• Title/Summary/Keyword: Underground Subway Fire

검색결과 66건 처리시간 0.031초

대심도 지하역사에서의 화재시 연기거동과 피난에 대한 수치해석 연구 (Numerical Study on the Smoke Movement and Evacuation in the Deeply Underground Subway Station Fire)

  • 김홍진;배승용;최영기;홍기배;유홍선
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2011년도 정기총회 및 추계학술대회 논문집
    • /
    • pp.1342-1347
    • /
    • 2011
  • Advantages of the deeply underground subway are underground space efficiency, high speed, decrease of noise and vibration. However, when fire occurs in the deeply underground subway station, large casualties are occurred like Daegu subway station fire due to the increase of evacuation distance. In this study, a numerical analysis was performed by using the fire and evacuation analysis program FDS+EVAC for smoke movement and evacuation in Beotigogae station among the deeply underground subway station. Heat release rate of carriage fire was set 10MW and the fire growth rate was ultrafast. As a result, the smoke move to the exit at 1085 second. The total evacuation time took 956 second.

  • PDF

도심지하공간의 화재안전계획에 관한 연구 (I) (A Study on the fire Safety Plan in downtown underground Space (I))

  • 서동구;황현배;권영진
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2008년도 추계학술논문발표회 논문집
    • /
    • pp.348-355
    • /
    • 2008
  • In Korea, the Seoul subway line 1 was opened in 1974 and the subway service is being operated in Seoul, Pusan, Daegu, Daejeon, and Inchon. The subway station is related to a underground shopping mall that was developed as complex spaces. According to the time of people's stay at the underground space, the necessity about the safety countermeasure of the underground space has been enlarged. Therefore the result of this study is t propose guidelines for improving the evacuation safety performance in underground subway stations.

  • PDF

지하역사에서의 화재연기거동 실험 (Experiments of Smoke Behavior in an Underground Subway Station)

  • 김동현;장용준;박원희
    • 한국철도학회논문집
    • /
    • 제10권1호
    • /
    • pp.67-73
    • /
    • 2007
  • Experiments were carried out to investigate smoke movement in platform of a subway station which currently is in service in Pusan, the second largest city in Korea. The recently constructed underground station of the "bank type" (two platforms on both sides of track) which is the popular layout of platforms in Korea, is chosen in Pusan. The smoke generator and heater are used for simulating the smoke movement at the fire break in the platform located in the 2nd basement of the station. Video recordings were used to monitor smoke lowering. In this study, the movements of smoke in the underground station are investigated under various smoke-control operating modes. Three tests wire conducted according to its operating mode of the ventilation systems in the platform: no operation of any ventilation systems, smoke extraction mode in occurrence of fire (presently running mode) and full capacity of smoke extraction where all vents are activated in the platform. The results can be used for comparing with the numerical prediction results of fire subway stations.

대심도 지하역사에서 화원 위치에 따른 연기거동 특징 연구 (THE STUDY ON THE CHARACTERISTICS OF FIRE DRIVEN SMOKE-FLOW FOR DIFFERENT FIRE-LOCATION IN DEEPLY UNDERGROUND SUBWAY STATION)

  • 김학범;장용준;이창현;정우성
    • 한국전산유체공학회:학술대회논문집
    • /
    • 한국전산유체공학회 2009년 춘계학술대회논문집
    • /
    • pp.202-207
    • /
    • 2009
  • 본 연구에서는 대심도 지하역사에서 화원 위치에 따른 연기거동의 특징을 분석하였다. 전산수치해석에 FDS code가 사용되었다. 화재에 의한 유체거동을 모사하기 위하여 난류모델은 LES를 사용하였으며, 빠른 계산을 수행하기 위하여 병렬수치해석기법을 사용하였다. 본 연구를 통하여 대심도 역사에서 화재시 피난을 저해하는 화원의 위치에 대하여 검토하였다.

  • PDF

지하철 터널내의 객차 화재발생시 환기실 위치변화에 따른 화재특성의 수치적 연구 (Numerical Predictions of Fire Characteristics of Passenger Train Fire in an Underground Subway Tunnel, Depending on Change of Location of Ventilation Facility)

  • 손봉세;장희철
    • 한국화재소방학회논문지
    • /
    • 제22권5호
    • /
    • pp.1-8
    • /
    • 2008
  • 본 연구의 목적은 지하철 터널에서 화재가 발생한 경우 역사와 환기실의 위치에 따른 화재특성을 수치적으로 분석하는데 있다. 이를 위해 피난거리, 피난시간 및 최악조건 화재가 발생한 2가지 시나리오를 선정하고, 환기실 위치 변경에 따른 시간별 화재상황에 대한 터널내의 시류 및 열환경을 분석하였다. 화재해석을 위해 FLUENT v.6.3.26을 이용하였으며, 난류모델은 표준 k-${\varepsilon}$ 모델을 사용하였다. 경우에 따른 터널 내 일산화탄소의 농도 분포, 온도분포 및 속도분포의 결과를 분석하였고 본 연구의 결과는 지하철 역사 및 터널 설계시 최적의 방재 및 환기시스템을 구축하는데 기여할 것으로 생각된다.

대심도 역사의 화재강도에 따른 연기확산 영향 분석 (ANALYSIS OF SMOKE SPREAD EFFECT DUE TO THE FIRE STRENGTH IN UNDERGROUND SUBWAY-STATION)

  • 장용준;구인혁;김학범;김진호
    • 한국전산유체공학회:학술대회논문집
    • /
    • 한국전산유체공학회 2011년 춘계학술대회논문집
    • /
    • pp.373-378
    • /
    • 2011
  • As the number of deeply-underground subway station(DUSS) increases, the safety measures for DUSS have been requested. In this research, Shingumho station (The line # 5, Depth: 46m) has been selected as case-study for the analysis of smoke-spread speed with the different fire strength. Field test data measured for actual fan in DUSS was applied as a condition of a simulation. The whole station was covered in this analysis and total of 4 million grids were generated for this simulation. The fire driven flow was analyzed case by case to compare the smoke-spread effect according to the fire strength. in order to enhance the efficiency of calculation, parallel processing by MPI was employed and large eddy simulation method in FDS code was adopted.

  • PDF

대심도 지하역사에서의 화재시 플랫폼 스크린 도어에 의한 열, 연기 거동 영향 분석 (The Analysis of the effects of the platform screen door on the fire driven flow in The Deeply Underground Subway Station)

  • 장용준;김학범;이창현;정우성
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2008년도 추계학술대회B
    • /
    • pp.1984-1989
    • /
    • 2008
  • In this study, fire simulations were performed to analyze the characteristics of the fire driven flow and the effects of the platform screen door on the smoke flow in the station, when the fire occurred in the center of the platform. Soongsil Univ. station (line number 7, 47m in depth underground) was chosen which was the one of the deepest underground subway stations in the Seoul metro, SMRT. The parallel computational method was employed to compute the heat and mass transfer eqn's with 6 CPUs of the linux clustering machine. The fire driven flow was simulated with using FDS code in which LES method was applied. The Heat release rate was 10MW and The Ultrafast model was applied for the growing model of the fire source. The 10,000,000 structured grids were used.

  • PDF

지하철 터널 내 운행 중 객차에서 화재발생시 제연풍량에 따른 열 및 연기 확산 예측 연구 (Numerical Prediction of the Heat and Smoke Propagations for a Passenger Train Fire in an Underground Subway Tunnel for Different Extraction Flowrate)

  • 장희철;윤경범;박리진;김태국;박원희;김동현
    • 한국방재학회:학술대회논문집
    • /
    • 한국방재학회 2007년도 정기총회 및 학술발표대회
    • /
    • pp.250-253
    • /
    • 2007
  • The purpose of this research is focussed on the numerical predictions of the heat and smoke propagations for a passenger train fire in an underground subway tunnel for different air supply and extraction flowrates. The analysis is performed for one of the stations on subway line #5 in Seoul under the emergency operation mode for different air supply and extraction flowrates. Five different the air supply and extraction flowrates are considered for the numerical analyses. The numerical results show that the air supply and extraction flowrates affect the smoke control performance significantly by improving the smoke removal performance for the balanced control of air supply and smoke extraction and for the unbalanced control with lager smoke extraction than air supply.

  • PDF

지하철터널 환기변환모드에 따른 안전성 평가에 관한 연구 (A study on safety evaluation by changing smoke ventilation mode in subway tunnels)

  • 이동호
    • 한국터널지하공간학회 논문집
    • /
    • 제5권4호
    • /
    • pp.389-400
    • /
    • 2003
  • 본 연구는 지하철방재대책의 일환으로 터널구간에 설치된 환기기의 제연절환 운전모드 및 승강장 선로부 환기장치를 포함한 6종류의 제연운전모드를 대상으로 승강장에 정차된 열차화재 시나리오에 따라 3차원 실시간 화재 시뮬레이션을 수행하여 제연방식별 열 및 연기전파특성을 규명함으로서, 승강장에서 열차 화재 발생시, 승객이 안전하게 최적 대피가 가능한 환기기의 제연절환 조합운전의 도출을 목표로 한다.

  • PDF

대심도 지하역사에서의 화재현상 연구 (The Study on Fire Phenomena in The Deeply Underground Subway Station)

  • 장용준;김학범;이창현;정우성
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2008년도 춘계학술대회 논문집
    • /
    • pp.1773-1780
    • /
    • 2008
  • 대심도 역사에서의 화재 발생시 승객의 주 대피이동로인 계단이 매우 길기 때문에 피난의 어려움이 예상된다. 이에 본 연구에서는 서울 지하철 호선별 대심도 역사 중에서 하나인 숭실대역(7호선, 47m)을 선정하여, 화재시뮬레이션을 수행하였고, 이를 통하여 열기류 및 연기의 거동을 분석하였고, 적절한 피난대책을 고찰하였다. 최근에 지하역사에서의 화재유동 시뮬레이션이 몇 몇 기관에서 수행되고 있으나, 지하의 전역사에서 화재 유동 해석은 드물게 수행되어 왔다. 특히 지하 40m가 넘는 대심도 역사에서의 유동해석은 일반 PC로는 불가능하기 때문에 이에 대한 연구가 전무하였으나, 본 연구에서는 리눅스 클러스터(Linux cluster) 장비를 이용한 병렬처리기법을 적용하여 대심도 역사에서의 화재해석을 수행하였다. 화재유동해석은 화재전용 FDS code를 이용하였으며, 난류모델은 LES 기법을 적용하였다. 화원의 규모는 10MW이고, 성장모델은 Ultrafast model를 적용하였다. 적정한 격자크기는 화원의 특성직경을 통하여 산출하였다. 본 연구에 사용된 총 격자규모는 약 10,000,000개이다. 이는 일반 PC에서는 다루기가 불가능한 격자수이므로, 병렬처리기법을 적용하여 6 cpu 리눅스 클러스터 장비로 수치해석을 수행하였다.

  • PDF