• Title/Summary/Keyword: UV/IR detector

Search Result 16, Processing Time 0.025 seconds

The Development of UV-IR Combination Flame Detector (UV-IR 복합형 화재감지장치 개발)

  • 이복영;권오승;정창기;박상태
    • Journal of the Korean Society of Safety
    • /
    • v.16 no.1
    • /
    • pp.1-8
    • /
    • 2001
  • All objects emit thermal radiation and this radiation is the basis of the techniques used to detect flames. The usual phenomena occurring in the initial stage of the fire are generally invisible products of a combustion and visible smoke. Liquid or gaseous materials do not undergo a smoldering stage so that fires develop very rapidly. Also, the heat generated by the initial flames is usually not sufficient to activate a heat detector. In this case the most effective criterion for automatic fire detection is the flame. According to the fire regulation of korea, the compulsory standard provided that a flame detector shall be installed in a place that the attachment height of detector is higher than 20 m, chemical plants, hangar, refinery, etc.. The results of the research and development are discriminated between a flame and other radiant emitters, developed a UV detector tube contains an inert gas which absorbs UV radiation, developed PZT pyroelectric element is based on the use of photovoltanic cell, developed IR band-pass filter that only allow a 4.3 $\mu\textrm{m}$ radiation wavelength to reach the sensors and developed UV-IR combination flame detector combined into a single detection device.

  • PDF

UV/IR flame detector using Microprocessor (마이크로프로세서를 사용한 UV/IR 불곶 감지기)

  • 박성진;임병현;임종연;김명원;윤길호
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.07a
    • /
    • pp.215-218
    • /
    • 2001
  • A flame detector responds either to radiant energy visible to the human eye or outside the range of human vision. Such a detector is sensitive to glowing embers, coals, or flames which radiate energy of sufficient intensity and spectral quality to actuate the alarm. An infra-red detectors can respond to the total IR component of the flame alone or in combination with flame flicker in the frequency range of 5 to 30 Hz. A major problem in the use of infrared detectors receiving total IR radiation is the possible interference of solar radiation in the infrared region. When detectors are located in places shielded from the sun, such as vaults. filtering or shielding the unit from the sun's rays is unnecessary. In this study, we proposed method for redue a false alarm with using filtering & sensor technology for distinguish of causes of raise a false alarm and pure flame.

  • PDF

화염감지기에 대한 고찰

  • Lee, Bok-Yeong
    • Fire Protection Technology
    • /
    • s.13
    • /
    • pp.18-26
    • /
    • 1992
  • This report is explained about operating principles, characteristices of flame detectors. Flame detector is designed to detect the UV (Ultraviolet) and IR (Infrared) rediation produced by flaming involving carbonaceous materials.

  • PDF

Analyses of Additives Applied in a Polycarbonate (폴리카보네이트에 사용된 첨가제의 분석)

  • Kim, Seog-Jun
    • Analytical Science and Technology
    • /
    • v.13 no.3
    • /
    • pp.282-290
    • /
    • 2000
  • In this study, polymer additives were extracted and separated by Soxhlet extraction method and the dissolution-precipitation method from a polycarbonate (optical grade) which completely absorbed UV light below 390 nm. Analytical techniques such as UV-Vis spectroscopy, FT-IR, and HPLC were applied to analyze additives in polycarbonate. Separated materials from the polycarbonate may be a complex mixture containing additives such as UV stabilizer, antioxidants (primary and secondary), monomers, and oligomers. Several compounds such as bisphenol A, Irganox 1010, and Cyasorb UV-5411 were identified by chromatograms and UV spectra obtained from RP HPLC analysis using Bondapak $C_{18}$ column, methanol mobile phase, and a photodiode array (PDA) detector. Also, the content of UV-5411 in the polycarbonate was about 0.12 wt% by a quantitative analysis through UV spectroscopy.

  • PDF

Introduction of Ultraviolet/Infrared Flame Detector and Method for False Detection Prevention (자외선/적외선 불꽃감지기 소개 및 오동작 방지를 위한 연구)

  • Lim, Byung-Hyun;Ko, Nak-Yong;Hwang, Jong-Sun;Kim, Yeong-Min;Kim, Jong-Man
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.05b
    • /
    • pp.8-11
    • /
    • 2003
  • We propose that when combustible burn with contain carbon, introduce fire detector with sensor of private-use detectable light energy as infrared and ultraviolet in energy of electromagnetic-wave type radiate from flame, method for correct discrimination to resemble fire produce false alarm of detector such as sun light, hot object radiation, are welding. This research using infrared sensor is pyroelectric infrared sensor based black body radiation theory. Ultraviolet sensor is uv Tron using gas multiplication effect to current discharge and photoelectric effect of metal. To have high sensibility and to gain proper output voltage, it has high responsive performance. This research introduced UV/IR compound type flame detector and proposed method of false alarm reduced to resemble fire. The result propres the prevention and extinction of fire technique degree, certificated operation of detector.

  • PDF

Application of UV-Vis Spectroscopic Analysis for Transformer Insulating Paper Degradation (UV-Vis 분광분석에 의한 전기변압기 내 절연지 열화도 측정)

  • Kong, Hosung;Han, Hung-Gu
    • Tribology and Lubricants
    • /
    • v.35 no.3
    • /
    • pp.151-157
    • /
    • 2019
  • Insulated oil degradation produces charged by-products, such as acids and hydro-peroxides, which tend to reduce the insulating properties of the oil. In this study, UV-vis spectroscopy measurement technology is developed and experimentally compared with other measurement methods, such as the titration method and IR spectroscopy, to validate its ability to monitor the degradation of electrical insulating paper. The degradation characteristics of the insulating paper are appropriately represented through various types of measurement methods, such as the Tan (delta) method, $CO_2$ gas production measurement, the titration method, and IR spectroscopy. The results are demonstrated to be well comparable to a change in the fluorescence emission ratio (FER), which is defined as the shift in fluorescence intensity in the measured wavelength range, and also to the chromatic ratio, which is defined as a color shift to longer wavelength ranges. The results also show that, by using UV-vis spectroscopy, it is possible to detect the degradation of the insulating paper. This study suggests that UV-vis spectroscopy can be applied as an alternative to high-performance liquid chromatography, which is the internationally recognized measurement technology for cellulose paper degradation. The FER detector is also verified to be useful as an effective condition-monitoring device for power transformers.

A Study on the protection of false alarm in the UV/IR flame detector (불꽃 감지기에서 오동작 방지에 관한 연구)

  • Lim, Byung-Hyun;Park, Sung-Jin;Lim, Jong-Yeon;Hwang, Jong-Sun;Kim, Young-Min
    • Proceedings of the KIEE Conference
    • /
    • 2001.04a
    • /
    • pp.209-212
    • /
    • 2001
  • A flame detector responds either to radiant energy visible to the human eye or outside the range of human vision. Such a detector is sensitive to glowing embers, coals, or flames which radiate energy of sufficient intensity and spectral quality to actuate the alarm. An infra-red detectors can respond to the total IR component of the flame alone or in combination with flame flicker in the frequency range of 5 to 30 Hz. A major problem in the use of infrared detectors receiving total IR radiation is the possible interference of solar radiation in the infrared region. When detectors are located in places shielded from the sun, such as vaults, filtering or shielding the unit from the sun's rays is unnecessary. In this study, we proposed method for redue a false alarm with using filtering & sensor technology for distinguish of causes of raise a false alarm and pure flame.

  • PDF

UV/IR Detector를 중심으로 한 화재감지 기술에 대한 고찰

  • 김영민;안형일;김응식
    • Proceedings of the Korean Institute of Industrial Safety Conference
    • /
    • 1999.06a
    • /
    • pp.39-44
    • /
    • 1999
  • 최근 들어 산업설비 및 건축물의 대형화, 다 기능화 추세가 두드러지게 나타나고 있는 가운데 화재발생으로 인한 인명 및 재산상의 피해규모가 비례적으로 증가하고 있다. 이에 화재의 근원적 원인과 발생 가능성을 미연에 방지하는 방화ㆍ방폭 기술의 개발이 무엇보다도 중요해지고 있다. 또한 화재예방이 불가능하였을 경우 신속한 화재감지를 통해 화재진압에 나서는 것과 화재특성을 분석하여 화재를 방지하는 것 역시 중요해지고 있다. (중략)

  • PDF

Optimum Installation Methods and Characteristics of the Hybrid Type Flame-Sensor (하이브라드형 화재감지기의 특성 및 최적 설치 방안)

  • Kim, Yeong-Min;Kim, Jong-Man;Shin, Dong-Yong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2010.06a
    • /
    • pp.286-286
    • /
    • 2010
  • In this paper, we proposed that optimum installation methods and characteristics of the hybrid type flame-sensor. The hybrid type flame-sensor has the high responsive performance. This research introduced the characteristics of the hybrid type flame-sensor, it was consist of IR/UV flame detector and proposed the optimum installation methods of false alarm reduced to resemble fire.

  • PDF