도로터널 반횡류식 환기방식의 최적배연 풍량산정에 관한 연구 - 균일배기의 경우 - (A Study on the Effective Smoke Exhaust Amount of Load-Tunnel with Semi-Transverse Ventilation - Balanced Exhaust Case -)

  • 이동호;유지오;신현준
    • 한국안전학회지
    • /
    • 제21권2호
    • /
    • pp.46-51
    • /
    • 2006
  • The smoke exhaust system is one of the effective systems to save lives when fire occurs underground. This study presents a complete analysis of effective smoke exhaust and smoke characteristics for a fire occurring with a transverse ventilation system use as a smoke exhaust system. The performance of the smoke management system was studied by computer modeling using FDS version 3.1. A fire size of 20MW was used for tunnel with balanced exhaust transverse ventilation. The smoke management design and the procedure as simulated in this study are also compliant to the tunnel construction and fire codes of Korea.

균일배기 환기방식에서의 배연특성에 관한 연구 (A Study on the Effective Fire and Smoke Control in Semi-Transverse Ventilation)

  • 전용한;김종윤;서영호;유지오;한상필
    • 한국화재소방학회논문지
    • /
    • 제24권1호
    • /
    • pp.90-94
    • /
    • 2010
  • 본 연구에서는 횡류환기방식의 균일배기방식(balanced exhaust)에 대한 터널 내 풍속, 배연풍량에 따른 수치해석을 수행하여 연기의 이동거리를 분석하고 기존의 유동가시화 실험결과와 비교하였다. 그 결과 균일배기방식의 배연시스템에서는 풍속이 존재하지 않는 경우 배연풍량을 연기발생량(Vc = 0)일 때 건설교통부의 도로터널방재시설 지침에 의한 피난연결통로의 간격 250m 이내로 연기가 제한되었으며, 배연효율은 본 실험범위에서 55.1%에서 95.8%로 나타났다. 터널 내 풍속이 존재하면 연기를 배연하기 위한 배연풍량이 급격하게 증가하는 경향을 보이는 것으로 알 수 있으며, 배기구의 풍속이 증가하면 배연효율이 감소하며, 연기의 이동거리를 목표로 하는 거리로 제한하기 위해서 배연풍량은 연기발생량 보다 최대 1.8배에서 1.04배까지 증대하는 것으로 나타나고 있다. 본 연구에서 평가기준으로 선정한 250m 이내로 연기의 이동거리를 제한하기 위한 배연풍량은 터널 내 풍속이 존재하지 않는 경우에는 배연풍량은 최소 $84m^3/s{\cdot}250m$, 1.75m/s인 경우에 배연풍량은 최소 $393m^3/s{\cdot}250m$($Q_E$= 80 + 5Ar)으로 나타났다.