Characteristic Changes of ZnO Arrester Blocks by Multiple-lightning Impuse Currents

다중 뇌충격전류에 의한 산화아연형 피뢰기 소자의 특성 변화

  • 길경석 (한국해양대 공대 전기공학과) ;
  • 한주섭 (한국해양대 공대 전기공학과)
  • Published : 2000.12.01

Abstract

Multiple-lightning impulse currents are a general feature of the lightning ground f=flash. It is therefore necessary for lightning arresters used in power systems to be estimated by applying not only a single-lightning impulse current but also a multiple-lightning impulse currents. This paper presents the effects of multiple-lightning impulse currents on deterioration of ZnO arrester blocks. The multiple-lightning impulse generator which can produce quadruple 8/20$[\mus]$ 5[kA] with separation time of 30~120[ms] is designed and fabricated. The total energy applied to the arrester block at each impulse is about 1,200[J]. In experiment, various parameters such as leakage current component, reference voltage, and temperature are measured with the number of applied impulse current. Also, micro-structure changes of the ZnO blocks after applying the single and the multiple-lightning impulse currents of 200 times are compared. The experimental results indicate that the types of arrester blocks are more vulnerable to deterioration or damage by multiple-lightning impulse currents.

Keywords

References

  1. M. Bartkowiak et al., 'Failure Modes and Energy Absorption Capability of ZnO Varistors,' IEEE Trans. Power Delivery, Vol. 14, No. 1, pp. 152-162, 1999 https://doi.org/10.1109/61.736708
  2. W. G. Carlson, T. K. Gupta, A. Sweetana, 'A Procedure for Estimating the Lifetime of Gapless Metal Oxide Surge Arresters,' IEEE Trans. Power Delivery, Vol. 1, No. 2, pp. 67-74, 1986 https://doi.org/10.1109/TPWRD.1986.4307935
  3. O. Nigol, 'Methods for Analyzing the Performance of Gapless Metal Oxide Surge Arresters,' IEEE Transaction on Power Delivery, Vol. 7, No. 3, pp. 1256-1262, 1992 https://doi.org/10.1109/61.141839
  4. Jinbo Kuang et al., Temperature Distribution in a ZnO Arrester Subjected to Multiple Current Impulses,' Proceeding of the 1996 International Symp. on Electrical Insulation, pp. 494-497, 1996. 7 https://doi.org/10.1109/ELINSL.1996.549390
  5. 한국공업표준협회, '산화아연형 갭리스 피뢰기,' KSC 4609, 1987
  6. 한국전력공사, '전력용 피뢰기,' ES 153-261, 1984
  7. The Institute of Electrical and Electronics Engineers Inc., 'IEEE Std. for Metal-Oxide Surge Arresters for AC power Circuits,' ANSI/IEEE C62.11, 1987
  8. Martin A. Uman, The Lightning Discharge, Academic Press Inc., pp. 1-36, 1987
  9. 길경석 외, '다중 뇌충격전류에 의한 피뢰기 소자의 전기적 특성 변화,' 대한전기학회 하계종합학술대회 논문집, C권, pp. 2035-2037, 2000. 7
  10. 길경석 외, 피뢰기 누설전류 분석장치의 설계 및 제작, 대한전기학회 방전 및 고전압 연구회 춘계학술대회 논문집, pp. 65-68, 1999
  11. S. Tominaga, Y. Shibuya et al., 'Stability and Long Term Degradation of Metal Oxide Surge Arresters,' IEEE Trans. on Power Apparatus and Systems, Vol. PAS-99, No. 4, pp. 1548-1556, 1980 https://doi.org/10.1109/TPAS.1980.319580
  12. 길경석, 한주섭, 박영호, '뇌충격 전류에 의한 산화아연형 피뢰기소자의 전기적 특성변화, 대한전기학회 논문지, Vol. 48, No. 7, pp. 550-555, 1999. 7
  13. S. S. Kershaw, G. L. Gaibrois, K. B. Stump, 'Applying metal-oxide surge arresters on distribution systems,' IEEE Transactions on Power Delivery, Vol. 4, No. 1, pp. 301-307, 1989 https://doi.org/10.1109/61.19217