• 제목/요약/키워드: ZnO arresters

검색결과 53건 처리시간 0.023초

전력용 피뢰기의 열안정화 특성 (Study on Thermal Stability Characteristics of Surge Arrester for High Power)

  • 한세원;조한구
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 하계학술대회 논문집 Vol.5 No.2
    • /
    • pp.1142-1145
    • /
    • 2004
  • ZnO surge arresters continuously endure the operating voltages during the operation course, and in the mean time, which need to withstand occasionally transient voltages of lightning and switching overvoltages. Under these voltages, the ZnO varistors inside arresters would have aging phenomena, one important result of aging phenomena is the increasing of resistive currents of varistors, which leads to the increasing of power losses of varistors. And the operating voltage is continuously applied on the ZnO varistors, there is a degradation phenomenon existing in ZnO varistors. When the degradation reaches a certain degree, then the arrester must stop operation. The degradation is related to the applied voltage ratio, the applied voltage ratio is high, the degradation is quickly. When the power loss is higher than the thermal dispersion ability of house of arrester, then the arrester will thermally breakdown. In this study the thermal stability characteristics of surge arresters for high power wil be discussed on the view point of watt losses and thermal breakdown.

  • PDF

온도측정에 의한 산화아연형 피뢰기 진단 (ZnO Arrester Diagnosis by Measurement of Temperature)

  • 길경석;한주섭;송재용;서황동;문승보;박태곤
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제54권8호
    • /
    • pp.361-364
    • /
    • 2005
  • In this paper, surface temperatures of ZnO arresters as a function of ambient temperatures and leakage currents were experimentally investigated. The variations of the leakage current was below 10 uA, which comes about $4.5\%$ of the normal leakage current. Temperature differences between the ambient and the surface of arresters were not shown until $150\%$ to the normal leakage current, and were remarkable over $200\%$. From the results, we deduced a couple of polynomials which enables the calculation of the leakage current by the measurement of surface temperature. Tests on used arresters have shown the same results as the experimental one. Also, we expect that an arrester diagnosis is possible by measuring the surface temperature of them after more studies on the effect of wind, moisture penetration, and arrester types.

폴리머 피뢰기의 구조에 따른 온도와 누설전류 특성 (Temperature and Leakage Current Characteristics of Polymeric Surge Arrester with Housing)

  • 조한구;유대훈;이운용;김하나
    • 한국전기전자재료학회논문지
    • /
    • 제20권3호
    • /
    • pp.273-280
    • /
    • 2007
  • In this paper, the ZnO surge arrester performance of power distribution class has been studied under different manufacturing conditions such as housing materials(polymeric, porcelain), interface sealants and one-body molding type. In the recent years, the polymeric ZnO surge arresters have been developed and put into operations based on their excellent characteristics. For polymeric surge arresters, the inner gas volume is extremely small, especially in solid insulation polymeric arresters there are not any gas volume inside arresters in the structure due to polymeric materials are filled into the internal gas volume. The sealing integrity is related to safe operation of surge arrester, the prime failure reason of porcelain housed arresters is moisture ingress. In this paper, the sealing integrity of polymeric surge arresters is investigated with moisture multi-aging test and ingress test. The evaluation techniques are used to inspect the sealing integrity of polymeric arresters, including leakage current, surface temperature, reference voltage and dissipation factor.

ZnO 피뢰기의 저항분 누설전류와 제 3고조파 누설전류의 관계 (Correlation between the resistive and the $3^{rd}$ harmonic leakage current of ZnO arresters)

  • 김일권;송재용;문승보;차명수;길경석
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2006년도 하계학술대회 논문집 Vol.7
    • /
    • pp.515-516
    • /
    • 2006
  • The resistive leakage current is an important parameter for arrester diagnosis. However, the 3rd harmonic leakage current is more widely used than the resistive one because of its easy measurement. In this paper, we studied the correlation between the resistive and the $3^{rd}$ harmonic leakage current of ZnO arresters. The resistive leakage current was measured according to the IEC 60099-5 in AC applied voltage. The $3^{rd}$ harmonic leakage current was analyzed by using a designed band-pass filter having 180 [Hz]-center frequency and 10 [Hz]-bandwidth. The experimental results show that the $3^{rd}$ harmonic leakage current changes proportionally with the resistive leakage current variation under the maximum continuous operating voltage (MCOV).

  • PDF

전철 탑재형 ZnO 고분자 피뢰기의 전계해석 (Electric Field Analysis of Polymeric ZnO Surge Arrester for loading in Electric Traction)

  • 이운용;장동욱;강성화;임기조;한세원;조한구
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 E
    • /
    • pp.2293-2295
    • /
    • 1999
  • Polymeric ZnO surge arresters are used to protect the electric traction to limit the overvoltage invading into its inner electrical circuits. We have developed polymeric ZnO surge arresters design and investigated electric field analysis of its by FEM(Finite Element Method).

  • PDF

ZnO 피뢰기의 경년변화 특성분석 (Aging Characteristics of ZnO Surge Arresters)

  • 김주용;김찬영;송일근;이병성;한용희
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1999년도 춘계학술대회 논문집
    • /
    • pp.383-386
    • /
    • 1999
  • Surge arrestor is used for protection of facilities and lines. Recently lots of arresters fatted prematurely In the distribution lines. It is important to know that what the cause of the failures is. This paper presents characteristics of the aged and new 18kV surge arrester. In order to analyse characteristics, we measured leakage current using specialty made leakage current measurement system and also investigated Tan $\delta$ of the arrester and microstructure of the elements. Through the investigation we found that the characteristics among the ZnO elements in an arrester were a little different, It means that the surge arreste can have non-uniform electric field due to the characteristic difference of The each element. Owing to this concentration of the electric field, the localized aging might be proceeded.

  • PDF

철도용 피뢰기의 열화진전에 관한 연구 (A Study on the Deterioration Progress of Railway Arresters)

  • 길경석;한주섭;한문섭
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2004년도 춘계학술대회 논문집
    • /
    • pp.1393-1395
    • /
    • 2004
  • Arresters are the best protective device on electrical power systems against transient overvoltages generated by lightning and/or switching operation. Nonetheless, arresters will be deteriorated due to absorption of moisture in the environments of its use, repetition in the protective operation to overvoltages, and some defects at manufacturing. It is therefore important to estimate the electrical characteristic changes of ZnO blocks. In this paper, an accelerated deterioration test by a standard lightning impulse current was carried out to extract parameters needed for diagnosing arrester deterioration, and leakage current components were measured. Total energy applied to the ZnO blocks at each time is 1,050[J] in 8/20[${\mu}s$] impulse current. From the experimental results, we proposed electrical parameters and leakage current level to diagnose arrester soundness.

  • PDF

철도용 피뢰기의 열화진전에 관한 연구 (A Study on the Deterioration Progress of Railway Arresters)

  • 길경석;한주섭;한문섭
    • 한국철도학회논문집
    • /
    • 제7권4호
    • /
    • pp.307-311
    • /
    • 2004
  • Arresters are the best protective device on electrical power systems against transient overvoltages generated by lightning and/or switching operation. Nonetheless, arresters are deteriorated by absorption of moisture in the environments of its use, repetition in the protective operation to overvoltages, and some defects at manufacturing. It is therefore important to estimate the electrical characteristic changes of ZnO blocks. In this paper, an accelerated ageing test by a standard lightning impulse current was carried out to extract parameters needed for arrester diagnosis, and leakage current components were measured. Total energy applied to the ZnO blocks at each time is about 1,050[J] in 8/20[${\mu}\textrm{s}$] impulse current. From the experimental results, we proposed electrical parameters and leakage current level to diagnose arrester soundness.

피뢰기의 ZnO 소자 성능평가 분석 (Performance Evaluation and Analysis of ZnO Element for Distribution Line Arresters)

  • 김석수;김경운;박영창;조한구;박태곤;송일근;김주용
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 춘계학술대회 논문집 유기절연재료 방전 플라즈마
    • /
    • pp.78-81
    • /
    • 2000
  • Metal oxide surge arrester were developed in the late 1970s, and were immediately adopted as significant breakthrough in over voltage protection of power system. Work was continued throughout the world on the design, development and application of metal oxide surge arrester. This paper describes the evaluating test and results of practical use for analyzing the performance of gapless metal oxide surge arresters under various type test. In the result, ZnO element exhibited badness rate of 6.95 percent.

  • PDF

수배전계통의 여러 가지 고장조건에서 피뢰기에 흐르는 누설전류 (Leakage Currents Flowing through Lightning Surge Arresters under Various Fault Conditions in Receiving and Distribution Power Systems)

  • 이복희;길형준;강성만;최휘성
    • 조명전기설비학회논문지
    • /
    • 제18권5호
    • /
    • pp.132-139
    • /
    • 2004
  • 수배전계통의 고장에는 1선 지락, 선간 단락, 2선 지락 등의 고장이 있다. 가공 배전 계통에서 일어나는 대부분의 고장은 1선 지락이며, 피뢰기는 이러한 고장에 의한 빈번한 과전압에 의해 스트레스를 받는다. 본 논문에서는 수배전계통에서 일어날 수 있는 고장을 모의하여 여러 가지 고장에 의해 피뢰기에 흐르는 누설전류의 특성에 대하여 조사하였다. 결과적으로, $\pm$10[%] 범위의 전압변동률에 의해서 피뢰기에 흐르는 누설전류는 거의 변화가 없었다. 성능이 우수한 접지 시스템 하에서는 전압변동률은 피뢰기의 긴 시간동안의 동작에 별 영향을 줄 수가 없었다. 하지만, 1선 지락 고장에서 피뢰기에 흐르는 누설전류의 최대값은 비효과적인 접지 시스템의 운전 전압에서의 누설전류와 비교하였을 때 140배 이상이 되었다. 그러나 선간 단락과 2선 지락 고장의 경우에는 피뢰기의 누설전류에 거의 영향을 미치지 못했다.