• Title/Summary/Keyword: Vacuum Interrupter

Search Result 77, Processing Time 0.027 seconds

Analysis of surface flashover along shield gap inner vacuum interrupter (진공 인터럽터 내부 쉴드간 gap에 따른 연면방전 특성파악)

  • Yoon, Jae-Hun;Lee, Seung-Su;Lim, Kee-Jo;Kim, Sung-Tae
    • Proceedings of the KIEE Conference
    • /
    • 2008.10a
    • /
    • pp.103-104
    • /
    • 2008
  • this paper describes the electric field distribution analysis along a shield gap inner vacuum interrupter(VI). The equipotential line and electric field and field vector in a VI are analysed by a finite element method and experiment at shield gap. in result, The equipotential line and electric field distribution was affected to VI shield gap. The reason is as it gets distortion of equipotential line done. finally, this paper recognized whether or not affected, and proposed gap with the most suitable shield length and an external insulation.

  • PDF

Electric field distribution interpretation along a shield form inner vacuum interrupter (진공 인터럽터 내부 Shield형상에 따른 전계분포 해석)

  • Yoon, Jae-Hun;Kim, Beung-Chuel;Lee, Sung-Su;Lim, Kee-Jo;Kang, Seung-Hwa
    • Proceedings of the KIEE Conference
    • /
    • 2008.05a
    • /
    • pp.143-144
    • /
    • 2008
  • this paper describes the electric field distribution interpretation along a shield form inner vacuum interrupter(VI). The equipotential line and electric field in a VI are analysed by a finite element method at various shield form. in result, The electric potentials of end shield form was increased or decreased because it was various the length of shield and between external insulation and source area or fix._end shield. finally shield is how to electric field affect, and advance, and will achieve the optimum design of VI inside shield.

  • PDF

Development of Direct Molding Technology for Embedded VI (Embedded VI 직접성형 기술 개발)

  • Lee, J.G.;Byon, J.M.;Lee, S.G.;Shin, Y.S.;Kim, Y.K.
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2010.06a
    • /
    • pp.126-126
    • /
    • 2010
  • 대표적인 친환경 차단부로 Vacuum Interrupter(VI)를 에폭시 수지로 성형한 Embedded VI 의 적용이 확대되고 있다. 이러한 Embedded VI의 제작에 있어, 기존에는 대부분 VI의 Ceramic 표면과 에폭시 성형층의 계면에 고무재질의 완충층을 적용하는 방식으로 제작되었다. 본 연구에서는 이러한 완충층 형성시 발생되는 문제를 해결하기 위한 방법으로 VI외부에 추가적인 완충층을 형성하지 않고, 에폭시 수지를 성형하는 Direct Molding 방안을 제시하고. VI표면과 에폭시간에 화학적 결합 메커니즘을 도출하여 Direct Molding 을 적용한 Embedded VI의 제작기술을 개발하였다.

  • PDF

Analysis of Arc Behavior as a Function of Twisting Angle Between Contacts in Spiral Type VI by Means of Arc Image, Arc Voltage and FEM (아크이미지, 아크전압과 유한요소해석을 통한 나선형 VI 전극 간의 비틀림 각도에 따른 아크거동분석)

  • Kim, Byoung-Chul;Park, Hong-Tae;Son, Jin-Woo;Lim, Kee-Joe
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.22 no.4
    • /
    • pp.333-341
    • /
    • 2009
  • In this paper arc behavior in spiral type vacuum interrupter(VI) was analyzed by means of arc images, arc voltages and finite element method(FEM). As a result of experiment, the difference of arc voltage was observed under different twisting angles. It was found that the reason of the difference was the difference of arc resistance from simultaneous analysis of arc images and arc voltages. and the difference of arc resistance was explained by Lorentz force calculation with FEM. And the results of calculation were sufficient to explain the experimental results.

Electric field distribution analysis along shield gap inner vacuum interrupter (진공인터럽터 내부 shield gap에 따른 전계분포해석)

  • Yoon, Jae-Hun;Kim, Byung-Chul;Lee, Seung-Su;Lim, Kee-Jo;Kang, Seong-Hwa
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.1368-1369
    • /
    • 2008
  • This paper describes the electric field distribution analysis along a shield form inner vacuum interrupter(VI). The equipotential line and electric field and field vector in a VI are analysed by a finite element method at various shield form. in result, The equipotential line and electric field distribution was affected to VI shield gap. The reason is as it gets distortion of equipotential line done. finally, this paper recognized whether or not affected, and proposed gap with the most suitable shield length and an external insulation.

  • PDF

Analysis of Lorentz force of radial magnetic field type vacuum interrupter using finite element method (유한요소해석을 통한 횡자계 방식의 진공인터럽터 전극의 로렌츠 힘 분석)

  • KIM, Byoung-Chul;YOON, Jae-Hun;HOE, Jun;KANG, Seong-Hwa;LIM, Kee-Joe
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.1197-1198
    • /
    • 2008
  • There have been few papers using finite element method(FEM) to analyze arc driving force for spiral type vacuum interrupter electrode up to date while there have been many papers dealing with AMF type electrode by means of FEM. AMF analysis is very important in AMF type electrode because it has proportional relation with effective area which means the area of magnetic flux density above critical magnetic flux density to diffuse arc. In the same manner, arc driving force is an important factor to drive arc by Lorentz force. In this paper two models were calculated and compared by using commercial FEM software Maxwell 3D.

  • PDF

Evaluation of Breaking Performance of New Contact Material for the Vacuum Interrupter (진공인터럽터용 신규 접점소재에 대한 차단 성능 평가)

  • Cha, Young-Kwang;Lee, Il-Hoi;Ju, Heung-Jin;Shin, Tae-Yong;Park, Kyong-Tae
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.34 no.1
    • /
    • pp.50-55
    • /
    • 2021
  • Copper-chromium alloys have been used as contact materials of vacuum interrupters in circuit breakers, but new materials with highly stable performance are required to break the high voltage and high current barrier due to the recent increase in breaking capacity. In this paper, a new contact material was fabricated from a ternary alloy instead of existing Cu-Cr alloys. Its breaking performance and endurance were verified from a synthetic test and compared with that of various contact materials. The test results verified that the breaking performance of the new contact material was excellent.

Study on Current Conditioning Process for Improving Withstand Voltage Performance of Vacuum Interrupter (진공인터럽터의 내전압 성능 향상을 위한 전류컨디셔닝 기법 연구)

  • Cha, Young-kwang;Lee, IL-Hoi;Jeon, Ki-Beom;Jang, Ji-Hoon;Ju, Heung-Jin
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.35 no.5
    • /
    • pp.480-487
    • /
    • 2022
  • As a process to improve the insulation performance of VIs (Vacuum Interrupters), AC voltage conditioning is generally adopted by many manufacturers. Although the insulation performance is enhanced easily with AC Voltage conditioning, it has limitations when high recovery voltage is required due to high voltage rate or capacitive current switching. In particular, impurities such as oxides segregated on the electrode surface can be removed not by the energy level of the voltage conditioning but by the higher energy level achieved by the current conditioning process In this article, the current conditioning was carried out in various conditions and its validity was examined. The current conditioning was processed by changing the amplitude of applied current, arc time, the number of tests, and frequency. The insulation performance and the status of contact surface were checked as well. We concluded that as the applied charge quantity and the conditioning coverage area increase, the conditioning effect is much higher.

Development of Multi-Sensor Convergence Monitoring and Diagnosis Device based on Edge AI for the Modular Main Circuit Breaker of Korean High-Speed Rolling Stock

  • Byeong Ju, Yun;Jhong Il, Kim;Jae Young, Yoon;Jeong Jin, Kang;You Sik, Hong
    • International Journal of Advanced Culture Technology
    • /
    • v.10 no.4
    • /
    • pp.569-575
    • /
    • 2022
  • This is a research thesis on the development of a monitoring and diagnosis device that prevents the risk of an accident through monitoring and diagnosis of a modular Main Circuit Breaker (MCB) using Vacuum Interrupter (VI) for Korean high-speed rolling stock. In this paper, a comprehensive MCB monitoring and diagnosis was performed by converging vacuum level diagnosis of interrupter, operating coil monitoring of MCB and environmental temperature/humidity monitoring of modular box. In addition, to develop an algorithm that is expected to have a similar data processing before the actual field test of the MCB monitoring and diagnosis device in 2023, the cluster analysis and factor analysis were performed using the WEKA data mining technique on the big data of Korean railroad transformer, which was previously researched by Tae Hee Evolution with KORAIL.

Dynamic Responses Optimization of Vacuum Circuit Breaker Using Taghchi Method (실험 계획법을 이용한 진공 차단기의 동특성 최적화)

  • Jo, Jun Yeon;Ahn, Kil Young;Kim, Sung Tae;Yang, Hong Ik;Kim, Kyu Jung
    • Transactions of the KSME C: Technology and Education
    • /
    • v.3 no.2
    • /
    • pp.141-148
    • /
    • 2015
  • In this study, the VCB(Vacuum Circuit Breaker) has been developed using the Recurdyn that is widely used on multibody dynamics analysis. The VCB consists of three main circuits with the VI(Vacuum Interrupter) and the main frame with the operating mechanism. This analytic model is validated by comparing the simulation results and the experimental results. Generally, in order to reliably cut off the breaking current, the opening speed of the VCB after contact separation has to be a 0.9~1.1m/s. Therefore, the study of the design parameters of the VCB is needed. To improve the opening velocity, Taguchi design method is applied to optimize the design parameters of a VCB with a lot of linkages. In addition, to evaluate the improvement of the operating characteristics, the simulation results are compared with the Recurdyn and experimental results with improved prototype sample.