• Title/Summary/Keyword: Transient Recovery Voltage

Search Result 64, Processing Time 0.024 seconds

Analysis of Thermal Recovery Characteristics for $SF^6$ Gas-Blast Arc within Laval Nozzle (Laval Nozzle에 대한 $SF^6$ 아크의 열적회복특성 해석)

  • Song, Gi-Dong;Lee, Byeong-Yun;Gyeong-Yeop;Park, Jeong-Hu
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.51 no.9
    • /
    • pp.522-529
    • /
    • 2002
  • In this paper, computer simulations of the physical Phenomena occurring in the arc region before and after current zero were carried out to evaluate the thermal recovery characteristics of a Laval nozzle. A commercial CFD program "PHOENICS" is used for the simulation and the user-coded subroutines to consider the arcing phenomena were added to this program by the authors. The computed results were verified by the comparison with the test results presented by the research group of GE Co.(General Electric Company). In order to investigate the state of the arc region after current zero, the simulation was carried out with three steps. They are steady state arc simulation, transient arc simulation before current zero, and transient hot-gas flow simulation after current zero. The semi-experimental arc radiation model is adapted to consider the radiation energy transport and Prandtl's mixing length model is employed as the turbulence model. The electric field and the magnetic field were calculated with the same grid structure used for the simulation of the flow field. The post-arc current was calculated to evaluate the thermal recovery characteristics after current zero. Compared with the results obtained by GE Co., it has been found that the critical RRRV(ratio of rise of recovery voltage) will be determined previously by this study.his study.

Analysis of Thermal Recovery Characteristics for Nozzle of SF6 GCB Considering Nozzle Ablation (노즐용삭을 고려한 SF6 가스차단기 노즐의 열적회복특성 해석)

  • Lee Byeong-Yoon;Song Ki-Dong;Chong Jin-Kyo;Park Kyong-Yop
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.2
    • /
    • pp.76-82
    • /
    • 2005
  • In this paper, a method for analyzing the thermal recovery characteristics of the nozzle of gas circuit breaker was described. In order to obtain thermal recovery characteristics, the transient simulation of SF6 arc plasma within the nozzle was carried out. In particular, the nozzle ablation was taken into account by simultaneously solving the PTFE concentration equation with the governing equations such as continuity, momentum and energy equation. After that, post arc current calculation was performed with the rate of rise of recovery voltage changed. From the calculated post arc current, it was possible to suggest the thermal recovery characteristics of the nozzle of gas circuit breaker.

An Improved Gate Control Scheme for Overvoltage Clamping Under High Power IGBTs Switching (대용량 IGBT 스위칭 시 과전압 제한을 위한 향상된 게이트 구동기법)

  • 김완중;최창호;이요한;현동석
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.3 no.3
    • /
    • pp.222-230
    • /
    • 1998
  • This paper proposes a new gate drive circuit for high power IGBTs which can reduce the harmful effect of reverse recovery current at turn-on and actively suppress the overvoltage across the driven IGBT at turn-off without a snubber circuit. The turn-on scheme decreases the rising rate of the collector current by inereasing the input capacitance at turn-on transient when the gate-emitter voltage goes above threshold voltage. It results in soft transient of the reverse recovery current with no variation in turn-on delay time. The turn-off driving scheme has adaptive feature to the amplitude of collector current, so that the overvoltage can be limited much effectively at the fault collector current. Experimental results under various normal and fault conditions prove the effectiveness of the proposed circuit.

  • PDF

Investigation of the Impact of Voltage Sags on 3-Phase Induction Motors (순간전압강하가 3상 유도전동기에 미치는 영향 검토)

  • Kang, Bong-Seok;Kim, Jae-Chul;Moon, Jong-Fil;Yun, Sang-Yun
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.05a
    • /
    • pp.361-365
    • /
    • 2004
  • This paper describes the various characteristics of voltage sags which can affect the functions of three-phase induction motors that are mostly used in the power distribution systems. These assorted characteristics include motor speed losses, voltage recovery, motor reacceleration, and transient characteristics. An experimental study on the induction motor behaviors was also carried out to confirm these impacts. In addition sequential voltage sags with short durations were considered and investigated. The results show that the occurrence of the second voltage sag after the first one may affects the induction motor adversely.

  • PDF

Investigation of the Impact of Voltage Sags and Temporary Interruptions on 3-Phase Induction Motors (배전계통 순간전압강하 및 순간정전이 3상 유도전동기에 미치는 영향 검토)

  • Kang, Bong-Seok;Kim, Jae-Chul;Moon, Jong-Fil;Yun, Sang-Yun
    • Proceedings of the KIEE Conference
    • /
    • 2003.11a
    • /
    • pp.106-109
    • /
    • 2003
  • This paper describes the various characteristics of voltage sags and temporary interruptions which can affect the functions of 3-phase induction motors. These assorted characteristics include motor speed loss, voltage recovery, motor reacceleration, and transient characteristics. An experimental study on induction motor behavior was also carried out to confirm these impacts. Besides, sequential voltage sags of short duration were considered for this paper. The results show that the occurrence of the second voltage sag after the first one may affects the induction motor adversely.

  • PDF

Investigation of the impact of Voltage Sags on 3-Phase Induction Motors Considering Reclosing Interval in Distribution System (리클로징 시간을 고려한 배전계통 순간전압강하의 3상 유도전동기에 미치는 영향 검토)

  • Kang Bong Seok;Kim Jae Chul;Moon Jong Fil;Yun Sang Yun
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.45-47
    • /
    • 2004
  • This paper describes the various characteristics of voltage sags which can affect the functions of three-phase induction motors that are mostly used in the power distribution systems. These assorted characteristics include motor speed losses, voltage recovery, motor reacceleration, and transient characteristics. An experimental study on the induction motor behaviors was also carried out to confirm these impacts. In addition, sequential voltage sags with short durations were considered and investigated. The results show that the occurrence of the second voltage sag after the first one may affects the induction motor adversely.

  • PDF

Transient State Analysis of Network Connected to Wind Generation System (풍력발전시스템이 연계된 계통의 과도상태해석)

  • Kim, Se-Ho
    • Journal of the Korean Solar Energy Society
    • /
    • v.23 no.3
    • /
    • pp.29-35
    • /
    • 2003
  • Generator for wind power can be either synchronous or asynchronous (induction) types. Induction and synchronous generators behave in a different way when subjected to severe faults. Induction generators does not have an angle stability limit and short circuit in the neighborhood of an Induction generator causes the demagnetization of the machine when the fault is cleared, the voltage raises slowly, while the grid contributes with reactive power to the generator and the magnetic flux recovers. On the other hand in the synchronous generators the recovery of the voltage is immediate, since the excitation of the rotor angle comes from an independent circuit. This paper shows the result of the transient state analysis in the network connected to wind generation system Several case studies have been conducted to determine the effect of the clearing time of a fault on the network stability. It has been found that the critical clearing time can be as low as 61ms in the case of induction generator compared to 370ms in the case of synchronous generator.

Characteristics of Short-Circuit Protector in Pad-Mounted Transformer (지상변압기의 단락보호장치 특성연구)

  • Kim, K.H.;Lee, W.Y.;Sun, C.H.;Kim, D.M.;Kim, S.J.
    • Proceedings of the KIEE Conference
    • /
    • 1995.07c
    • /
    • pp.1350-1352
    • /
    • 1995
  • This paper discribed the characteristic of I-t cross-over-point between current limited-fuse and explusion fuse(Bay-O-Net Fuse) and fuse protection in pad-mounted transformer that was generated internal faults and the short circuit of secondary side(load side). In the I-t cross-over-point, current limited fuse was melted when transient recovery voltage was raised rapidly.

  • PDF

TRV analysis by using multi - port equivalent (다 단자망 축약 이론을 이용한 TRV 해석)

  • Yoon, Jae-Young;Moon, Young-Hyun;Park, Dong-Wook
    • Proceedings of the KIEE Conference
    • /
    • 1988.11a
    • /
    • pp.236-240
    • /
    • 1988
  • The simplified equivalent by using the short circuit impedance has been used for analyzing the prospective transient recovery voltage of the large power system. But it sometimes generates untorelable error in the rate-of-rise of TRV when using the Thevenin equivalent source. This paper provides the new equivalent by using the multi-port theory. The application of the new method to the sample system gives satisfactory accuracy compared with the short-circuit equivalent.

  • PDF