• 제목/요약/키워드: Z continuous winding

검색결과 1건 처리시간 0.013초

초전도 변압기의 절연기반 연구 (A Study on the Insulation Basis of Hts Transformer)

  • 천현권;곽동순;윤문수;김상현
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2005년도 하계학술대회 논문집 Vol.6
    • /
    • pp.639-642
    • /
    • 2005
  • HTS Transformer developing is developing a power distribution and transmission class HTS transformer that is one of the 21st century superconducting frontier projects. Therefore, we prepared the model, that is Z continuous winding from Kapton insulated Cu tape for a small simulated the HTS transformer. For the development of electrical insulation design of a HTS transformer with Z continuous winding, we have been discussed insulation composition and investigated breakdown characteristics such as breakdown of liquid $N_2(LN_2)$, polymer and surface flashover on FRP and breakdown-surface combination in $LN_2$. Also we have been designed and manufactured a bobbin that has spiral slot for the Z continuous winding. The Z continuous winding mini-model from Kapton film insulated Cu tape for simulated 22.9kV class HTS transformer has been constructed using 0.1 % breakdown strength obtained by Weibull distribution. The widing model was measured their insulation characteristics such as ac (50kV, 1min) and impulse (154kV, $1.2\times50{\mu}s$ full wave, 3 times) withstand test and its excellent performance was confirmed.