• 제목/요약/키워드: Xlpe

검색결과 449건 처리시간 0.026초

XLPE의 절연파괴특성에 미치는 휘발성 불순물의 영향 (Effects of Volatile Impurities on Dielectric Breakdown Characteristics of XLPE)

  • 조영신;심미자;김상욱
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1997년도 춘계학술대회 논문집
    • /
    • pp.301-304
    • /
    • 1997
  • Effects of volatile impurities on deterioration characteristics of XLPE were investigated. Block type plate with needle-plane electrode and artificial void filled with $N_2$gas or humidity was subjected under high electric field. The dyed region by oxidation reaction around the artificial void filled with humidity was detected before tee initiation. Electrical tree was started from the tip of void filled with $N_2$gas earlier than humidity.

  • PDF

XLPE/EPOM 계면의 전기적 특성 (Electrical Characteristics on the Interface between XLPE/EPDM)

  • 한성구;조정형;이창종;김종석;서광석;박대희;한상옥
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1996년도 춘계학술대회 논문집
    • /
    • pp.235-238
    • /
    • 1996
  • In this paper, We intended to evaluate the characteristics of XLPE/EPDM interface which exists in the cable joint. The fault was mainly occurred in this interface. Thus we looked into the electrical characteristics through the conduction current and the breakdown test. Through from the experiment, we obtained the result that the conduction current in this interface flowed less than other dielectric materials, that the breakdown strength was higher and that the pressure dependance ㅐf the breakdown strength was higher.

  • PDF

방전발생 빈도해석을 통한 XLPE 절연진단 (XLPE Diagnostics according to Analysis of Discharge Number)

  • 김탁용;신종열;이수원;홍진웅
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.89-91
    • /
    • 2004
  • 본 논문은 XLPE 절연재료의 보이드에 따른 방전빈도를 와이블 함수로 조사하였으며, 또한 방전빈도와 결함에 대한 상관관계를 와이블 해석을 이용한 진단시스템을 제안하고 있다. 인가전압은 교류 60[Hz]를 방전개시전압을 기점으로 1[1kV]씩 승압하였으며, 전하량이 512[pC]이상이 발생하면 검출한도를 초과하므로 실험을 멈추었다. 그 결과 보이드 시료에서 큰 형태파라메터값을 나타냄을 확인하였다.

  • PDF

전력용 XLPE Cable의 부분방전과 방사전자파 특성 (Characteristics of Radiated Electromagntic Wave and Partial Discharge in Power XLPE (Crosslinkable Polyethylene ) cable)

  • 이현철;박광서;윤대희;이상훈;김충년;박원주;이광식
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2003년도 학술대회논문집
    • /
    • pp.377-380
    • /
    • 2003
  • XLPE(Crosslinkable Polyethylene) 케이블은 절연성이 우수하여 전력용으로 많이 사용되고 있다. 그러나, 시설된지 오래된 케이블의 노후화와 지중 매설 케이블의 시공시 및 포설이후 외부손상 등으로 인해 정전사고가 많이 발생하고 있는 추세이다. 본 논문은 케이블의 외부 손상에 의해 발생하는 부분방전에 의해 공간으로 전파되는 전자파를 측정하는 UHF법을 통해 주파수 스펙트럼을 측정하고 측정된 데이터 처리를 통해 방전진전에 따른 스펙트럼의 특성을 분석하였다. $^{[1]}$[3][6]//

  • PDF

XLPE의 수트리와 절연파괴 현상에 관한 연구 (A Study on Phenomena of Watertree and Dielectric Breakdown in XLPE)

  • 이성일
    • 대한안전경영과학회지
    • /
    • 제3권4호
    • /
    • pp.45-52
    • /
    • 2001
  • In order to Investigate water tree degradation behavior on XLPE cable, direct voltage of 200 to 800V has been applied to the material at 5$0^{\circ}C$~10$0^{\circ}C$, and the water tree property has been correlated with voltage and temperature. The leakage current was increase as temperature increased and the Ohm's law was generally satisfied in this experiment though some experimental errors were found. The leakage current was decreased and reached to the stable state with time. It was also shown that the time for the stabilization of leakage current was lessened as voltage increased

  • PDF

고주파 전압이 XLPE cable의 가속열화에 미치는 영향 분석 (Analysis of Influence for High Frequency voltage Accelerated Aging of XLPE Cable)

  • 김위영;허종철;윤대혁;박태곤
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 C
    • /
    • pp.1670-1672
    • /
    • 2004
  • XLPE compound have used for insulation of 22.9kV power cable. XLPE insulation is aged for use long time in distribution line. The cause of aging is water tree is happening and growth. Accelerated water tree test method are Accelerated volatge aging method and high frequency aging method. In this paper, high frequency accelerated water tree was performed. And the result was analysed AC breakdown voltage and size and number of water trees.

  • PDF

고압용 XLPE의 유전특성에 관한 연구 (A Study on Dielectric Properties of XLPE for High Voltage)

  • 이용성;이경용;이관우;최용성;박대희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 C
    • /
    • pp.1561-1563
    • /
    • 2004
  • In this paper, we researched the dielectric properties and voltage dependence on slice XLPE sheet from 22[kV] and 154[kV] power cable. We studied effects for impurities and water for semiconductor shield through a dielectric properties experiment to estimate performance of insulating materials in power cable. Capacitance and tan${\delta}$ of 22[kV], 154[kV] were 53/43[pF] and $7.4{\times}10^{-4},\;2.1510^{-4}$. In these results, the trend was increased with the increase of temperature. The tan${\delta}$ of XLPF/ semiconductor layer was increased as compared with that of XLPE. Dielectric properties reliability of tan${\delta}$ was small.

  • PDF

기계적 스트레스가 XLPE에서의 전기트리 개시특성에 미치는 영향 (The Effects of Mechanical Stress on the Initiation Characteristics of Electrical Tree in XLPE)

  • 신두성;최수걸;전승익
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.241-244
    • /
    • 2001
  • 절연체의 수명과 직접적인 관련이 있는 전기트리의 개시특성을 연구하는데 있어서, 전기트리의 개시시간이 매우 길기 때문에 실험적으로 절연재료의 수명을 구하는데 어려움이 있다. 따라서. 본 논문에서는 Weibull 해석을 이용하여, 일반적으로 사용되는 가속시험법에 의하여 얻어진 전기트리 개시전계를 사용하여 일정전압 인가시에 전기트리 개시시간을 추정하는 방법을 이론적으로 고찰하여 실험에 적용하였다. 또한 기계적 스트레스에 의한 전기트리 개시특성을 평가하기 위하여 기계적 스트레스를 모의한 XLPE 시료에 대하여 이러한 기계적 스트레스가 전기트리 개시전계 및 개시시간 특성에 미치는 영향을 평가하였다. 기계적 스트레스가 전기트리 개시전계 뿐만 아니라 개시시간을 현저하게 감소시켰으며, XLPE의 장기적인 신뢰성을 보증하기 위해서는 이러한 기계적 스트레스를 완화시키는 것이 매우 중요하다.

  • PDF

전력케이블 접속재 XLPE/EPDM 계면의 부분방전 특성 (Partial Discharge Characteristics of the XLPE/EPDM Interface in Power Cable Joint)

  • 조경순;홍진웅
    • 한국전기전자재료학회논문지
    • /
    • 제20권9호
    • /
    • pp.780-786
    • /
    • 2007
  • This paper describes the influence on partial discharge characteristics of defects at the model XLPE/EPDM interfaces of power cable joints. The defects of void and copper which could inadvertently be present at the joint interface. We measured ${\Phi}-n,\;{\Phi}-q$ patterns by a computer-aided partial discharge measuring system. Several parameters i, e, maximum discharge $q_{max}$ [pC], average discharge q [pC/cycle], and average angle of discharge ${\Theta}g$ [deg] were found to depend upon the defect type varying applied voltage. As the result of time evaluation, partial discharges are small different at copper defects, but is decreasing obviously about 20 minutes at void defect. It considered that difference of magnitude of total positive discharge of Q+ [pC] and total negative discharge of Q- [pC] is SPMD(swarming pulsive micro discharges).

154kV OF/XLPE 케이블 이종접속함의 실선로적용 (The Application of 154kV OF/XLPE Transition Joint)

  • 황순철;최종현;오종옥;고창성
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1991년도 하계학술대회 논문집
    • /
    • pp.274-276
    • /
    • 1991
  • Since the successful development of 154kV XLPE cable in 1983, its commercial use has been drastically expanded due to technical advantages and high performance of insulation, Futhermore, the large conductor size of 1200ml and 2000ml has been mainly employed in Korea for the purpose of meeting the bulk power demand in urban area. However, it is highly required to solve the problems which can be occured at the level of the joints between the cables of different type such as between existing OF and XLPE cables.

  • PDF