• 제목/요약/키워드: Underground power transmission system

검색결과 114건 처리시간 0.023초

180kV HVDC 해저케이블 기계적/전기적 특성 평가 (Mechanical and Electrical Performance of 180kV HVDC Submarine Cable System)

  • 김남열;이태호;지봉기;이상진;김정년;전승익;윤희석;정수길;강채홍;안용호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.616-618
    • /
    • 2007
  • This paper describes the mechanical and electrical test on HVDC submarine cable, Flexible Repair Joint and termination for 180kV. This HVDC submarine cable was manufactured using LS cable's unique skill and would be applied the HVDC submarine cable system in korea. The performance test consist of mechanical test and electrical test. The tensile bending test and tensile test was done as the mechanical test and Electrical test is DC voltage and Impulse test. The tensile bending test carried out 6 times(double of specified times) for maximum reliability. The DC test voltage is $\pm$400kV/1hr. We estimate the lower limit of DC breakdown voltage is 600kV. The impulse test voltage is $\pm$800kV/10shots. The type of developed cables is the MI type. Its insulation consist of paper tapes impregnated with a high viscosity oil. The development of new HVDC cable is available for HVDC underground or submarine power transmission. The developed HVDC cable, FRJ and termination have passed the mechanical and electrical test successfully and showed excellent performance.

  • PDF

삼상 다중 접지 배전계통에서 활선로 추적 방법 (Live Lines Tracing Method in Power Distribution System with 3-phase-4 wires)

  • 정언붕;변희정;손수국
    • 한국정보통신학회:학술대회논문집
    • /
    • 한국정보통신학회 2017년도 춘계학술대회
    • /
    • pp.559-562
    • /
    • 2017
  • 도심에서 배전선로는 지중과 가공 선로의 구성, 연가, 건물과 나무로 인한 시야 방해로 추적하기가 어렵다. 이러한 3상 4선식 배전계통에서 특정 수용가가 어떤 변압기 또는 어떤 선로로부터 공급되는지를 결정하는 것이 현장의 전기 기술자에게 어려운 문제다. 배전선로 사이의 부하 평형 등을 위해 선로의 정확한 추적기술이 필요하다. 기존의 임펄스 전류를 사선에 주입하는 방식과는 다르게 활선에 고주파 신호를 주입하는 식별 방법을 제안한다. 배전선로에 고주파 전력 신호를 주입하여 분석 한 결과 고주파 신호는 배전선에서 전달 능력에 한계 능력을 갖는다. 보통 배전계통의 전력 변압기는 그러한 고주파 신호의 전달을 차폐하게 된다. 이러한 전송제한 특성을 사용하여 변압기와 배전선로를 식별하는 방법을 제안한다. 측정 배전선로의 양단에서 전기신호에 대한 동일 선로 여부를 판별하는 방식이다. 어려운 점은 원격 두 지점이 동기화되어야 하는데, 동기화 시간을 제공하는 GPS를 사용하지 않고 두 지점에 동기화를 달성한다. 새로운 형태의 선로 및 변압기 식별시스템을 설계 및 구현한다. 시스템은 전력선 통신 모듈을 바탕으로 송수신기로 구성된다. 이론적 개념을 검증하기 위해서 일반 상업용 건물에서 실험이 행하여진다.

  • PDF

초고압 XLPE 케이블 접속함의 부분방전 펄스파형 시뮬레이션 (Pulse Waveform Simulation of Partial Discharges for HV XLPE Cable Joints)

  • 김정태
    • 전기학회논문지
    • /
    • 제67권1호
    • /
    • pp.75-81
    • /
    • 2018
  • In this study, the simulation of partial discharge pulse waveform have been performed for the typical joints such as EBA and PMJ in the HV underground transmission XLPE cable system in order to improve the understanding of partial discharge pulse waveform and the on-site measurement accuracy of partial discharges. FDTD simulation technique was adopted for the simulation and has been shown to be suitable for partial discharge simulation of power cables in terms of pulse propagation characteristics and waveform formation. The simulation results for the EBA showed that the second not-so-large opposite polarity peak appeared after the first negative polarity peak and the measurement sensitivity was the highest near the bottom of the EBA copper box. In the analysis results for PMJ, the magnitude of the second opposite polarity peak was large enough to compare with the first peak, and the measurement sensitivity at the end of the PMJ copper box was the highest. These simulation results show considerable similarity with the on-site measurement, and it would be very useful for the partial discharge measurement of HV XLPE cable systems.

스마트 워터그리드 네트워크의 원격 단말기 보안을 위한 암호화 모듈에 관한 연구 (A Study on Encryption Module for Remote Terminal Security of Smart Water-Grid Network)

  • 박승환;박형모;김창복
    • 한국항행학회논문지
    • /
    • 제17권6호
    • /
    • pp.712-719
    • /
    • 2013
  • 본 논문은 스마트 워터그리드의 원격단말기와 상위 서버단간의 검침 및 제어 데이터의 안정적 전송을 위한 보안모듈에 대해 연구하였다. 제안한 보안모듈은 기존에 보급되어 사용 중인 보안성 없는 원격 단말기에 부착할 수 있도록 구현되었다. 특히, 전기 분야의 스마트그리드와는 달리 스마트 워터그리드는 배터리 전원을 사용하므로 저 전력을 고려하였으며, 지하에 설치되는 계량기 위치에 의한 습하고 열악한 환경이 대단위 네트워크 시스템 구축 시 통신 장애 발생시키는 점을 고려하여 ARIA-GCM-128 대칭키 방식을 채택하였다. 본 논문의 암호화 모듈은 단말기의 검침 데이터와 상위 서버단의 제어 데이터에 대한 보안을 확보하고 임의로 위변조 되는 것을 방지하여 원격검침 시스템에 대한 안정성을 확보할 수 있도록 구현되었다.