• Title/Summary/Keyword: air-duct cooling

Search Result 59, Processing Time 0.024 seconds

A study on a precision temperature control unit using thermoelectirc module (열전소자를 이용한 정밀 항온 유지 장치에 관한 실험 및 시뮬레이션 연구)

  • Park, Kyung-Seo;Song, Young-Joog;Im, Hong-Jae;Jang, Si-Yeol;Lee, Kee-Sung;Jeong, Jay;Shin, Dong-Hoon
    • Proceedings of the KSME Conference
    • /
    • 2007.05b
    • /
    • pp.1937-1941
    • /
    • 2007
  • During a process of a nanoimprint for manufacturing LCD, a small temperature variation on the LCD glass can cause thermal stress and generate unexpected displacement. To avoid this trouble, a precision temperature control unit using thermoelectric modules is appropriate for nanoimprint processes. The unit consists of an air control system, a cooling water control system, and a power control system. The air control system includes a thermoelectric module, thermocouples measuring temperatures of air and a duct-stale fin, and two air fans. The heat generated by the thermoelectric module is absorbed by the cooling water control system. The power control system catches the temperature of the thermoelectric module, and a PID controller with SCR controls the input power of the thermoelectric module. Temperature control performance is evaluated by experiment and simulation. The temperature control unit is able to control the exit temperature about ${\pm}2^{\circ}C$ from the incoming fluid temperature, and the error range is ${\pm}0.1^{\circ}C$. However, the control time is approximately 30minute, which needs further study of active control

  • PDF

On-Site Measurement of the Inlet Air Evaporative Cooling Performance for a Centrifugal Turbo Compressor (CDA 인입공기 증발냉각을 통한 압축기 성능 개선장치 개발 연구)

  • Kim, Gyu Wan;Park, Jin Ouk;Kim, Heuy Dong
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.38 no.11
    • /
    • pp.873-879
    • /
    • 2014
  • In the present study, water vapor is injected at various positions in a Clean Dry Air (CDA) system such as a system inlet duct, compressor inlet, and compressor outlet by humidified air turbines. The application of evaporative cooling reduces the compression work and enhances the Energy Consumption Index (ECI) per unit volume. The main purpose of this study is to investigate the compressor power performance with different inlet air temperatures and humidity conditions. It is found that the actual power consumption and discharge flow are significantly influenced by the inlet air temperature as well as relative humidity. The results obtained during this study are compared both numerically and experimentally and are found to be in very good agreement.

Temperature Rise Test and Temperature Distribution Analysis of Pole Mount Mold Transformer with One-body Molding (일체형 주상용 몰드 변압기의 온도분포 및 특성 비교)

  • Cho, Han-Goo;Lee, Un-Yong;Kang, Tack-Sou;Choi, In-Hyuk
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.19 no.12
    • /
    • pp.1154-1159
    • /
    • 2006
  • The mold transformers have been widely used in underground substations of large building and have some advantages when compared with oil-transformer. Those advantages are low fire risk, environmental compatibility, compact size and high reliability. The mold transformer is generally known to have cooling duct between low voltage and high voltage coil. To achieve better compact structure and low loss, mold transformers made by one body molding method has been developed. Nevertheless, such kinds of transformer need better cooling method because heat radiation between each winding is still of problem. The life of transformer is significantly dependent on the thermal behavior in windings. Many designers have calculated temperature distribution in transformers and hot spot point by finite element method(FEM) to analyze winding temperature rise. In this paper, the temperature distribution analysis of 100 kVA pole mold transformer for power distribution were investigated by FEM program and the thermal analysis results were compared with temperature rise test.

The Temperature Distribution and Thermal Stress Analysis of Pole Mold transformer (주상용 몰드변압기의 온도분포와 열응력 해석)

  • 조한구;이운용;한세원;김석수
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.14 no.4
    • /
    • pp.297-301
    • /
    • 2001
  • In this paper, the temperature distribution and thermal stress analysis of 50kVA pole cast resin transformer for power distribution are investigated by FEM program. The one body molding model (Model 1) and air duct model (Model 2) are designed and their temperature distribution are analysed. The temperature rise value is about 105.5 deg in the model 1 and 65.28 de in the model 2. The temperature change of secondary winding is more than primary winding according to load ratio. The concentration part of Von Mises Stress occurs at interface between glass fiber and epoxy.

  • PDF

Study on the Cooling Performance of Heatsink for Induction Cooktop using Computational Fluid Dynamics (인덕션 쿡탑 기구물 형상변경이 Heatsink 및 Coil 냉각성능에 미치는 영향에 대한 연구)

  • Park, Dong Ho;Kwon, Myoung Keun;Lee, Dong Beom;Seo, Eung Ryeol;Park, Yong Jong
    • The KSFM Journal of Fluid Machinery
    • /
    • v.18 no.3
    • /
    • pp.33-37
    • /
    • 2015
  • A numerical study on the IPM/Bridge Diode cooling and coil cooling has been performed. Results are presented as plots of thermal resistance, temperature drop and RPM-ratio. CFD analysis for conventional cooling system has been performed as a reference case. As the RPM-Ratio was increased, heatsink thermal resistance and coil temperature were decreased. IPM/Bridge Diode thermal resistance and temperature of the coil is tended to be trade-off. The temperature of coil closest to the AC-motor fan showed the most significant change in accordance with duct design. The temperature of coil located at the top of DC-motor fan showed the most significant variation as the cooling air passes the heatsink fin area.

Change of Heat Transfer Characteristics in a Rotating Channel of Square Duct at Wall with Bleed Holes ( I ) - Effects of Rotation Speed - (회전하는 사각덕트 유로에서 벽면 유출홀에 따른 열전달 특성 변화( I ) -회전수 변화에 따른 영향 -)

  • Kim Sang In;Kim Kyung Min;Lee Dong-Hyun;Jeon Yun Heung;Cho Hyung Hee
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.10
    • /
    • pp.898-906
    • /
    • 2005
  • The present study has been conducted to investigate convective heat/mass transfer in the cooling passage with bleed holes. The rotating square channel has 40.0 mm hydraulic diameter and the bleed holes on the leading surface of the channel. The hole diameter of bleed hole is 4.5mm and its spacing is ( p/d:4.9) about five times of hole diameter. Exit mass flow rate through bleed holes is $10\%$ of the main mass flow rate and relation number is changed form 0.0 to 0.4. A naphthalene sublimation technique is employed to determine the detailed local heat transfer coefficients using the heat and mass transfer analogy The cooling performance is influenced by exit mass flow rate through bleed holes and Coriolis force of rotating channel for fixed Reynolds number. The heat transfer on the leading surface is decreased due to Coriolis force. However the total heat transfer is enhanced around holes on the leading surface because of trapping flow by bleeding.

Change of Heat Transfer Characteristics in a Rotating Channel of . Square Duct at Wall with Bleed Holes ( II ) - Effects of Exit Mass Flow Rate - (회전하는 사각덕트 유로에서 벽면 유출홀에 따른 열전달 특성 변화( ll ) -유출유량 변화에 따른 영향 -)

  • Kim Sang In;Kim Kyung Min;Lee Dong-Hyun;Jeon Yun Heung;Cho Hyung Hee
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.10
    • /
    • pp.907-913
    • /
    • 2005
  • The present study has been conducted to investigate convective heat/mass transfer in the cooling passage with bleed holes. The rotating square channel has 40.0 mm hydraulic diameter and the bleed holes on the leading surface of the channel. The hole diameter of bleed hole is 4.5mm and its spacing is ( p/d:4.9) about five times of hole diameter. Exit mass flow rate through bleed holes is $0\%,\;10\%\;and\;20\%$ of the main mass flow rate respectively. rotation number is fixed 0.2. A naphthalene sublimation technique is employed to determine the detailed local heat transfer coefficients using the heat and mass transfer analogy. The cooling performance is influenced by exit mass flow rate through bleed holes and Coriolis force of rotating channel for fixed Reynolds number. The heat transfer on the leading surface is decreased due to Coriolis force. However the total heat transfer is enhanced around holes on the leading surface because of trapping flow by bleeding.

Recent Progress in Air Conditioning and Refrigeration Research - A Review of papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 1998 and 1999 - (공기조화, 냉동 분야의 최근 연구 동향 - 1998년 1999년 학회지 논문에 대한 종합적 고찰 -)

  • 이재헌;김광우;김병주;이재효;김우승;조형희;김민수
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.12
    • /
    • pp.1098-1125
    • /
    • 2000
  • A review on the papers published in the Korean Journal of Air-Conditioning and Refrigerating Engineering in 1998 and 1999 has been done. Focus has been put on current status of research in the aspect of heating, cooling, ventilation, sanitation and building environment. The conclusions are as follows. 1) A review of the recent studies on fluid flow, turbomachinery and pipe-network shows that many experimental investigations are conducted in applications of impingement jets. Researches on turbulent flows, pipe flows, pipe-networks are focused on analyses of practical systems and prediction of system performance. The results of noise reduction in the turbomachinery are also reported. 2) A review of the recent studies on heat transfer analysis and heat exchanger shows that there were many papers on the channel flow with the application to the design of heat exchanger in the heat transfer analysis. Various experimental and numerical papers on heat exchanger were also published, however, there were few papers available for the analysis of whole system including heat exchanger. 3) A review of the recent studies on heat pump system have focused on the multi-type system and the heat pump cycle to utilize treated sewage as the heat source. The defrosting and the frosting behaviors in the fin-tube heat exchanger is experimentally examined by several authors. Several papers on the ice storage cooling system are presented to show the dynamic simulation program and optimal operation conditions. The study on the micro heat pipes for the cooling of high power electronic components is carried out to examine the characteristics of heat and mass transfer processed. In addition to these, new type of separate thermosyphon is studied experimentally. 4) The recent studies on refrigeration/air conditioning system have focused on the system performance and efficiency for new alternative refrigerants. New systems operating with natural refrigerants are drawing lots of attention. In addition to these, evaporation and condensation heat transfer characteristics of traditional and new refrigerants are investigated for plain tubes and also for microfin tubes. Capillary tubes and orifice are main topics of research as expansion devices and studies on thermophysical properties of new refrigerants and refrigerant/oil mixtures are widely carried out. 5) A review of the recent studies on absorption cooling system shows that numerous experimental and analytical studies on the improvement of absorber performance have been presented. Dynamic analysis of compressor have been performed to understand its vibration characteristics. However research works on tow-phase flow and heat transfer, which could be encountered in the refrigeration system and various phase-change heat exchanger, were seemed to be insufficient. 6) A review of recent studies on duct system shows that the methods for circuit analysis, and flow balancing have been presented. Researches on ventilation are focused on the measurement of ventilation efficiency, and variation of ventilation efficiency with ventilation methods by numerous experimental and numerical studies. Furthermore, many studies have been conducted in real building in order to estimate indoor thermal environments. Many research works to get some information for cooling tower design have been performed but are insufficient. 7) A review on the recent studies on architectural thermal environment and building mechanical systems design shows that thermal comfort analysis is sitting environment, thermal performance analysis of Korean traditional building structures., and evaluation of building environmental load have been performed. However research works to improve the performance of mechanical system design and construction technology were seemed to be insufficient.

  • PDF

HEATING PERFORMANCE OF AIR SOURCE HEAT PUMP WITH HEAT REGENERATIVE DEVICE USING FIBER BELT

  • Ryou, Y.S.;Chang, J.T.;Kim, Y.J.;Kang, G.C.;Yun, J.H.;Lee, K.J.
    • Proceedings of the Korean Society for Agricultural Machinery Conference
    • /
    • 2000.11c
    • /
    • pp.647-653
    • /
    • 2000
  • In this research the heat regenerative technology was employed to eliminate frosting on evaporator coil and improve COP of the heat pump system. This heat regenerative device(HRD) has very simple structure consisting a geared motor and a porous fiber belt passing through alternatively between cold and warm air duct. The laboratory test showed that the heat pump system with HRD yielded an impressive COP higher than 3.5 at the outside air temperature of $-7^{circ}C$ in heating mode.

  • PDF

A Study for Improving the Thermal Environment of Telecommunication Equipment Room -based on TDX-10, TDX-100, 5ESS-2000, PCM room- (통신장비실의 열환경 개선방안에 관한 연구 -TDX-10, TDX-100, 5ESS-2000, PCM실 중심으로-)

  • Cho, Chun-Sik;Leigh, Seung-Bok
    • KIEAE Journal
    • /
    • v.4 no.3
    • /
    • pp.87-94
    • /
    • 2004
  • The purpose of this study is to improve thermal environment of telecommunication equipment rooms that hold TDX-10, TDX-100, 5ESS-2000, PCM of the latest telecommunication equipment. Analysis program is used the commercial CFD code, Star-CD and DOE-2.1E. The result has been compared by the energy consumption and the temperature contour at the 1 m height of room for each case. Different methods such as the relocation of the existing air-conditioner, the inflow of the ambient air into room, the installation of the forced fan and the cooling system equipment of the duct-connection type have been used to test for improvement of thermal environment. The analysis shows that most efficient method is the inflow of the ambient air into room but auxiliary equipment should be needed to prevent the local thermal spot.