• Title/Summary/Keyword: Variable capacity refrigeration

Search Result 49, Processing Time 0.03 seconds

Experimental Study on Heat Transfer Performance of Absorber with Variable Plate Types

  • M.A. Sarker;Moon, C.G.;Lee, H.S.;Kim, E.P.;Yoon, J.I.
    • Proceedings of the Korea Society for Energy Engineering kosee Conference
    • /
    • 2004.05a
    • /
    • pp.201-212
    • /
    • 2004
  • An experimental study of the absorption process of water vapor into a lithium bromide solution was performed. For the purpose of developing high performance absorption chiller/hater utilizing lithium bromide solution as working fluid, it is important to improve the performance of absorber with the larger heat transfer area of the four heat exchangers. The experimental apparatus was composed of a plate type absorber which could increase the heat exchange area per unit volume to investigate more detail characteristics instead of the conventional type, that is, horizontal tube bundle type. The size of plate absorbers were made for 0.4m$\times$0.6m and the design objective of a refrigeration capacity was 1RT. In this experiment, three kinds of plate absorbers namely flat plate, dimple plate and groove plate were used. The obtained results were less than the design objective values, that is, the refrigeration capacity was about 0.3 ~0.4RT and the overall heat transfer coefficient was 500~600 kcal/$m^2$h$^{\circ}C$ at the standard conditions.

  • PDF

An Experimental Investigation on the Variation of Heating Performance Due to the Refrigerant Flow Control in a Variable-Speed Heat Pump (가변속 열펌프의 냉매 유량제어에 의한 난방성능 변화에 관한 실험적 연구)

  • 김봉훈
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.8
    • /
    • pp.746-756
    • /
    • 2001
  • An experimental study was conducted to investigated the effect of refrigerant flow control on the performance of a variable-speed heat pump operating in both cooling and heating mode. For this purpose, cooling and heating capacity, EER and refrigerant mass flow rate corresponding to an electronic valve as well as a capillary tube were measured as functions of compressor speed, length of capillary tube (or valve opening of the electronic valve), refrigerant charge, and outdoor temperature. From the comparison of experimental results, it was found that the performance variation due to the electronic valve opening became significant as the operating conditions(outdoor temperature and compressor speed) deviated from the standard condition at which heating capacity and EER were rated for the indicated capillary tube.

  • PDF

Characteristics of Capacity Control of Variable Speed Water Cooler with the Electronic Expansion Valve Open/Close Degree (전자팽창밸브 개도에 따른 가변속 수냉각기의 용량제어 특성)

  • Beak, Seung-Moon;Moon, Choon-Geun;Kim, Hyun-Woo;Jeong, Seok-Kwon;Yoon, Jung-In
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.34 no.2
    • /
    • pp.282-288
    • /
    • 2010
  • The paper presents the characteristics of capacity control of variable speed water cooler with the electronic expansion valve open/close degree. It is a preliminary study on the optimum control of the water cooler system using a variable speed compressor controlled by inverter. The electronic expansion valve controlled by the variation of compressor speed maintains the constant degree of superheat at the evaporator outlet, which aims to find the degree of superheat obtaining the optimum refrigeration effect. The investigation indicates that there is a point achieving the maximum cooling capacity by the variation of the electronic expansion valve open/close degree with constant compressor speed.

Study on the Cooling Performance of Single and Cascade Refrigeration Systems Using Thermoelectric Modules (열전소자를 이용한 싱글 및 캐스케이드 냉동시스템의 냉각 성능에 관한 연구)

  • Lim, Changhak;Kim, Dongwoo;Kim, Yongchan;Seo, Kookjeong
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.25 no.12
    • /
    • pp.641-646
    • /
    • 2013
  • The purpose of this study is to improve the cooling performance of single and cascade refrigeration systems using thermoelectric modules. The system consists of a heat sink, fan, and thermoelectric module. The operating parameters considered in this study include power distribution between the first- and second-stage thermoelectric modules, air flow, and variable condensing unit. The cooling capacity increased with decreases in the temperature difference between hot and cold surfaces, but decreased with increases in the condensing temperature. The COP decreased with increasing electric power of the thermoelectric module because of the increased Joule heat. The cooling performance improvement using the thermoelectric module is represented by the freezer temperature.

Capacity Modulation of a Multi-Type Heat Pump System Using PID Control (PID 제어를 이용한 멀티형 열펌프의 용량조절)

  • 정대성;김민성;김민수;이원용
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.5
    • /
    • pp.446-475
    • /
    • 2000
  • Performance of a water-to-water multi-type heat pump system using R22 has been experimentally investigated. Total refrigerant flow rate was adjusted with a variable speed compressor and the refrigerant flow rate for two indoor units were controlled by electronic expansion valves. Evaporator outlet pressure of refrigerant and indoor unit outlet temperatures of secondary fluid were selected as controlled variables. Experiments were carried out for both cooling and heating modes using PID control method. Results show that the multi-type heat pump system can be adequately controlled by keeping control gains at certain levels for various operating conditions.

  • PDF

Capacity Modulation of a Multi-Type Heat Pump System using PID Control with Fuzzy Logic (퍼지 로직 적용 PID 제어를 이용한 멀티형 열펌프의 용량조절)

  • 김세영;김민수
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.9
    • /
    • pp.810-817
    • /
    • 2001
  • Performance of a water-to-water multi-type heat pump system using R22 which has tow indoor units has been investigated experimentally. The refrigerant flow rate of each indoor unit was regulated by an electronic expansion valve and the total refrigerant flow rate of the system was controlled by a variable speed compressor. In the system, evaporator outlet pressure of refrigerant and outlet temperatures of secondary fluid from indoor units were selected as control variables. Experiments were executed for both cooling and heating modes using PID control method with fuzzy logic, and results of the test are compared with a classical PID method. In the case of PID control with fuzzy logic, the fuzzy control rules corrects PID parameters each time. Results show that PID control with fuzzy logic has the merits of quick response and reduced overshoot.

  • PDF

Performance of the Flow Distribution and Capacity Modulation of a Multi-Heat Pump System (멀티형 열펌프의 유량분배 및 용량조절 특성)

  • 최종민;김용찬;하진호
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.5
    • /
    • pp.313-320
    • /
    • 2001
  • In the present study, various experiments were performed to investigate capacity modulation and refrigerant flow distribution of a multi-heat pump using a variable speed compressor and electronic expansion valves(EEVs) in the cooling mode. Based on the experimental results, it was possible to understand the interrelation of dual indoor units which provides some difficulties in capacity control of each indoor unit. The characteristics of capacity modulation of two indoor units were measured by controlling two EEVs with a cooling load of each indoor unit.

  • PDF