• Title/Summary/Keyword: Ventilation simulation

Search Result 383, Processing Time 0.022 seconds

The Effects to Indoor Air Quality as Ventilation System Operation in Apartment House Using CFD Simulation (공동주택에서 환기장치류 가동특성에 따른 실내공기질 변화특성에 관한 연구)

  • Kim, Seok-Keun;Yee, Jurng-Jae
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.19 no.2
    • /
    • pp.142-148
    • /
    • 2007
  • The purpose of this study is to suggest the effective ventilation strategies and control methods that can minimize energy cost maintaining acceptable IAQ level in apartment house. The effects of the air-cleaning and heat-recovery ventilation system on IAQ under various operating conditions are investigated based on the experimental and CFD analyzed results. The results can be summarized as follows. (1) When a ventilator is not operated, the concentration of several pollutants may highly show in the house even though environment-friendly building materials are applied. Therefore, a mechanical ventilation system is required to obtain proper ventilation. (2) The pollutant concentration is noticeably deceased under air-cleaning/ventilation mode of air-clinic system, however, pollutant of kitchen is stagnant, because fresh air is not carried into the kitchen. (3) When air-clinic system is only equipped at master bedroom and living room, the system does not effectively deliver fresh air throughout the whole house, and then high pollutant concentration is obtained in each room. In contrast the average pollutant concentration meets the guideline when air-clinic system is installed at each room. (4) The air-cleaning/ventilation mode significantly affects on room ventilation in comparison with ventilation mode only.

A Numerical Analysis on the Indoor Air Ventilation by Stack Effect and Outdoor Wind in a High-rise Residential Building (초고층 주거건물에서 굴뚝효과와 외풍영향에 인한 실내 환기 기류해석 및 평가에 관한 연구)

  • Kim, Chi-Wan;Lim, Tae-Kun;Ahn, Young-Chull
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.23 no.12
    • /
    • pp.828-835
    • /
    • 2011
  • The purpose of this study is to analyze and evaluate the 3 types of indoor ventilation methods such as natural, mechanical, and hybrid ventilation in high-rise building which is affected by stack effect and outdoor air pressure. For the evaluation of the ventilation capacity, CFD simulation was performed in a typical high-rise residential building. The results of the simulations are as follows: 1) Natural ventilation method is not enough to the regulation. 2) In case of mechanical ventilation, congested area is occurred but meets the regulation. 3) In case of hybrid ventilation with stack effect, all the areas of indoor meet the regulation and congested area is reduced. 4) In case of high-rise building, the differences of ventilation rate among houses in the building are not large because the mechanical ventilation is main factor.

Ventilation System Strategy for a Prospective Korean Radioactive Waste Repository (한국형 방사성 폐기물 처분장을 위한 환기시스뎀 전략)

  • Kim Jin;Kwon Sang-Ki
    • Journal of Nuclear Fuel Cycle and Waste Technology(JNFCWT)
    • /
    • v.3 no.2
    • /
    • pp.135-148
    • /
    • 2005
  • In the stage of conceptual design for the construction and operation of the geologic repository for radioactive wastes, it is important to consider a repository ventilation system which serves the repository working environment, hygiene & safety of the public at large, and will allow safe maintenance like moisture content elimination in repository for the duration of the repositories life, construction/operation/closure, also allowing safe waste transportation and emplacement. This paper describes the possible ventilation system design criteria and requirements for the prospective Korean radioactive waste repositories with emphasis on the underground rock cavity disposal method in the both cases of low & medium-level and high-level wastes. It was found that the most important concept is separate ventilation systems for the construction (development) and waste emplacement (storage) activities. In addition, ventilation network system modeling, natural ventilation, ventilation monitoring systems & real time ventilation simulation, and fire simulation & emergency system in the repository are briefly discussed.

  • PDF

The study of operation mode of ventilation system in the longitudinal ventilation system tunnel (조합환기 방식 터널의 환기기 운전 단계에 관한 연구)

  • Yoo, Ji-Oh;Shin, Hyun-Jun;Lee, Dong-Ho;Lee, Young-hwa
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.4 no.4
    • /
    • pp.343-353
    • /
    • 2002
  • In the past many tunnels have been built to lowest capital investment cost without adequate regard for the cost of operation. But according to increasing the capacity of a ventilation system and to becoming diverse, it is to become more important to come up with the optimal operation stage of ventilation system. In this study, the tunnel ventilation dynamic simulation program had been developed. it is used to calculate the unsteady-state tunnel air velocity and concentration of pollutants according to the assumed average day traffic profile and summarize the energy consumption for the operation of ventilation system. And the operation energy consumption for the electric precipitation system and vertical vent shaft system are evaluated and compared in various operation mode. As the results of this study, the optimal operation stage for these ventilation system are provided.

  • PDF

A Study on simulation analysis of the microbe transport of air-born virus in hospital for microbiological safety (미생물 안전을 위한 병원건물의 환기설계에 따른 공기 감염균 확산에 관한 시뮬레이션 연구)

  • Choi, Sang-Gon
    • Journal of the Korea Safety Management & Science
    • /
    • v.19 no.4
    • /
    • pp.115-123
    • /
    • 2017
  • Recently there is a growing interest in the airborne spread of virus. In particular, there is growing interest in secondary infection through the air in the hospital. The distribution of air-born virus depends on ventilation system installed in a hospital. In this study, simulations were carried out to predict the move of air-born virus by ventilation system at hospital. Simulation results showed that pressure distribution was -372.05Pa ~ -3.45 Pa at 1st floor incase of only used mechanical exhaust at bathroom, shower stall, storage, kitchen etc.. if ventilation switch from used mechanical exhaust to mechanical exhaust & mechanical supply. Simulation results showed that pressure distribution was -336.44Pa at stair hall < -0.2Pa at bathroom < mean 1.19Pa at other room. So simulation results showed that using all of the mechanical supply and mechanical exhaust was more effective then the mechanical exhaust for maintain the pressure distribution in hospital. It was also showed that when using the mechanical supply and mechanical exhaust more effectively prevention of air born virus diffusion.

Investigation of Ventilation Efficiency for the Natural Gas High Pressure Release in an Underground Valve Station (지하 공급관리소내 천연가스 고압분출시 환기효율성 검증)

  • Ha J. M.;Lee J. H.;Sung W. M.
    • Journal of the Korean Institute of Gas
    • /
    • v.6 no.1 s.17
    • /
    • pp.74-80
    • /
    • 2002
  • This study was carried out for the purpose of safety evaluation about the ventilation system (according to the structure of confined room, the position and size of vent window, the amount of blowing air, e.t.c.), which is equipped in one of KOGAS underground valve stations. Particularly, the effect of the fans placed in the upper region was focused in detail. Numerical simulation was conducted in order to predict the features of flow pattern and the diffusion of natural gas concentration. This work examined the ventilation system and resulted in proposing an optimal design of ventilation system.

  • PDF

Analysis of Natural Ventilation Rates of Venlo-type Greenhouse Built on Reclaimed Lands using CFD (전산유체역학을 통한 간척지 내 벤로형 온실의 자연환기량 분석)

  • Lee, Sang-Yeon;Lee, In-Bok;Kwon, Kyeong-Seok;Ha, Tae-Hwan;Yeo, Uk-Hyeon;Park, Se-Jun;Kim, Rack-Woo;Jo, Ye-Seul;Lee, Seung-No
    • Journal of The Korean Society of Agricultural Engineers
    • /
    • v.57 no.6
    • /
    • pp.21-33
    • /
    • 2015
  • Recently, the Korean government announced a new development plan for a large-scale greenhouse complex in reclaimed lands. Wind environments of reclaimed land are entirely different from those of inland. Many standard books for ventilation design didn't include qualitative standard for natural ventilation. In this study, natural ventilation rates were analyzed to suggest standard for ventilation design of venlo type greenhouse built on reclaimed land. CFD (Computational Fluid Dynamics) simulation models were designed according to the number of spans, wind conditions and vent openings. The wind profile at a reclaimed land was designed using ESDU (Engineering Sciences Data Unit) code. Using the designed CFD simulation model, ventilation rates were computed using mass flow rate and tracer gas decay method. Additionally computed natural ventilation rates were evaluated by comparing with ventilation requirements. As a result of this study, ventilation rates were decreased with increasing of the number of spans. Ventilation rates were linearly increased with increasing of wind speed. When the wind speed was $1.0\;m{\cdot}s^{-1}$, only side vent was open and wind direction was $45^{\circ}$, homogeneity of ventilation rate at 0~1 m height is the worst. Finally, chart for computing natural ventilation rate was suggested. The chart was expected to be used for establishing standard of ventilation design.

Hydrodynamic analysis of the surface-piercing propeller in unsteady open water condition using boundary element method

  • Yari, Ehsan;Ghassemi, Hassan
    • International Journal of Naval Architecture and Ocean Engineering
    • /
    • v.8 no.1
    • /
    • pp.22-37
    • /
    • 2016
  • This article investigates numerical modeling of surface piercing propeller (SPP) in unsteady open water condition using boundary element method. The home code based on BEM has been developed for the prediction of propeller performance, unsteady ventilation pattern and cross flow effect on partially submerged propellers. To achieve accurate results and correct behavior extraction of the ventilation zone, finely mesh has generated around the propeller and especially in the situation intersection of propeller with the free surface. Hydrodynamic coefficients and ventilation pattern on key blade of SPP are calculated in the different advance coefficients. The values obtained from this numerical simulation are plotted and the results are compared with experiments data and ventilation observations. The predicted ventilated open water performances of the SPP as well as ventilation pattern are in good agreement with experimental data. Finally, the results of the BEM code/experiment comparisons are discussed.

Simulation and Analysis of Local Ventilation characteristic of Road Tunnel with Ventilation System (환기시스템 적용 도로터널의 국소환기 특성 시뮬레이션 및 해석)

  • 박기림;오명도;이재헌
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.5
    • /
    • pp.321-332
    • /
    • 2001
  • In this study, a design program for ventilation requirements of a longitudinal raod tunnel were developed and investigated. The control volume method was applied to calculate the local air velocity and the local concentration distribution of pollutants, CO, $NO_x$, soot along the tunnel for various tunnel ventilation system. This program was validated by comparing with the practical design data for the road tunnel ventilation system. The calculation results were in good agreement with the practical design data.

  • PDF

Numerical Simulation on the Temperature Distribution by Ventilation Type during Heat of the Power line in Electric Power Tunnel (전력구 터널 내 전력선 발열 시 환기방식에 따른 온도분포에 대한 전산해석)

  • Lee, Ho-Hyung;Lee, Seung-Chul;Kwak, Dong-Kurl;Baek, Doo-San
    • Proceedings of the KIPE Conference
    • /
    • 2014.07a
    • /
    • pp.3-4
    • /
    • 2014
  • Power line in electric power tunnel generate heat around during power transmission. Rising temperature inside the electric power tunnel reduces the transmission efficiency of the power line. In this study, trying to understand the change in temperature in the electric power tunnel by forced ventilation and natural ventilation when the temperature rise of the electric power tunnel. The results show that average temperature in electric power tunnel by natural ventilation, forced ventilation is $56.55^{\circ}C$, $23.25^{\circ}C$. Therefore electric power tunnel during power transmission needs cooling or ventilation system.

  • PDF