뮬레이션 비교 분석 (A Comparative study on the Insulation Performance of the Tilt & Sliding System Window by Actual Survey and Simulation)

  • 장철용;안병립;김치훈;홍원화
    • 한국태양에너지학회:학술대회논문집
    • /
    • 한국태양에너지학회 2009년도 추계학술발표대회 논문집
    • /
    • pp.222-226
    • /
    • 2009
  • The parts of building which has the most influence on thermal load are skins, outer walls and windows. Among them, window is the worst weak point of building even if it has many advantage of solar radiation gain than other parts. The present time, many researches on various performance of window and many types of system-window are being made. This study evaluates thermal performance of tilt & sliding system window by simulation program Therm 5.2 and Window 5.2. After making a sample model improving it's thermal weak point, this study evaluates real thermal performance of system window. As a result, this study understands manufacture ability condition of domestic company and proposes a research plan of system window.

  • PDF

유리성능에 따른 커튼월건물의 에너지절약효과에 대한 연구 -표준건물 에너지소비와의 비교분석을 중심으로- (A Study on a Efficiency of Glazing for Energy Reduction of Curtain Wall Buildings)

  • 이용준;정광섭;오보환;강재식;최경석;이득호
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.114-119
    • /
    • 2009
  • This study has been conducted to describe the establishment of national measures to reduce world energy consumption and $CO_2$ Emission. Particularly, Reductions in energy consumption from building operation is the most important part to achieve these national objectives. Element to evaluate the quantitative effects of these systems by having rationalized regulation and operation is essential, when planning for building energy reduction design. USGBC(US Green Building Council) have operated sustainable assessment method called LEED, which introduces baseline performance and evaluation direction for building simulation techniques. This research analyzed Quantitative assessments of the building energy consumption and analyzed baseline figures to provide comparative analysis with standard building settings.

  • PDF