• Title/Summary/Keyword: VCTFK

Search Result 5, Processing Time 0.024 seconds

A Characteristic of Tracking Progress Happened at the End of the VCTFK (VCTFK 끝단에서 발생되는 트래킹의 진전특성)

  • Jee, Seung-Wook;Kim, Shi-Kuk;Ok, Kyung-Gea;Lee, Chun-Ha;Lee, Kwang-Sik
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.8
    • /
    • pp.78-83
    • /
    • 2010
  • This paper describes the characteristic of tracking progress happened at the end of the polyvinyl chloride insulated cabtyre oval cord(VCTFK) that is widely used for distribution cord. Tracking is occurred owing to the drop of electrolyte at the end of the VCTFK. The tracking progress and its characteristic happened at the end of the VCTFK are as follow; Carbonization and electrical erosion are happened at the end of the VCTFK. Electrical erosion is begun at the insulation layer near conductors. After that, it is also happened at the sheath layer. Accumulation of carbonized insulation and sheath materials at the end of the VCTFK is begun after progress of electrical erosion. When the accumulation is progressed arc discharge is appeared and finally it goes to tracking breakdown.

The Characteristics Analysis of Damaged Pattern by Repeated Stress of VCTFK (VCTFK의 반복피로에 의한 소손 패턴의 특성 해석)

  • Choi Chung-Seog;Shong Kil-Mok;Kim Dong-Woo
    • Journal of the Korean Society of Safety
    • /
    • v.19 no.4 s.68
    • /
    • pp.42-47
    • /
    • 2004
  • In this paper, we analyzed on the characteristics of the stranded wire disconnected by repeated stress. The stranded wires that were used in the experiment are PVC insulated flexible cords(VCTFK: Vinyl Insulated Vinyl Cabtyre Cord Flat-type) of $0.75mm^2,\;1.25mm^2,\;and\;2.0mm^2$. They are used to connect the load in low voltage. The stranded wires disconnected by repeated stress were magnified with optical microscope. Using X-ray, the disconnected wire were photo-graphed. we compared mechanical characteristics of the stranded wire between disconnected tendency and allowable current. On the mechanical strength of vinyl cap tire ellipse type cords under bending stress, VCTFK of $1.25mm^2$ was the strongest of them. When it was bent $826.3\pm7$ times, it appeared the disconnected tendency that element wires of VCTFK of $1.25mm^2$ are more about 1.67 times than element wires of VCTFK of $0.75mm^2$. In mechanical strength, VCTFK of $1.25mm^2$ is higher about 1.7 times than VCTFK of $0.75mm^2$. Therefore, we found out that mechanical strength was higher, when the wire had a lot of element wires. In comparison with bending stress, VCTFK of $1.25mm^2$ is the strongest among samples, and it is the most useful in wires of movable type.

Analysis on the Characteristics of the Stranded Wire Disconnected by Bending Stress (구부림 피로에 의한 연선의 반단선 특성 해석)

  • Shong, Kil-Mok;Choi, Chung-Seog;Kim, Dong-Woo;Kwak, Hee-Ro
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.07a
    • /
    • pp.464-467
    • /
    • 2003
  • In this paper, we analyzed on the characteristics of the stranded wire disconnected by bending stress. The stranded wire that used in the experiment are PVC insulated flexible cords(VCTFK) of $0.75mm^2,\;1.25mm^2,\;and\;2.0mm^2$. They are used to connect the load in low voltage. The stranded wires disconnected by bending stress were magnified with optical microscope. Using X-ray, the disconnected wire were photographed. we compared mechanical characteristics of the stranded wire between disconnected tendency and allowable current. On the mechanical strength of vinyl captyre ellipse type cords under bending stress, $1.25mm^2$ VCTFK was the strongest of them. When it was bended $826.3{\pm}7\;times$, it appeared the disconnected tendency that element wires of $1.25mm^2$ VCTFK are more about 1.67 times than element wires of $0.75mm^2$ VCTFK. In mechanical strength, $1.25mm^2$ VCTFK is higher about 1.7 times than $0.75mm^2$ VCTFK. Therefore, we found out that mechanical strength will be higher, if element wire is a lot. In comparison with bending stress, $1.25mm^2$ VCTFK is the strongest among samples, and then it is the most useful in wires of movable type.

  • PDF

A Study on the Identification of Electrical Eire -Focused on Distance Analysis of Electrical Wires by Overcurrent- (전기화재의 감식에 관한 연구 -과전류 사고시 전선의 이격거리 분석을 통하여-)

  • 이상호;김준식;오홍석
    • Fire Science and Engineering
    • /
    • v.18 no.2
    • /
    • pp.7-11
    • /
    • 2004
  • In this paper, we have simulated the force between the two electrical wires using the finite element method(FEM) according to the value of current and distance when overcurrent flows in the vinyl-insulated vinyl-cabtyre cord(flat-type, 600 V, VCTFK, $2C{\times}1.25mm^2$). And we will present the basic data for the identification of electrical fire by experiment for maximum distance between the two wires according to current and time using large current supply device(Model : EHT_EFAD, Korea) in case of overcurrent.

Analysis of Thermal Characteristic for VCTFK, VFF, HIV and CV Wring by Electric Fan at Livestock Barn (축산용 송풍기 부하에 대한 VCTFK, VFF, HIV 및 CV 전선의 열적특성 분석)

  • Kim, Doo-Hyun;Yoo, Sang-Ok;Kim, Sung-Chul
    • Journal of the Korean Society of Safety
    • /
    • v.29 no.5
    • /
    • pp.35-39
    • /
    • 2014
  • This paper is purposed to analyze the thermal characteristics of wiring according to the number of electric fans in operation for 10 fans over 10 year old and 10 fans less than 1 year old in livestock barn. In order to achieve the goal in the paper, it selected VCTFK, VFF, HIV, and CV wiring that were used most at 64 livestock barns in Cheongwon location through the research on the field investigation. Finally, it also analyzed the dangers by deducing the thermal characteristic data of 4 wiring. In addition, this paper suggested the mode of load current (the most frequently measured load current) of both over 10 years old and less than 1 year old electric fans. The data of this paper could be used for the maintenance and management of wiring and fire investigation of livestock barn as well as for materials of safe designs of wiring of electric fans.