• Title/Summary/Keyword: Ultra Violet Germicidal Irradiation, UVGI

Search Result 4, Processing Time 0.02 seconds

A study on the disinfection performance of indoor microorganism using energy consumption analysis for indoor bio-safety (건물 재실자의 미생물 안전을 위한 면역건물 기술의 에너지 사용 연구)

  • Choi, Sang-Gon
    • Journal of the Korea Safety Management & Science
    • /
    • v.11 no.4
    • /
    • pp.111-118
    • /
    • 2009
  • In this study the real situation of apartment house in seoul is reproduced with multi-zone modeling program CONTAM2.4. This model include disinfection system which is consist of dilution, filtration, UVGI(ultra violet germicidal irradiation). It's energy consumption was also analyzed through the linked model of CONTAM and TRNSYS according to the combination of components. The comparison of total energy consumption through energy analysis revealed that adjusting the air change rate of the UVGI air sterilizer to maintain the same indoor microbe removal capability was more advantageous in terms of energy consumption.

The study on the multizone modeling for preventing transmission of air borne contagion (실내 미생물오염 전파방지를 위한 멀티죤 모델링에 관한 연구)

  • Choi, Sang-Gon;Lee, Hyun-Woo;Hong, Jin-Kwan
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.429-435
    • /
    • 2006
  • In this study multi-zone modeling program CONTAM 2.4 which is developed by NIST is used for modeling the air disinfection system which is consist of dilution, filtration, ultra violet germicidal irradiation (UVGI) for removing the indoor microorganism such as bacteria and fungus. Developed models those protect occupants against indoor microorganism generated in our daily life are enable to use for immune building simulation tool. Also, results indicate that those models are enable to compute the real situation that is almost impossible of carrying out experiment and identify the disinfection rate with highly reliance. Results also suggest that engineers will use these models as a design tool for the immune building system.

  • PDF

An Experimental Study on the Air Sterilization Performance of A Reflective Electro Magnetic Energy System (Reflective Electro Magnetic Energy(REME)를 이용한 공기살균시스템의 성능평가에 관한 실험적 연구)

  • Hong, Jin Kwan;Lim, Ga Yeon
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.28 no.12
    • /
    • pp.509-514
    • /
    • 2016
  • From the point of view to prevent airborne infection-related diseases such as H1N1, SARS, and MERS, an actual application of air cleaning and purification systems including technologies like UVGI has become increasingly important. Recently, an air purification system using REME (Reflective Electro Magnetic Energy) developed in the U.S. is applied for indoor air purification and sterilization technology to counteract the outbreak of new airborne infections. In this study, an air sterilization performance experiment using REME was carried out. The results verified that air sterilization performance in the case of installing a REME system in a medical center was 31%, namely the number of floating bacteria decreased by 31% after only a five-day operation. In addition, the number of culture collections in the REME operating air conditioning systems using nonpathogenic Geobacillus stearothemophilus as a biological indicator decreased maximally to 67%. A field application of REME technology will be useful to prevent airborne infection-related diseases, especially in response to public health crises due to the advent of emerging diseases.

A Study on the Multizone Modeling for Preventing Transmission of Air Borne Contagion (실내 미생물오염 전파방지를 위한 멀티존 모델링에 관한 연구)

  • Choi, Sang-Gon;Lee, Hyun-Woo;Hong, Jin-Kwan
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.11
    • /
    • pp.933-940
    • /
    • 2006
  • In this study multi-zone modeling program CONTAM 2.4 developed by NIST is used for estimating the air disinfection rate of the interior of a room which is set up the indoor air disinfection system with filter and ultra violet germicidal irradiation (UVGI). Developed models those enable to predict the transmission of air home contagion such as bacteria and fungus generated in our daily life are useful model for designning air cleaning & ventilation system of building. Also, results indicate that these models are enable to compute the real situation that is almost impossible of carrying out experiment in an actual condition due to biohazard problems and suggest that engineers will use these models as a design tool for the future immune building system.