• Title/Summary/Keyword: Zinc oxide (ZnO) surge arrester

Search Result 10, Processing Time 0.023 seconds

Deterioration Characteristics of ZnO Surge Arrester Blocks for Power Distribution Systems Due to Impulse Currents (임펄스전류에 의한 배전용 ZnO 피뢰기 소자의 열화특성)

  • Lee, Bok-Hee;Cho, Sung-Chul;Yang, Soon-Man
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.3
    • /
    • pp.79-86
    • /
    • 2013
  • In order to analyze the electrical performance of ZnO surge arresters stressed by the combined DC and AC voltages that are generated in DC/AC converter systems, the leakage current properties of ZnO surge arrester blocks deteriorated by impulse currents were investigated. The test specimens were deteriorated by the 8/$20{\mu}s$ impulse current of 2.5kA and the leakage currents flowing into the deteriorated zinc oxide(ZnO) arrester blocks subjected to the combined DC and power frequency AC voltages are measured. As a result, the leakage currents flowing through deteriorated ZnO surge arrester blocks were higher than those flowing through the fine ZnO surge arrester blocks and the larger the injection number of 8/$20{\mu}s$ impulse current of 2.5kA is, the greater the leakage current is. The leakage current-voltage curves(I-V curves) of the fine and deteriorated ZnO surge arrester blocks stressed by the combined DC and AC voltages show significant difference in the low conduction region. Also the cross-over phenomenon is observed at the voltage close to the knee of conduction on plots of I-V curves.

Electrical Characteristics of ZnO Surge Arrester Elements Subjected to the Mixed DC and 60[Hz] AC Voltages (직류+60[Hz] 교류 중첩전압에 대한 ZnO 피뢰기 소자의 전기적 특성)

  • Lee, Bok-Hee;Yang, Soon-Man
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.4
    • /
    • pp.41-47
    • /
    • 2012
  • This paper deals with the electrical characteristics related to power loss, equivalent resistance, and leakage currents flowing through new and deteriorated zinc oxide(ZnO) arrester elements subjected to the mixed DC and 60[Hz] AC voltages. The test specimens were deteriorated by 8/20[${\mu}s$] impulse current of 2.5[kA]. The leakage current-applied voltage($I-V$) characteristic curves of ZnO surge arrester elements were measured as a parameter of the ratio of the peak of 60[Hz] AC voltage to the peak of total voltage. As a consequence of test results, in case of the same applied voltage, the leakage currents flowing through the deteriorated ZnO arrester elements were higher than those flowing through the new ZnO surge arrester elements. The cross-over phenomenon in $I-V$ curves of ZnO surge arrester elements measured as a parameter of the mixed ratio of DC and AC voltages was observed at the low current domain. The effect of DC voltage on the leakage current flowing through ZnO surge arrester elements is pronounced at the same magnitude of test voltages. In addition, the larger the applied number of 8/20[${\mu}s$] impulse current of 2.5[kA] is, the greater the power loss is, in particular, the more severe the power loss increases at higher applied voltages.

Electrical Properties of 18[kV] ZnO Surge Arrester Stressed by the Mixed DC and 60[Hz] AC Voltages (직류+60[Hz]교류 중첩전압에 대한 18[kV] ZnO 피뢰기의 전기적 특성)

  • Lee, Su-Bong;Lee, Seung-Ju;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.10
    • /
    • pp.66-72
    • /
    • 2007
  • This paper describes the characteristics of power loss and leakage currents flowing through new and used 18[kV] zinc oxide(ZnO) surge arrester under the mixed DC and AC voltages. The mixed DC and AC voltage generator of 50[kV] peak was designed and fabricated. The I-V curves of ZnO surge arrester were measured as a function of the voltage ratio K. The I-V curves under the mixed DC and AC voltages lay between the pure DC and AC characteristics, and the cross-over phenomenon in both I-V curves and R-V curves was observed at the low current region. As a result, the increase of DC component in the mixed voltages causes the increase of resistive component of total leakage current of ZnO surge arrester. Also, in the case of same applied voltage, the leakage current flowing through the used ZnO surge arrester was higher than that of the new ZnO surge arrester.

The electrical properties of in 18kV ZnO surge arrestor with mixed direct and 60Hz Alternating Voltage (중첩전압(직류 +60Hz 교류)에서 18kV 배전용 피뢰기의 전기적 특성)

  • Lee, Bok-Hee;Lee, Seung-Ju;Lee, Su-Bong;Jung, Dong-Cheol;Baek, Young-Hwan
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2007.05a
    • /
    • pp.291-294
    • /
    • 2007
  • This paper preserts the characteristics of leakage currents flowing through 18 kV zinc oxide (ZnO) surge arrester under the mixed DC and AC voltages. The I-V curves of ZnO surge arrester were measured as a function of the voltage ratio K The I-V curves under the mixed DC and AC voltages lay between the pure DC and AC characteristics, and the cross-over phenomenon in I-V curves was observed at the low current region As a result, the increase of DC component to mixed voltages causes the increase of resistive component of total leakage current th ZnO surge arrester.

  • PDF

Temperature dependent characteristics of leakage currents of ZnO blocks (온도에 따른 ZnO 피뢰기 소자의 누설전류의 온도의존성)

  • Lee, Bok-Hee;Lee, Su-Bong;Li, Feng;Kim, Dong-Sung
    • Proceedings of the KIEE Conference
    • /
    • 2006.07c
    • /
    • pp.1572-1573
    • /
    • 2006
  • This paper presents electrical properties of Zinc Oxide(ZnO) surge arrester blocks under the power frequency AC voltages and various temperatures. The leakage current, $I_{R}-V$ curios and power dissipation for the fine and aged ZnO surge arrester blocks were measured as a function of the temperatures and applied voltages. When the temperature is increased from $50\;[^{\circ}C]$ to $150\;[^{\circ}C]$, the total leakage current significantly increased at the sane applied voltage level. Also, the resistive leakage currents and power dissipation were increased with increasing temperature. The leakage current and power dissipation of the aged ZnO arrester blocks were higher than the fine ZnO arrester blocks.

  • PDF

Electrical Behaviors of ZnO Elements under Combined Direct and Alternating Voltages

  • Yang, Soon-Man;Lee, Bok-Hee;Paek, Seung-Kwon
    • Journal of Electrical Engineering and Technology
    • /
    • v.4 no.1
    • /
    • pp.111-117
    • /
    • 2009
  • This paper presents the characteristics of leakage currents flowing through zinc oxide (ZnO) surge arrester elements under the combined direct-current (DC) and 60 Hz alternating-current (AC) voltages. The current-voltage characteristic curves (I-V curves) of the commercial ZnO surge arrester elements were obtained as a function of the voltage ratio a. At constant peak value of the combined DC and AC voltage, the resistive leakage current of the ZnO blocks was significantly increased as the voltage ratio $\alpha$ increased. The I-V curves under the combined DC and AC voltages were placed between the pure DC and AC characteristics, and the cross-over phenomenon in both the I-V curves and R-V curves was observed at the low current region. The ZnO power dissipation for DC voltages was less than that for AC voltage in the pre-breakdown region and reversed at higher voltages.

Discharge Luminous Phenomena Caused Between ZnO Surge Arrester Block and Electrodes (산화아연 피뢰기 소자와 전극사이에 발생하는 방전광 현상)

  • Lee, Bok-Hee;Park, Keon-Young;Kang, Sung-Man
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.19 no.3
    • /
    • pp.44-50
    • /
    • 2005
  • This paper deals with the characteristics and reduction methods of the plasma luminosity caused between the ZnO surge arrester block and metal electrodes. In this study, the impulse current generator that can generate $8/20[{\mu}s]$ impulse currents with a peak short-circuit of 10[kA] is designed and fabricated. Plasma luminosity phenomena for fine and used ZnO blocks were observed as a function of the contact states between the ZnO block and electrodes and the polarity of applied impulse voltages. As a result, discharge luminous events are produced near the contact edges between the ZnO block and metal electrodes. The discharge plasma luminosity between the ZnO surge arrester block and low potential electrode is more intensive than that between the ZnO surge arrester block and high potential electrode. Surface flashover of ZnO blocks are mainly caused by plasma generation near the edge of metal electrode. Also, plasma luminosity for the fine ZnO blocks is less than that for the used ZnO blocks. Plasma luminosity at the contact of the ZnO block and ring-type electrode is more intensive than that at the contact of ZnO block and disk electrode. It is desirable to use the disk electrode with the proper contact area to reduce the plasma luminosity caused at the contact point between the ZnO block and electrodes.

A New Approach to On-Line Monitoring Device for ZnO Surge Arresters

  • Lee Bok-Hee;Gil Hyoung-Jun;Kang Sung-Man
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • v.5C no.3
    • /
    • pp.131-137
    • /
    • 2005
  • This paper describes a new approach to the algorithm and fundamental characteristics of the device for monitoring the leakage currents flowing through zinc oxide (ZnO) surge arresters. In order to obtain a technique for a new on-line monitoring device that can be used in the deterioration diagnosis of ZnO surge arresters, the new algorithm and on-line leakage current detection device for extracting the resistive and capacitive currents using the phase shift addition method were proposed. The computer-based on-line monitoring device can sense accurately the power frequency leakage currents flowing through ZnO surge arresters. The on-line leakage current monitoring device of ZnO surge arresters proposed in this work has the high sensitivity compared to the third harmonic leakage current detection devices. As a consequence, it was found that the proposed leakage current monitoring device would be useful for forecasting the defects and degradation of ZnO surge arresters.

Leakage Currents Flowing through Lightning Surge Arresters under Various Fault Conditions in Receiving and Distribution Power Systems (수배전계통의 여러 가지 고장조건에서 피뢰기에 흐르는 누설전류)

  • Lee, Bok-Hee;Kil, Hyeong-Joon;Kang, Sung-Man;Choi, Hwee-Sung
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.18 no.5
    • /
    • pp.132-139
    • /
    • 2004
  • Unsymmetrical faults are classified into single line-to-ground faults, line-to-line faults, or double line-to-ground faults in receiving and distribution power systems. Many of overhead distribution-line faults are single line-to-ground faults, and lightning surge arresters are stressed by system frequency overvoltages due to unsymmetrical faults. In this work, the unsymmetrical faults in receiving and distribution systems were experimentally simulated, and the characteristics of total leakage current flowing through lightning surge arresters due to various unsymmetrical faults were investigated. As a result, a little variations of the leakage current flowing through Zinc oxide (ZnO) surge arresters in the range of $\pm$10[%] voltage regulations were observed. It could be concluded that the unsymmetrical faults have no effect on the long-term life performance of ZnO surge arresters in effective grounding systems. On the other hand, the magnitude of the leakage current flowing through ZnO surge arrester elements under single line-to-ground faults was more than 140 times as compared with that under normal operating voltages in ineffective grounding systems. But abnormal voltages caused by line-to-line faults and double line-to-ground faults have a little effect on total leakage current of ZnO surge arrester elements.

AC Accelerated Ageing Characteristics of Zinc Oxide Varistors for the Station Class Lightning Surge Arresters (발변전급 피뢰기용 산화아연소자의 AC 가속열화특성)

  • Cho, Han-Goo;Yoon, Han-Soo;Kim, Suk-Soo;Han, Dong-Hee
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.315-316
    • /
    • 2005
  • This paper describes the AC accelerated ageing characteristics of zinc oxide varistors for the station class lightning surge arresters. ZnO varistors whose rated voltage were 3.27kV, 4.00kV, and 6.00kV were manufactured with general ceramic production methods. The power loss of sample A varistors rapidly increased and eventually showing the thermal run-away, but sample B and sample C varistors exhibited negative creep phenomena in power losses during the test.

  • PDF