• 제목/요약/키워드: ZnO arresters

검색결과 53건 처리시간 0.031초

산화아연 피뢰기의 열화진단을 위한 저항성누설전류의 고정도 측정기법 및 장치의 개발 (A Development of the High Precise Measuring Device and Methods of Resistive Leakage Current for the Deterioration Diagnosis of ZnO Arrester)

  • 이복희;강성만;전덕규;박건영;최휘성;조성철;백영환;이동환
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 C
    • /
    • pp.1668-1670
    • /
    • 2003
  • This paper deals with a development of the high precise measuring device of resistive leakage current for the deterioration and diagnosis of ZnO arresters. The resistive leakage current increasing with time leads to a thermally unstable state that may even experience a disaster. So, the resistive leakage current can be used as an indicator to discriminate whether the ZnO arrester blocks is in good state or in bad. The resistive leakage current measuring system with an analysis program operated with micro-processor using the time delay addition method was designed and fabricated. The proposed measuring systems for the resistive leakage current can effectively be used to develop the techniques of forecasting the deterioration of ZnO arresters in electric power systems.⨀ᔌ?؀㔳㤮㈻Ԁ䭃䑎䷗ᜒं6〰Ԁ䭃䑎䴀

  • PDF

초고압 피뢰기용 ZnO 소자의 장시간 방전내량과 균일성 (Long Duration Current Impulse Withstand Characteristics and Uniformity of ZnO Blocks for High Voltage Surge Arresters)

  • 조한구;유대훈;이유정
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2007년도 추계학술대회 논문집
    • /
    • pp.486-487
    • /
    • 2007
  • This paper describes the evaluation of long duration current impulse withstand characteristics of ZnO blocks for high voltage surge arresters. Four ZnO varistors were manufactured with the general ceramic production method and three abroad varistors were also prepared to be compared. All varistors exhibited high density, which was in the range of $5.42{\sim}5.49g/cm^3$. In the electrical properties, the reference voltage of all samples was in the range of 5.11~5.72kV and the residual voltage was in the range of 8.314~9.305kV. In the long duration current impulse withstand test, sample 2 and 3 failed at the 2nd and 4th shot of series impulse currents, respectively, but the rest survived 18 shots during the test. Before and after this test, the variation ratio of the residual voltage of samples survived were below 1.7%, which were in the acceptance range of 5%.

  • PDF

배전용 폴리머 피뢰기의 고장원인 및 대책 (The Causes and Countermeasures for failures of Distribution Polymer Surge Arresters)

  • 김주용;이재봉;김동명;장상옥;황광수
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2003년도 하계학술대회 논문집 Vol.4 No.2
    • /
    • pp.1159-1162
    • /
    • 2003
  • Recently we suffered lot of failures of polymer surge arresters made by same manufacture after one year field operation. In order to set up countermeasures we investigated the causes of failures. We extracted faulted arresters and sound ones which were installed in same pole with faulted ones for the electrical test and dissection. 44 arresters were removed from 8 branch offices. Almost all of faulted arresters hadtracking damage on the interface between inner module and housing and the surface of inner module was very rough and irregular. It was possible to occur moisture ingress into the interface between inner module and housing due to the void of the interface and non tight sealing caps. Lots of sound arresters were failed during the moisture ingress test. This result must relate with tracking damage of faulted arresters. Therefore we can say that arresters had poor interface and sealing system. But we could not found aging and defects of ZnO elements because the electrical performance except moisture ingress test of arresters showed good.

  • PDF

폴리머 피뢰기의 구조에 따른 온도와 누설전류 특성 (Temperature and Leakage Current Characteristics with Structure of Polymeric Surge Arresters)

  • 조한구;이운용;김하나
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2006년도 하계학술대회 논문집 Vol.7
    • /
    • pp.513-514
    • /
    • 2006
  • This paper presents the temperature characteristics with the structure of 18 kV surge arresters for distribution system. Three types of polymer arrester were fabricated and a ceramic arrester was also prepared to investigate. Below $100^{\circ}C$, three types of polymeric arresters exhibited almost the same leakage current value, but above $100^{\circ}C$, the polymeric arresters whose module was injected into polymeric housing with the grease exhibited the highest leakage current. In contrary, the arresters being manufactured by directly injecting silicone rubber onto arrester module exhibited the lowest leakage current. The rapid rising of leakage current of the polymeric arresters with the grease at $120^{\circ}C$ was because of the deterioration of the insulation characteristics of the grease between the FRP module and the silicone housing. All polymeric arresters exhibited the same surface temperature characteristics but the ceramic arresters was slower than the polymer arrester in heat emission despite the lowest leakage current. It was thought that the air layer between ZnO varistor blocks and the ceramic housing prevented the heat emission.

  • PDF

열화정도에 따른 배전용 피뢰기의 열화특성 분석 (Analysis of degradation of distribution lightning arresters as degradation degree)

  • 장동욱;박동배;박영국;이용희;강성화;임기조
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 하계학술대회 논문집
    • /
    • pp.140-143
    • /
    • 2000
  • The primary function of ZnO lightning arrester is to protect transmission and distribution equipment from overvoltages and to absorb electrical energy resulting from lightning or switching surges and form temporary overvoltage. However, ZnO lightning arrester are known to exhibit an increases in resistive current with time, the rate of increase being exacerbated with increasing applied voltage and ambient temperature. So, it is important to the leakage current measurement of ZnO lightning arrester. In addition, since the resistive leakage current caused by deterioration of ZnO lightning arrester mainly caused an increase of the third harmonic component, thereby it is possible the arrester degradation diagnosis by measuring the third harmonic component in the total leakage current. The leakage current and third harmonic component are measured and used to investigate the degradation diagnosis of ZnO element of arrester. Also the SEM photography is used to investigate the change of crystal structure of ZnO element with degradation.

  • PDF

고분자 피뢰기의 기밀특성에 관한 연구 (Sealing Integrity of polymeric ZnO Surge Arresters)

  • Liang, He-Jin;Han, Se-Won;Cho, Han-Goo;Kim, In-Sung
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1997년도 추계학술대회 논문집
    • /
    • pp.258-261
    • /
    • 1997
  • The sealing integrity is related to the safe operation of arrester the prime failure reason of porcelain housed arresters is moisture ingress. To be a meaningful tests a polymer arrester sealing test must be a realistic acceleration of field service. We think the test should be an accelerating course of actual temperatures, the enduring property to mechanical load and temperatures should be considered together. A union test method consisting of the thermal mechanical test and thermal cycling test is proposed to test the sealing integrity of polymeric arresters, which uses dielectric loss, leakage current 1mA DC voltage and partial discharge as the diagnostic techniques, and the test results were presented. The comparison states that the TMTCUT method is suitable fur the test of sealing integrity of polymeric arresters. .

  • PDF

다중 뇌충격전류에 의한 산화아연형 피뢰기 소자의 특성 변화 (Characteristic Changes of ZnO Arrester Blocks by Multiple-lightning Impuse Currents)

  • 길경석;한주섭
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제49권12호
    • /
    • pp.685-690
    • /
    • 2000
  • Multiple-lightning impulse currents are a general feature of the lightning ground f=flash. It is therefore necessary for lightning arresters used in power systems to be estimated by applying not only a single-lightning impulse current but also a multiple-lightning impulse currents. This paper presents the effects of multiple-lightning impulse currents on deterioration of ZnO arrester blocks. The multiple-lightning impulse generator which can produce quadruple 8/20$[\mus]$ 5[kA] with separation time of 30~120[ms] is designed and fabricated. The total energy applied to the arrester block at each impulse is about 1,200[J]. In experiment, various parameters such as leakage current component, reference voltage, and temperature are measured with the number of applied impulse current. Also, micro-structure changes of the ZnO blocks after applying the single and the multiple-lightning impulse currents of 200 times are compared. The experimental results indicate that the types of arrester blocks are more vulnerable to deterioration or damage by multiple-lightning impulse currents.

  • PDF

18kV 배전용 피뢰기의 구조에 따른 온도특성 (Temperature Characteristics with Structure of 18kV Lightning Arresters for Distribution System)

  • 조한구;윤한수;이운용;김석수;최인혁
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 하계학술대회 논문집 Vol.5 No.2
    • /
    • pp.1125-1128
    • /
    • 2004
  • This paper presents the temperature characteristics with structure of 18 kV lightning arresters for distribution. Three types of polymer arresters were fabricated and ceramic type arrester was also ready to investigate. Below $100^{\circ}C$, three types of polymer arresters exhibited almost the same leakage current value, but above $100^{\circ}C$, polymer arrester that arrester module was injected into polymer housing with grease exhibited the highest leakage current and the arrester with the lowest leakage current was the arrester that silicon rubber was directly injected to arrester module. The rising of leakage current of polymer arrester with grease was because of existing grease between FRP winding and silicon housing, and reducing the insulation characteristics of the grease. All polymer arresters exhibited the same temperature characteristics but ceramic typr arrester was slower than polymer arrester in heat emission despite lowest leakage current. It was thought that the air layer between ZnO varistor blocks and ceramic housing prevented the heat emission. However, in spite of the difference of the structure, the variation of the surface temperature of all arresters exhibited the same result.

  • PDF

송전선로에 사용되는 갭형 피뢰기 소자의 뇌임펄스 전류특성 (Characteristics of Lightning Impulse Current of ZnO Block for Transmission Line Arrester with External Gap)

  • 조한구;유대훈
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2007년도 하계학술대회 논문집 Vol.8
    • /
    • pp.458-459
    • /
    • 2007
  • This paper describes the characteristics of lightning impulse current of ZnO block for transmission line arrester with external gap. The ageing parameters of lightning arresters are impulse current, moisture ingress, temperature ageing and so on. Especially it is important to estimate the change of electrical characteristics by impulse current. Total energy applied to the ZnO arrester each time is $4/10{\mu}s$, 30kA and $2/20{\mu}s$, 10kA impulse current. Before and After the test, the residual voltage variation of varistors passed was below 5%. According to the test, it is thought that the ZnO arrester shows good stability with impulse current test.

  • PDF

Series Gap Type 피뢰기의 뇌임펄스 동작책무 및 온도의존성에 관한 연구 (A Study of Lightning Impulse Operating Duty and Temperature Dependence of Series Gap Type Arrester)

  • 조한구;유대훈
    • 한국전기전자재료학회논문지
    • /
    • 제22권8호
    • /
    • pp.659-664
    • /
    • 2009
  • This paper describes lightning impulse operating duty performance and temperature dependence of series gap type for transmission line arresters. The ageing parameters of lightning arresters are impulse current, moisture ingress, temperature ageing and so on. Especially it is important to estimate the change of electrical characteristics by lightning impulse current. In the discharge withstand test, total energy applied to the ZnO arrester each time is 4/10 ${\mu}s$, 30 kA. and in the operating duty test, the arrester has passed the test if thermal stability is achieved, if the residual voltage measured before and after the test is not changed by more than 5 %, and after the test reveals no evidence of puncture, flashover or cracking of the ZnO block. As a results, the residual voltage was in the range of 17.2${\sim}$20.3 kV and ZnO block bear up against at 2 shot of series impulse current of 30 kA. Also it was so excellent that the mechanical destruction does not occur at the 2 groups of 5 impulses current of 2/20 ${\mu}s$ 10 kA. According to the tests, it is thought that the ZnO arrester shows good stability with impulse current test. and it was found that the ambient temperature is increased resistive leakage current was increased in the range 47.3${\sim}$167.4 ${\mu}A$.