• 제목/요약/키워드: Wide Ratio Error Voltage Transformer

검색결과 5건 처리시간 0.019초

넓은 범위의 비오차를 갖는 전압변성기를 이용한 계기용 변성기 비교 측정 장치의 비오차 직선성 평가기술 (Evaluation Technique for Linearity of Ratio Error of Instrument Transformer Comparator Using Voltage Transformer with Wide Range of Error Ratios)

  • 정재갑;권성원;김한준;박영태;김명수
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제54권2호
    • /
    • pp.66-70
    • /
    • 2005
  • Linearity of ratio error of instrument transformer comparator has been tested using wide ratio error voltage transformer(VT) with the ratio errors in the range of -3 % to 3 %. The technique is the method for evaluation of the linearity for instrument transformer comparator by comparing both the theoretical and experimental values in wide ratio error VT. The developed method has been successfully applied for calibration and correction in instrument transformer comparator belonging to industry.

66kV급 전압변성기 비교측정 장치의 현장 평가설비 구축 (Construction of On-Site Calibration Facilities of 66 kV Voltage Transformer Comparator System)

  • 정재갑;이상화;권성원;김명수
    • 전기학회논문지
    • /
    • 제56권7호
    • /
    • pp.1268-1274
    • /
    • 2007
  • A recently developed methods for the on-site calibration of the voltage transformer (VT) comparator system have been reviewed in the paper. The method utilizes the several traveling standards consisting of the VT, the non-reactive standard resistors, the wide ratio error VT, and the decade resistors. The VT is used for the absolute evaluation of a standard VT belonging to the industry. The non-reactive standard resistor and wide ratio error VT are used for the linearity check of errors in the voltage comparator of the industry. The decade resistors are used for evaluation of a VT burden of the industry.

전압변성기 비교 측정 장치의 비오차 및 위상각 오차의 직선성 평가기술 (Evaluation Technique of Linearity of Ratio Error and Phase Angle Error of Voltage Transformer Comparison Measurement Equipment)

  • 정재갑;박영태;권성원
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제53권9호
    • /
    • pp.470-474
    • /
    • 2004
  • Both ratio error and phase angle error in voltage transformer(VT) depend on values of burden of VT used. A method of evaluation for linearity of ratio error and phase angle error in VT measurement equipment have been developed using the standard resistance burdens, with negligible AC-DC resistance difference less than $10^-6$. These burden consists of five standard resistors, with nominal resistance of 100 $\Omega$, 1 k$\Omega$, 10 k$\Omega$, 100 k$\Omega$, and 1 M$\Omega$. The developed method has been applied in VT measurement equipment of industry and the validity of the developed method has been verified by showing the consistency of the result of linearity obtained using VT with wide ratio error.

표준저항기를 이용한 전압변성기 비교기의 비오차 평가 (Evaluation for Ratio Error of Voltage Transformer Comparator using Standard Resistors)

  • 한상길;김윤형;정재갑;한상옥
    • 전기학회논문지P
    • /
    • 제57권4호
    • /
    • pp.412-416
    • /
    • 2008
  • We have developed the calibration technique of the VT comparator using nonreactive standard resistors, which evaluates both accuracy and linearity of the VT comparator by comparing experimental values with theoretical values. The correction values of VT comparator obtained by using both our method and wide ratio error VT are consistent within the expanded uncertainty. Furthermore the specification for ratio error of VT comparator have been revaluated.

고온초전도변압기 절연설계를 위한 격벽효과와 수명특성 (V-t and Barrier Characteristics for HTS Transformer Insulation Design)

  • 정종만;백승명;김영석;곽동순;김상현
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2003년도 춘계학술대회 논문집 유기절연재료 방전 플라즈마연구회
    • /
    • pp.61-64
    • /
    • 2003
  • In the response to an increasing demand for electrical energy, much effort aimed to develop and commercialise HTS power equipments is going on around the world. For the development, it is necessary to establish the dielectric technology in $LN_2$. Hence many types of dielectric tests should be carried out to understand the dielectric phenomena at cryogenic temperature and to gather various dielectric data. Among the many types dielectric tests, the barrier effect were conducted with the simulated electrode after analysing the insulating configuration of the pancake coil type HTS transformer. The influence of a barrier on the dielectric strength was measured according to the size and the position of the barrier. It was shown that the effectiveness, the ratio of the breakdown voltage in presence of barrier to the voltage without barrier, is highest when the barrier is placed at the needle electrode side. And the barrier effect was not depend on the electrode array. The life time to breakdown with decreasing the applied voltage was increased remarkably having wide error band but the shape parameter in Weibull distribution was almost constant.

  • PDF