• Title/Summary/Keyword: Unbalanced impedance

검색결과 45건 처리시간 0.027초

부하 변동에 의한 전압불평형율의 특성 해석 (Analysis on the Characteristics of Voltage Unbalance Factor by Load Variations)

  • 김종겸;박영진;이은웅
    • 전기학회논문지P
    • /
    • 제54권1호
    • /
    • pp.47-53
    • /
    • 2005
  • Most of the loads in industrial power distribution systems are balanced and connected to three power systems. However, in the user power distribution systems, most of the loads are single & three phase and unbalanced, generating voltage unbalance. Voltage unbalance factor is mainly affected by load system rather than stable power system. Unbalanced voltage will draw a highly unbalanced current. As a result, the three-phase currents may differ considerably, thus resulting in an increased temperature rise in the machine. This paper presents a scheme on the characteristics of voltage and current unbalance factor under the load variation at the three phase 4-wire system. Load unbalance factor is measured by the power quality measurement apparatus and compared by the current unbalance factor. Two methods are indicated similar results. The voltage unbalance factor of the three-phase 4-wire system is approved by the field measurement. Each phase has an impedance each other by the unbalanced operation pattern and give rise to voltage unbalance.

New Techniques for Impedance Characteristics Measurement of Islanded Microgrid based on Stability Analysis

  • Hou, Lixiang;Zhuo, Fang;Shi, Hongtao
    • Journal of Power Electronics
    • /
    • 제16권3호
    • /
    • pp.1163-1175
    • /
    • 2016
  • In recent years, microgrids have been the focus of considerable attention in distributed energy distribution. Microgrids contain a large number of power electronic devices that can potentially cause negative impedance instability. Harmonic impedance is an important tool to analyze stability and power quality of microgrids. Harmonic impedance can also be used in harmonic source localization. Precise measurement of microgrid impedance and analysis of system stability with impedances are essential to increase stability. In this study, we introduce a new square wave current injection method for impedance measurement and stability analysis. First, three stability criteria based on impedance parameters are presented. Then, we present a new impedance measurement method for microgrids based on square wave current injection. By injecting an unbalanced line-to-line current between two lines of the AC system, the method determines all impedance information in the traditional synchronous reference frame d-q model. Finally, the microgrid impedances of each part and the overall microgrid are calculated to verify the measurement results. In the experiments, a simulation model of a three-phase AC microgrid is developed using PSCAD, and the AC system harmonic impedance measuring device is developed.

3상 계통 연계형 인버터의 역상분 전류 주입을 이용한 계통 등가 임피던스 추정 기법 (Equivalent Grid Impedance Estimation Method Using Negative Sequence Current Injection in Three-Phase Grid-connected Inverter)

  • 박찬솔;송승호;임지훈
    • 전력전자학회논문지
    • /
    • 제20권6호
    • /
    • pp.526-533
    • /
    • 2015
  • A new algorithm is proposed for the estimation of equivalent grid impedance at the point of common coupling of a grid-tie inverter output. The estimated impedance parameter can be used for the improvement of the performance and the stability of the distributed generation system. The estimation error is inevitable in the conventional estimation method because of the axis rotation due to PLL. In the conventional estimation error, the d-q voltage and current are used for the calculation of the impedance with active and reactive current injections. Conversely, in the proposed algorithm, the negative sequence current is injected, and then the negative sequence voltage is measured for the impedance estimation. As the positive and negative sequence current controller is independent and the PLL is based on the positive sequence component only, the estimation of the equivalent impedance can be achieved with high accuracy. Simulation and experimental results are compared to validate the proposed algorithm.

출력전력 백-오프 구간을 확장시킨 고출력 고효율 불균형 도허티 전력증폭기 (High Power and High Efficiency Unbalanced Doherty Amplifier used to Extend the Output Power Back-off)

  • 장동희;김지연;김종헌
    • 한국ITS학회 논문지
    • /
    • 제10권5호
    • /
    • pp.99-104
    • /
    • 2011
  • 본 논문에서 출력 전력 백-오프 구간을 확장하기 위한 고출력 고효율 불균형 도허티 전력 증폭기를 제안하였다. 제안된 불균형 전력증폭기는 기존의 대칭형 도허티 전력증폭기처럼 주 증폭기와 보조 증폭기에 같은 트랜지스터를 사용하는 구조이며 주 증폭기의 출력에 연결되어 있는 ${\lambda}/4$ 변환기의 임피던스를 변형하여서 구간을 확장할 수 있다. 제안된 불균형 도허티 전력증폭기는 기존의 백-오프 출력 구간을 확장하기 위한 비대칭 도허티 전력증폭기와 비교해서 구조가 더 간단함에도 불구하고 유사한 효율과 선형성 특성을 갖는다. 제안된 증폭기의 성능을 증명하기 위해서 CDMA2000 1FA 신호를 입력으로 사용하여 46 W 도허티 전력증폭기를 설계 및 제작하였다. 제작된 불균형 도허티 전력증폭기에서 35 %의 효율과 885 kHz 오프셋 주파수에서 ACPR -34 dBc 그리고 1.98 MHz 오프셋 주파수에서 ACPR -35.6 dBc를 얻었다.

일정전류 비평행교류브릿지에 의한 전도도측정과 황의 정량 (An Unbalanced A.C. Bridge with High Voltage Source for the Conductometric Determination of Sulfur in Iron Ores)

  • 채명준;최규원
    • 대한화학회지
    • /
    • 제14권4호
    • /
    • pp.327-332
    • /
    • 1970
  • A simple and convenient device for deflection-type direct reading the variations in electrolytic conductance is described and applied to the analysis of sulfur by combustion-$H_2O_2$ oxidation method. The apparatus consisted of a high resistance-ratio bridge in which the other adjacent arms are the differential cells. By adopting unusually high a-c voltage source for the bridge excitation, the a-c method for unbalanced bridge is established, decreased sensitivity owing to reduced bridge factor, 0.01, is overcome and also the absolute sensitivity and linearity are greatly improved. Over 50% variations in impedance of the balanced cell, within 1% deviation from the linearity can be attained with a volt (rms)order of output which was detected directly with VTVM without further amplification. Analysis of the bridge shows that these useful features are natural result of the constant current character of the high source impedance generator and the performance of the device agreed with the theoretical predictions. A standard procedure for the rapid analysis of sulfur using the bridge is also given, the analytical accuracy was approximately 1%. A determination takes not more than 5 minutes.

  • PDF

Yg-Yg 3상 내철형 변압기의 영상분 임피던스 분석 (Zero Sequence Impedance of Yg-Yg Three Phase Core Type Transformer)

  • 조현식;조성우;신창훈;차한주
    • 전기학회논문지
    • /
    • 제65권6호
    • /
    • pp.940-945
    • /
    • 2016
  • In this paper, zero sequence equivalent circuit of Yg-Yg three phase core-type transformer is analyzed. Many problems by iron core structure of the three phase transformer due to asymmetric three phase lines, which includes line disconnection, ground fault, COS OFF, and unbalanced load are reported in the distribution system. To verify a feasibility of zero sequence impedance of Yg-Yg type three phase transformer, fault current generation in the three phase core and shell-type Yg-Yg transformer is compared by PSCAD/EMTDC when single line ground fault is occurred. As a result, shell-type transformer does not affect the flow of fault current, but core-type transformer generate an adverse effect by the zero sequence impedance. The adverse effect is explained by the zero sequence equivalent circuit of core-type transformer and Yg-Yg type three phase core-type transformer supplies a zero sequence fault current to the distribution system.

불평형 요소 변화에 따른 지중 송전선로의 시스순환전류 분석 (Analysis of Sheath Circulating Current in Underground Transmission Power Cables according to Unbalanced Factor)

  • 최수현;김규호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2015년도 제46회 하계학술대회
    • /
    • pp.294-295
    • /
    • 2015
  • Many unbalanced factors of underground transmission power cable, such as burying types and the length difference of the cable between each minor section, etc will cause the impedance unbalance and excessive circulating current between cables. So this paper presents the analysis of sheath circulating current in accordance with the distance between the center conductors and phase arrangement. ground resistance value changes on 154kV transmission system. Based on these simulation results, this paper will contribute to the reduction method of sheath circulation current.

  • PDF

정지형 UPS의 병렬운전 제어 (The Parallel Operation Control of Static UPSs)

  • 민병권;원충윤
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제48권7호
    • /
    • pp.363-368
    • /
    • 1999
  • The parallel operation system of multiple uninterruptible power supplies(UPSs) is used to increase power capacity of the system or to secure higher reliability at critical loads. In the parallel operation of the two UPSs, the load-sharing control to maintain the current balance between them is a key technique. Because a UPS has low output impedance and quick response characteristics, in case of an unbalanced load inverter output current changes very rapidly and thereby can instantaneously reach an overload condition. In this study, high precise load-sharing controller is proposed and implemented for the parallel operation system of two UPSs with low impedance characteristics and this controller controls the frequency and the voltage to minimize the active power component and the reactive power component which are gotten from the current difference between two UPSs. And then a good performance of the proposed method is verified by experiments in the parallel operation system with two 40KVA UPSs.

  • PDF

Multi-frequency 자극 방식을 이용한 생체 전기 임피던스 측정 시스템 설계 및 경혈의 전기적 특이성에 대한 고찰 (Development of Multi-Frequency Impedance Measurement System for Acupuncture Points and Preliminary Report of Measurement Results)

  • 김수병;이나라;이승욱;최준영;이용흠
    • Korean Journal of Acupuncture
    • /
    • 제29권1호
    • /
    • pp.71-81
    • /
    • 2012
  • Objectives : The purpose of this paper was to suggest new diagnostic method that was to supersede the estimation of electrical properties at acupoints. Thus, we developed the multi- frequencies bioelectrical impedance measurement system so as to analyze the state of bio-ions in body fluid as body compositions, not skin impedance at acupoint. Methods : At low frequency, the current does not penetrate the cell membrane and at high frequency, the current passes through both intracellular and extracellular fluid because of the decreas of cell membrane impedance. To confirm the reflection of composition in extracellular fluid or intracellular fluid of segment such as acupoint, the system was developed to detect the acupoint potential between adjacent two points in the area of LU3, LU4 and LU9 using 5,50 and 200KHz. Results : The detected acupoint potential has been decreased according to elevation of frequency. As a result of correlation of left/right identical acupoint, we observed a high correlation of three types of acupoint potential at multi-frequencies. Moreover, we observed the low correlation at 5KHz, and that was a significant factor to be considered as unbalanced relationship of identical acupoints. Conclusions : On the basis of meridian theoretical point of view, we may infer the acupoint's physiological composition using the multi-frequencies bioelectrical impedance measurement system.

배전선로 고장에 의한 Voltage Sag의 특성 해석 (Characteristic Analysis of Voltage Sags Due to Faulted Distribution Lines)

  • 김성덕
    • 조명전기설비학회논문지
    • /
    • 제16권1호
    • /
    • pp.76-84
    • /
    • 2002
  • 송전선과 배전선의 고장에 의한 voltage sag는 산업 수용가와 전력회사에 당면한 가장 중요한 전력품질(power quality) 문제들 중 하나가 되었다. voltage sag는 일반적으로 진폭과 지속시간 특성으로 기술되지만 voltage sag 현상을 규명하여 그 대책을 찾는데는 위상변위 특성을 반드시 고려해야 한다. 이 논문에서는 3상지락, 단선지락, 및 선간단락 사고가 발생하였을 경우에, 고장임피던스의 변화에 의한 voltage sag를 symmetrical components 해석을 이용하여 특성해석을 하였다. 이 때, voltage sag와 이들이 진폭과 위상에 미치는 효과를 고찰하였다. 3상지락과 같은 평형 고장은 모든 상에서 전압과 전류가 동일한 값으로 변화되고 또한 영상성분들은 영이 되었다. 그렇지만, 단선지락과 선간단락 고장과 같은 불평형 고장으로 인한 voltage sag는 진폭과 위상이 각 상마다 다르게 변화되었다. 해석결과를 확인하기 위하여 전력회로 모델들을 토대로 시뮬레이션을 수행하고 그 결과들도 검토되었다.