• Title/Summary/Keyword: Zero Impedance

Search Result 131, Processing Time 0.021 seconds

Current limiting characteristics of the resistive and inductive SFCL in the double line-to-ground fault (2선 지락사고에 대한 저항형과 유도형 한류기의 전류제한특성)

  • Choi, Hyo-sang;Hyun, Ok-Bae;Kim, Sang-Joon;Han, Byoung-Sung
    • Proceedings of the KIEE Conference
    • /
    • 1999.07c
    • /
    • pp.1369-1372
    • /
    • 1999
  • We investigated the current limiting characteristics of resistive and inductive SFCLs with 100${\Omega}$ of Quench impedance for a double line-to-ground fault, in the 154 kV transmission system. The fault simulation at the phase angles $0^{\circ}$, $45^{\circ}$, and $90^{\circ}$ showed that the resistive SFCL limited the fault current less than 17 kA without any DC component after one half cycle from the instant of the fault. On the other hand, the inductive SFCL suppressed the current below 12 kA, but with 3$\sim$5 kA of DC component which decreased to zero in 6 cycles. We concluded that the inductive SFCL had higher performance in current limiting but the resistive SFCL was better from the view point of DC components.

  • PDF

Theoretical and Experimental Studies on the Adsorption of N-[(E)-Pyridin-2-ylmethylidene] Aniline, a Schiff Base, on Mild Steel Surface in Acid Media

  • N, Mohanapriya.;M, Kumaravel.;B, Lalithamani.
    • Journal of Electrochemical Science and Technology
    • /
    • v.11 no.2
    • /
    • pp.117-131
    • /
    • 2020
  • The adsorption of N-[(E)-Pyridin-2-ylmethylidene] aniline, a Schiff base, on to mild steel surface in 1M HCl and 0.5 M H2SO4 solutions and the consequent corrosion protection were studied employing weight loss method, electrochemical impedance spectroscopy and potentiodynamic polarization measurements. DFT calculations were performed to investigate its interaction with the metal surface at the atomic level to understand its inhibition mechanism. The adsorption process is well described by the Langmuir isotherm. The thermodynamic parameters indicated that the adsorption is spontaneous and the interaction of the inhibitor at the mild steel surface is mainly through physisorption. The Ra values obtained in AFM studies for the uninhibited and inhibited sample in HCl media respectively are 0.756 and 0.559 ㎛, and that in H2SO4 media are 0.411 and 0.406 ㎛. The lesser roughness values of the inhibited sample shows the adsorption of the molecules onto the mild surface. The inhibition efficiencies were found to improve with concentration of the inhibitor and the maximum efficiency was observed at 400ppm in all the investigation methods adopted. The inhibitor was found to exhibit a higher efficiency in HCl media (95.7%) than in H2SO4 (92.8%). The theoretical and experimental results are found to be in good agreement.

Fuzzy Inference System Based Distance Relay Algorithm Development for Protecting an Underground Power Cable Systems (퍼지추론시스템 기반 지중송전계통 보호용 거리계전 알고리즘 개발)

  • Jung, Chae-Kyun;Oh, Sung-Kwun;Park, Keon-Jun;Lee, Jae-Kyu;Lee, Jong-Beom
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.2
    • /
    • pp.172-178
    • /
    • 2008
  • If the fault occurs on the underground power cable systems, the fault current on the sheath has an influence on all sections of cable because it's returned through earth at the directly grounded point and operation point of SVL(Sheath Voltage Limiter) on each insulated joint box. Therefore, the earth resistance and the operation of SVL have an effect on the zero-sequence current, and then the impedance between relaying point and fault point is increased. That causes the overreach of distance relay. For these reasons, the distance relay algorithm for protecting an underground power cable systems hasn't been developed till now. In this paper, new distance relay algorithm is developed for protecting a underground power cable system using fuzzy inference system which is the one of ACI(Advanced Computational Intelligence) techniques. This algorithm is verified by EMTP simulation of real power cable system, and proves to effectively advance the errors

Full Bridge Resonant Inverter Using Asymmetrical Control with Resonant-frequency Tracking for Ultrasonic Cleaning Applications

  • Jittakort, Jirapong;Sangswang, Anawach;Naetiladdanon, Sumate;Koompai, Chayant;Chudjuarjeen, Saichol
    • Journal of Power Electronics
    • /
    • v.17 no.5
    • /
    • pp.1150-1159
    • /
    • 2017
  • Flexibility in the power control of ultrasonic transducers has remained a challenge for cleaning applications. This paper introduces a modification of the existing piezoelectric ceramic transducer (PCT) circuit to increase the range of operation through its impedance characteristics. The output power is controlled using the asymmetrical voltage-cancellation (AVC) method. Together with a phase-locked loop control, the switching frequency of the inverter is automatically adjusted to maintain a lagging phase angle under load-parameter variations during the cleaning process. With the proposed modification, the region of the zero-voltage switching (ZVS) operation is extended, which results in a wider range of output power control. A hardware prototype is constructed and the control algorithm is implemented using an STM32F4 microcontroller. Simulation and experimental results are provided to verify the proposed method for a 50-W PCT. The operating frequency and output power ranges under study are 37 - 41 kHz and 15.8 - 50 W, respectively.

High-frequency Magnetic Properties of Ni-Zn-Co Ferrites Used for Mangetic Shielding in NFC (NFC의 자기 차폐용 Ni-Zn-Co 페라이트 자성체의 고주파 자기특성)

  • Ryu, Yo-Han;Kim, Sung-Soo
    • Journal of Powder Materials
    • /
    • v.21 no.6
    • /
    • pp.429-433
    • /
    • 2014
  • This study investigated the magnetic properties and frequency dispersion of complex permeability of Ni-Zn-Co ferrites used for magnetic shielding in near field communication (NFC) system. The sintered specimens of $(Ni_{0.7}Zn_{0.3})_{1-x}Co_xFe_2O_4$ composition were prepared by the conventional ceramic processing. The coercive force and saturation magnetization were measured by vibrating sample magnetometer. The complex permeability was measured by RF impedance analyzer in the range of 1 MHz~1.8 GHz. The coercive force increased and saturation magnetization decreased with increasing the Co substitution. The real and imaginary parts of complex permeability decreased and the resonance frequency increased with Co substitution, which was attributed to the increase in crystal anisotropy field and reduction in saturation magnetization. The effect of Co substitution could be found in reducing the magnetic loss to nearly zero at the operating frequency of NFC (13.56 MHz).

Study of the Applicability of the Carson Line Model for the Series Reactance Calculation of the Power Feeding Lines with no Ground Return (전송로의 직렬리앤턴스 산정 시 Carson 모델의 적용범위 검토)

  • Chung, Sang-Gi;Kwon, Sam-Young;Chang, Sang-Hoon;Jang, Dong-Uk
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.2
    • /
    • pp.225-231
    • /
    • 2009
  • In this paper, it is shown that Carson's equation can still be applied for the calculation of the series reactance of transmission lines with no ground return current as well as the one with ground return. It is proved in the following method. First two voltage drop equations for three-phase three wire transmission line are derived, one without considering ground return and the other using Carson's equation. The impedance matrix of the two equations are different from each other. But if we put the condition of zero ground current, $I_a+I_b+I_c=0$, those two equations becomes the identical equations. Therefore even a transmission line is not grounded, its line parameters can still be obtained using the Carson's equation. It has been confused whether or not Carson's equation can be used for an ungrounded system. It is because where ever Carson's equation is shown in the book, it also says that the system has ground return current paths as a premise. It is also verified with EMTP studies on the test circuit.

Characteristics of Wireless Power Transmission applying the superconducting coil (초전도 코일을 적용한 WPT 특성)

  • Jeong, In-Sung;Choi, Hyo-Sang
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.62 no.6
    • /
    • pp.762-766
    • /
    • 2013
  • Interest in Wireless Power Transmission (WPT) technology has been increasing worldwide recently. This trend is proved by commercialized products such as electric toothbrush, wireless razor, and wireless charger for mobile phone battery. Studies for enhancing the applicability of the technology have been continuously conducted. Currently the WPT technology is based on the technologies using microwave, inductively coupling, and magnetic resonance. In the meantime, development of the microwave-based WPT faces difficulty due to health hazards involved in the technology, and application of the WPT technology using inductively coupling is restricted by area due to the problem of transmission length. In comparison, the WPT technology using magnetic resonance draws attention in terms of efficiency and transmission length. In this study, the sending coil based on the WPT technology using magnetic resonance system was replaced with an HTS coil to enhance transmission efficiency. Since the HTS coil has a zero resistance, power transmission loss can be minimized. At the same time, size of the current density could be increased to 100 times or more than typical coils. In addition, through impedance matching of LC device, maximal resonance properties were induced and consequently, frequency selection quality characteristics or Q was enhanced. As a result, the WPT type using the HTS coil showed a longer transmission length and better transmission efficiency compared with the WPT type using typical coils.

A Force-Reflecting Haptic interface using Ultrasonic Motors (초음파 모터를 이용한 힘 반영 촉각장치)

  • Shin, Duk;Oh, Geum-Kon;Kim, Young-Dong
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.13 no.1
    • /
    • pp.111-118
    • /
    • 1999
  • Throughout this thesis, I describe the design, fabrication, and evaluation of the 3 DOF farce-reflecting haptic interface using USMs(ultrasonic motors). This haptic interface allows a htmlaIl "observer" to explore and interact with a virtual environrrent for the sense of touch. To effectively display the mechanical impedance of the htmlaIl hand we need a haptic device with specific characteristics, such as low inertia, alrmst zero friction and very high stiffness. USMs have attracted considerable attention as the actuator satisfied these conditions. An observer may grasp the end effector of revice and interact with surfaces and objects created within a virtual environment The revice provires force feedback, allowing users to "feel" objects within the environment. The device works very well, as users are able to detect the edge of the wall, the stiffness of the button and the puncture. TIle force-reflecting haptic interface could be suitable as a master for micro-surgery or as an interface to virtual reality training systems.

  • PDF

Effective Harmonic Diagnose Tool for Power Quality Problems (전기품질개선을 위한 효율적인 고조파 진단 툴 개발)

  • 설용태;이의용
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.3 no.1
    • /
    • pp.63-68
    • /
    • 2002
  • In this paper harmonic diagnose tool is described for electric evaluate the power quality at industrial power systems is described both simulation and experimental testing during various operation conditions. PTW (Power Tools for Windows) and harmonic measuring instrument are organized around personal computer and/or instrumentation study environments interconnected via RS-232. Unknown zero sequence impedance data of cable is calculated by the modified T&D and BICC method. IEEE standard is also used to estimate the transformer input data. the proposed system provides a flexible and effective environment to diagnose the power quality at industrial distribution systems by utilizing simulations and actual field data.

  • PDF

A Study on the Fault Discrimination and Location Algorithm in Underground Transmission Systems Using Wavelet Transform and Fuzzy Inference (지중송전계통에서 Wavelet 변환과 퍼지추론을 이용한 고장종류판별 및 고장점 추정에 관한 연구)

  • Park, Jae-Hong;Lee, Jong-Beom
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.55 no.3
    • /
    • pp.116-122
    • /
    • 2006
  • The underground transmission lines is continuously expanded in power systems. Therefore the fault of underground transmission lines are increased every year because of the complication of systems. However the studies dealing with fault location in the case of the underground transmission lines are rarely reported except for few papers using traveling wave method and calculating underground cable impedance. This paper describes the algorithm using fuzzy system and travelling wave method in the underground transmission line. Fuzzy inference is used for fault discrimination. To organize fuzzy algorithm, it is important to select target data reflecting various underground transmission line transient states. These data are made of voltage and average of RMS value on zero sequence current within one cycle after fault occurrence. Travelling wave based on wavelet transform is used for fault location. In this paper, a variety of underground transmission line transient states are simulated by EMTP/ATPDraw and Matlab. The input which is used to fault location algorithm are Detail 1(D1) coefficients of differential current. D1 coefficients are obtained by wavelet transform. As a result of applying the fuzzy inference and travelling wave based on wavelet transform, fault discrimination is correctly distinguished within 1/2 cycle after fault occurrence and fault location is comparatively correct.