• Title/Summary/Keyword: Vestibule

Search Result 91, Processing Time 0.023 seconds

Numerical Study on Air Egress Velocity in Vestibule Pressurization System : Characteristics of Air Flow in the Vestibule with Multiple Fire Doors in an Apartment Building (부속실 가압 시스템의 방연풍속에 관한 수치해석적 연구: 공동주택 부속실내에 다수 출입문의 존재시 기류특성)

  • Seo, Chanwon;Shin, Weon Gyu
    • Fire Science and Engineering
    • /
    • v.28 no.5
    • /
    • pp.30-36
    • /
    • 2014
  • The pressurized smoke control system in the vestibule is important for fire safety in buildings because it is concerned with egress time of people and the safety of fire fighters. The vestibule pressurization system can prevent smoke from entering the vestibule using differential pressure when fire doors are closed and using the egress velocity when fire doors are open. Air supplying units in the vestibule need to be arranged by taking account of the location of doors and the volume of the vestibule in order to assure the uniform air egress velocity through a fire door when it is open. In this study, computational fluid dynamics (CFD) simulations were conducted for the vestibule where multiple doors are installed and it was found that the reverse flow occurs when the damper position in vestibule is not appropriate.

Vestibule Smoke Control Considering the Stack Effect and the Opening of the Outside Door (굴뚝효과와 외부출입문 개방을 고려한 부속실 제연)

  • Yongkwang Kim;Zudal Son;Seoyoung Kim;Hasung Kong
    • Journal of the Korea Safety Management & Science
    • /
    • v.26 no.1
    • /
    • pp.15-24
    • /
    • 2024
  • The purpose of this study is to improve the stack effect of the staircase and the failure to take into account the opening of the outside door of the staircase, which are the disadvantages of the existing smoke control only vestibule. As a result of the study, the new vestibule and the staircase simultaneous smoke control are equipped with an exhaust flap damper with an effective opening area of about 0.25 m2 in the upper part of the staircase, and a ventilator-type air supply fan of about 5 m3/s in the lower part, and take measures to prevent overpressure in the staircase. If you use the new simultaneous smoke control method of the vestibule and staircase, you can achieve the following effects. First, it is possible to open the external entrance door. Second, it can reduce the stack effect. Third, the staircase door closes automatically without fail. And a new method of preventing overpressure was proposed for the vestibule.

Design for Pressurizing System about Vestibule by Stack Effect & Engineering Analysis - Focused on Case Study - (굴뚝효과와 공학적분석에 의한 부속실 가압시스템 설계 - 사례를 중심으로 -)

  • Kim, Yong-Kwang
    • Fire Science and Engineering
    • /
    • v.23 no.4
    • /
    • pp.145-153
    • /
    • 2009
  • We are generally applicate smoke control only vestibule about special escape staircase, it is one of some smoke control model of NFSC 501A. But there are some point at issue in this system. The smoke control system on supervision field of writer is smoke control only vestibule same as the other resemble field. Writer studied in the concrete to find a solution at this issue, and derived a conclusion the most reasonable system on the field is "same time smoke control for staircase and vestibule" by the engineering analysis considering stack effect.

Experimental Study on Features of Air Egress Velocity in Vestibule Pressurization System (특별피난계단 부속실 제연설비의 방연풍속 기류특성에 관한 실험적 연구)

  • Ryu, Sung-Ho;Lee, Su-Kyung;Hong, Dae-Hwa;Yoon, Myong-O;Choi, Keum-Ran;Park, Jae-Hyun
    • Fire Science and Engineering
    • /
    • v.24 no.5
    • /
    • pp.79-86
    • /
    • 2010
  • In this study, we confirmed the fact that air egress velocity of pressure differential system which is installed in vestibule of smokeproof stairway in domestic high-rise building becomes back-flow into the vestibule not into the livingroom when the doors open to escape in case of fire by actual measurement. It concerned that fire smoke inflow into the vestibule of smokeproof stairway. so, reflux symptoms were developing the condition does not occur by creating an area of $2m^2$ and a model. if it‘s area is less, airflow in upper area was severely reflux. in the case upward 45 gradient of supply damper’s angle of blade, The results that reflux symptoms include upper door but bottom has some reflux. also vestibule of smokeproof stairway‘s area of $4m^2$ in the living room door in the direction of the flow distributon was normal. if a vestibule of smokeproof stairway is smaller, it designed to be performance-based design should be.

Numerical Study on Air Egress Velocity in Vestibule Pressurization System : Damper Locationfor Uniform Air Egress Velocity in the case of Two Fire Doors (부속실 가압 시스템의 방연풍속에 관한 수치해석적 연구: 2개 출입문이 존재할 경우 균일한 방연풍속을 얻기 위한 댐퍼 위치 선정방법)

  • Seo, Chanwon;Shin, Weon Gyu
    • Fire Science and Engineering
    • /
    • v.28 no.6
    • /
    • pp.1-7
    • /
    • 2014
  • Vestibule pressurization system should produce uniform air egress velocity to prevent the intrusion of smoke into escape route when fire accidents occur inside a building and fire doors are open for evacuation of people. Air supplying units in the vestibule need to be arranged by taking account of the location of doors and the volume of the vestibule. In this study, computational fluid dynamics (CFD) simulations were conducted for the vestibule where two doors are installed varying the location of a damper and louver angle. From simulations, we found that when the damper in the vestibule is located at the center of the wall opposite to two fire doors, the uniform air egress velocity can be obtained.

Comparison of the Performance of a Smoke Control System by Pressurization (가압방식에 따른 전실제연설비의 성능 비교 연구)

  • Kwon, Oh-Hyun;Nam, Jun-Seok;Nam, Sang-Ok;Ryou, Hong-Sun
    • Fire Science and Engineering
    • /
    • v.31 no.2
    • /
    • pp.24-28
    • /
    • 2017
  • This study compared the performance of a smoke control system in the case of a fire with that in the case of non-fire. Single-pressurization in the vestibule, single-pressurization in the stairwell, simultaneous smoke control of the stairwell and vestibule, which was the pressurization of smoke control, were assessed. The result showed that simultaneous smoke control of the stairwell and vestibule can maintain the differential pressure and is least influenced for the evacuation of evacuees. In addition, for the status of smoke control in Korea and the proper pressurization method, these results highlight the necessity of improving the current pressurization method through the survey.

A Study on Horizontal Relationship of Mandibular Teeth in Korean Adults (한국인 하악치아의 수평적인 위치관계에 관한 연구)

  • Choi, Seung-Min;Choi, Dae-Gyun;Choi, Boo-Byung
    • Journal of Dental Rehabilitation and Applied Science
    • /
    • v.19 no.3
    • /
    • pp.153-168
    • /
    • 2003
  • It is very important to arrange the artificial teeth correctly in bucco-lingual (labio- lingual) relation in reconstrcting dentition. Although many anatomic landmarks and techniques have been reported over the years, they are based on westerns. So this study was performd to examine the horizontal relations of mandibular teeth in Korean dentulous adults. 200 volunteers(mean age 22.9) who had natural dentition were selected. The impressions were taken with irreversible hydrocolloid impression material and mandibular study models were fabricated using class I dental stone. Then they were measured with 3-dimensional measuring device specially designed for this study. The results were as follows ; It is better to consider the lingual cusps of the lower posterior teeth as a guide than the linguoaxial surfaces of the lower posterior teeth, arranging the lower posterior teeth buccally to the line which starts from the mesial aspect of the lower canine and continue backward to the lingual aspect of the retromolar pad. It is better to arrange the fossae of the lower posterior teeth buccally to the line which starts from the cusp tip of the lower canine and continue backward to the top of the retromolar pad. The positions of the lower posterior teeth in the denture-bearing area ; considering the fossa as a guide, the 2nd premolar was positioned in center. considering the buccal cusp as a guide, the 1st molar and the 2nd molar were positioned in center. the distance ratio(d/a) was incresed constantly from the lower canine to the 2nd molar d ; the distance between the buccal vestibule(the lowest point) and the buccal cusp tips of the lower posterior teeth. a ; the distance between the buccal vestibule(the lowest point) and the lingual vestibule(the lowest point). The lower canine was positioned lingually($0.11{\pm}0.13$) than the labial vestibule, and the central incisor and the lateral incisor were positioned almost in the imaginary perpendicular plane of the labial vestibule(the lowest point).

Lipoma with Extraoral Swelling in the Labial Vestibule: Report of a Case

  • Cho, Ju-Yeon;Nam, Ki-Young
    • Maxillofacial Plastic and Reconstructive Surgery
    • /
    • v.34 no.4
    • /
    • pp.267-270
    • /
    • 2012
  • Lipoma is the most common benign neoplasm of the body with rare occurrence in the oral cavity. It represents 1~4% of benign neoplasms of the mouth, which affect the buccal mucosa, floor of the mouth, tongue and lips. We report a case of lipoma in the labial vestibule with extraoral swelling, which could easily be misdiagnosed as an odontogenic abscess. Excisional biopsy in this case revealed well-circumscribed masses, surrounded by a thin fibrous capsule and composed of sheets of mature adipocytes, arranged in a "chicken wire" configuration. After a computed tomography scan, excisoinal biopsy was done, and there were no recurrence after 5-month follow-up period.

Effects of Vestibule-Oriented Sensory Integration Treatment on the Nystagmus, Visual Perception and Balancing Ability of Children with Developmental Disability (전정 중심의 감각통합치료가 발달장애아동의 안구진탕, 시지각, 균형능력에 미치는 영향)

  • Kim, Hyun-Ho;HwangBo, Gak;Yoo, Byung-Kook;Kim, Meung-Kwon
    • The Journal of the Korea Contents Association
    • /
    • v.11 no.4
    • /
    • pp.290-302
    • /
    • 2011
  • The purpose of this research was to investigate the effects of vestibule-oriented sensory integration treatment on the nystagmus, visual perception and balancing ability of children with developmental disability. Twenty three children with developmental disability were participated in this experiment. Subjects were received the vestibule-oriented sensory integration treatment based on Ayres' sensory integration theory for 12 weeks. The effects of the treatment were evaluated by Southern California Postrotary Nystagmus Test (SCPNT), Developmental Test of Visual Perception-2 (DTVP-2), Pediatric-Clinical Test of Sensory Integration Balance (P-CTSIB), South California Sensory Integration Test (SCSIT) and the selected item in Bruininks-Oeretsky Test of motor proficiency (BOT). The collected data were analyzed by using Wilcoxon test. The result of this study was as follows that the data of the Nystagmus shown statical significant. The data of the Visual Perception and Balancing ability shown statical significant. The proposed vestibule-oriented sensory integration treatment was effective to improvement of nystagmus, the visual perception and the balancing ability in children with Developmenantal Disability.

Characteristics of Air Egress Velocity in Vestibule Pressurization System Using the Fire Dynamics Simulator (FDS를 이용한 특별피난계단 부속실 제연설비의 방연풍속 기류특성)

  • Ryu, Sung-Ho;Lee, Su-Kyung;Hong, Dae-Hwa;Choi, Keum-Ran
    • Fire Science and Engineering
    • /
    • v.24 no.6
    • /
    • pp.153-159
    • /
    • 2010
  • In this study, we confirmed the fact that air egress velocity of pressure differential system installed at vestibule of smokeproof stairway in domestic high-rise building becomes back-flow to stair-lobby at upper vestibule. Rather it do not back-flow to the livingroom. when fire occur and the door opens to escape from fire zone. so we carry out actual and computational fluid dynamics measurement. In the case upward 45 gradient of supply damper's blade, The simulation results that air flow of upper vestible is steady but back-flow phenomenon occurred at the bottom. However, in the case of $4m^2$, direction of the flow was ideal to living room. If a vestibule’s area is smaller, it must be designed and built according to performance-based design.