• Title/Summary/Keyword: Transformer fault diagnosis

Search Result 53, Processing Time 0.021 seconds

Intuitionistic Fuzzy Expert System based Fault Diagnosis using Dissolved Gas Analysis for Power Transformer

  • Mani, Geetha;Jerome, Jovitha
    • Journal of Electrical Engineering and Technology
    • /
    • v.9 no.6
    • /
    • pp.2058-2064
    • /
    • 2014
  • In transformer fault diagnosis, dissolved gas analysis (DGA) is been widely employed for a long period and numerous methods have been innovated to interpret its results. Still in some cases it fails to identify the corresponding faults. Due to the limitation of training data and non-linearity, the estimation of key-gas ratio in the transformer oil becomes more complicated. This paper presents Intuitionistic Fuzzy expert System (IFS) to diagnose several faults in a transformer. This revised approach is well suitable to diagnosis the transformer faults and the corresponding action to be taken. The proposed method is applied to an independent data of different power transformers and various case studies of historic trends of transformer units. It has been proved to be a very advantageous tool for transformer diagnosis and upkeep planning. This method has been successfully used to identify the type of fault developing within a transformer even if there is conflict in the results of AI technique applied to DGA data.

Expert System for Fault Diagnosis of Transformer

  • Kim, Jae-Chul;Jeon, Hee-Jong;Kong, Seong-Gon;Yoon, Yong-Han;Choi, Do-Hyuk;Jeon, Young-Jae
    • Journal of the Korean Institute of Intelligent Systems
    • /
    • v.7 no.1
    • /
    • pp.45-53
    • /
    • 1997
  • This paper presents hybrid expert system for diagnosis of electric power transformer faults. The expert system diagnose and detect faults in oil-filled power transformers based on dissolved gas analysis. As the preprocessing stage, fuzzy information theory is used to manage the uncertainty in transformer fault diagnosis using dissolved gas analysis. The Kohonen neural network takes the interim results by applying fuzzy informations theory as inputs, and performs the transformer fault diagnosis. The Proposed system tested gas records of power transformers from Korea Electric Power Corporation to verify the diagnosis performance of transformer faults.

  • PDF

Fault Diagnosis of Power Transformer Using Support Vector Machine (써포트 벡터머신을 이용한 전력용 변압기 고장진단)

  • Lim, Jae-Yoon;Lee, Dae-Jong;Lee, Jong-Pil;Ji, Pyeong-Shik
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.2
    • /
    • pp.62-69
    • /
    • 2009
  • For the fault diagnosis of power transformer, we develop a diagnosis algorithm based on support vector machine. The proposed fault diagnosis system consists of data acquisition, fault/normal diagnosis, and identification of fault. In data acquisition part, concentrated gases are extracted from transformer for data gas analysis. In fault/normal diagnosis part, KEPCO based decision rule is performed to separate normal state from fault types. The determination of fault type is executed by multi-class SVM in identification part. As the simulation results to verify the effectiveness, the proposed method showed more improved classification results than conventional methods.

Application of LVQ3 for Dissolved Gas Analysis for Power Transformer (전력용 변압기의 유중가스 분석을 위한 LVQ3의 적용)

  • Jeon, Yeong-Jae;Kim, Jae-Cheol
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.49 no.1
    • /
    • pp.31-36
    • /
    • 2000
  • To enhance the fault diagnosis ability for the dissolved gas analysis(DGA) of the power transformer, this paper proposes a learning vector quantization(LVQ) for the incipient fault recognition. LVQ is suitable expecially for pattern recognition such as fault diagnosis of power transformer using DGA because it improves the performance of Kohonen neural network by placing emphasis on the classification around the decision boundary. The capabilities of the proposed diagnosis system for the transformer DGA decision support have been extensively verified through the practical test data collected from Korea Electrical Power Corporation.

  • PDF

Fault Diagnosis of Transformer Based on Self-powered RFID Sensor Tag and Improved HHT

  • Wang, Tao;He, Yigang;Li, Bing;Shi, Tiancheng
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.5
    • /
    • pp.2134-2143
    • /
    • 2018
  • This work introduces a fault diagnosis method for transformer based on self-powered radio frequency identification (RFID) sensor tag and improved Hilbert-Huang transform (HHT). Consisted by RFID tag chip, power management circuit, MCU and accelerometer, the developed RFID sensor tag is used to acquire and wirelessly transmit the vibration signal. A customized power management including solar panel, low dropout (LDO) voltage regulator, supercapacitor and corresponding charging circuit is presented to guarantee constant DC power for the sensor tag. An improved band restricted empirical mode decomposition (BREMD) which is optimized by quantum-behaved particle swarm optimization (QPSO) algorithm is proposed to deal with the raw vibration signal. Compared with traditional methods, this improved BREMD method shows great superiority in reducing mode aliasing. Then, a promising fault diagnosis approach on the basis of Hilbert marginal spectrum variations is brought up. The measured results show that the presented power management circuit can generate 2.5V DC voltage for the rest of the sensor tag. The developed sensor tag can achieve a reliable communication distance of 17.8m in the test environment. Furthermore, the measurement results indicate the promising performance of fault diagnosis for transformer.

Neural Network Based Dissolved Gas Analysis Using Gas Composition Patterns Against Fault Causes

  • J. H. Sun;Kim, K. H.;P. B. Ha
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • v.3C no.4
    • /
    • pp.130-135
    • /
    • 2003
  • This study describes neural network based dissolved gas analysis using composition patterns of gas concentrations for transformer fault diagnosis. DGA samples were gathered from related literatures and classified into six types of faults and then a neural network was trained using the DGA samples. Diagnosis tests were performed by the trained neural network with DGA samples of serviced transformers, fault causes of which were identified by actual inspection. Diagnosis results by the neural network were in good agreement with actual faults.

PNN based Rogers Diagnosis Method for Fault Classification of Oil-filled Power Transformer (유입변압기 고장분류를 위한 PNN 기반 Rogers 진단기법 개발)

  • Lim, Jae-Yoon;Lee, Dae-Jong;Ji, Pyeong-Shik
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.65 no.4
    • /
    • pp.280-284
    • /
    • 2016
  • Stability and reliability of a power system in many respects depend on the condition of power transformers. Essential devices as power transformers are in a transmission and distribution system. Being one of the most expensive and important elements, a power transformer is a highly essential element, whose failures and damage may cause the outage of a power system. To detect the power transformer faults, dissolved gas analysis (DGA) is a widely-used method because of its high sensitivity to small amount of electrical faults. Among the various diagnosis methods, Rogers diagonsis method has been widely used in transformer in service. But this method cannot offer accurate diagnosis for all the faults. This paper proposes a fault diagnosis method of oil-filled power transformers using PNN(Probability Neural Network) based Rogers diagnosis method. The test result show better performance than conventional Rogers diagnosis method.

Fault Diagnosis of Oil-filled Power Transformer using DGA and Intelligent Probability Model (유중가스 분석법과 지능형 확률모델을 이용한 유입변압기 고장진단)

  • Lim, Jae-Yoon;Lee, Dae-Jong;Ji, Pyeong-Shik
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.65 no.3
    • /
    • pp.188-193
    • /
    • 2016
  • It has been proven that the dissolved gas analysis (DGA) is the most effective and convenient method to diagnose the transformers. The DGA is a simple, inexpensive, and non intrusive technique. Among the various diagnosis methods, IEC 60599 has been widely used in transformer in service. But this method cannot offer accurate diagnosis for all the faults. This paper proposes a fault diagnosis method of oil-filled power transformers using DGA and Intelligent Probability Model. To demonstrate the validity of the proposed method, experiment is performed and its results are illustrated.

Diagnosis of Fault and Abnormal Conditions in a Single-Phase Transformer Using S-parameter Measurement (S파라미터를 이용한 단상 변압기의 이상 상태 진단에 대한 연구)

  • Kim, Jeongeun;Kim, Kwangho;Nah, Wansoo
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.67 no.10
    • /
    • pp.1344-1352
    • /
    • 2018
  • In this paper, we propose a two-port S-parameter data to diagnose the fault conditions of a single-phase transformer. Using the S-parameters we can measure the reflection and transmission characteristics of signal power at the port of a transformer, which can also be converted into ABCD parameters and Z parameters through a well-known conversion formulas. Transformer fault diagnoses can be performed based on the intuitive and qualitative/quantitative characteristics of the these parameters. In addition, we can obtain wide frequency characteristics at the primary and secondary sides of the transformer, which can be used to get time domain responses using the inverse Fourier transformation with some specific input waveform. In order to verify the effectiveness of the proposed method, the fault conditions were analyzed in simulation and experiment for 3 kVA single phase transformer with 15: 5 turns ratio, and the validity of the proposed method was verified.

A Study on the Reliability of Failure Diagnosis Methods of Oil Filled Transformer using Actual Dissolved Gas Concentration (유중가스농도를 이용한 유입식 변압기 고장진단 기법의 신뢰성에 관한 연구)

  • Park, Jin-Yeub;Chin, Soo-Hwan;Park, In-Kyoo
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.60 no.3
    • /
    • pp.114-119
    • /
    • 2011
  • Large Power transformer is a complex and critical component of power plant and consists of cellulosic paper, insulation oil, core, coil etc. Insulation materials of transformer and related equipment break down to liberate dissolved gas due to corona, partial discharge, pyrolysis or thermal decomposition. The dissolved gas kinds can be related to the type of electrical faults, and the rate of gas generation can indicate the severity of the fault. The identities of gases being generated are using very useful to decide the condition of transformation status. Therefore dissolved gas analysis is one of the best condition monitoring methods for power transformer. Also, on-line multi-gas analyzer has been developed and installed to monitor the condition of critical transformers. Rogers method, IEC method, key gas method and Duval Triangle method are used to failure diagnosis typically, and those methods are using the ratio or kinds of dissolved gas to evaluate the condition of transformer. This paper analyzes the reliability of transformer diagnostic methods considering actual dissolved gas concentration. Fault diagnosis is performed based on the dissolved gas of five transformers which experienced various fault respectively in the field, and the diagnosis result is compared with the actual off-line fault analysis. In this comparison result, Diagnostic methods using dissolved gas ratio like Rogers method, IEC method are sometimes fall outside the ratio code and no diagnosis but Duval triangle method and Key gas method is correct comparatively.