• 제목/요약/키워드: TRNSYS(Transient System Simulation program)

검색결과 12건 처리시간 0.026초

향온시설물에 대한 현열 및 잠열 에너지 회수시스템의 성능해석 (Performance Analysis of Sensible and Latent Energy Recovery System for Thermally Controlled Facilities)

  • 박병규;김무근;김근오
    • 설비공학논문집
    • /
    • 제12권12호
    • /
    • pp.1057-1065
    • /
    • 2000
  • A sizing of sensible and latent energy recovery system with condensing heat exchanger is important to the design of a thermally controlled facilities. The transient system simulation program TRNSYS 14.2/IISiBat has been used to evaluate the energy consumptions of a thermally controlled facilities which consist of boiler, chiller and condensing heat exchanger, The boiler and chiller are selected based on the annual peak loads and controlled to maintain the setting temperature of $14~17^{\circ}C$. Simulation shows that the amount of sensible and latent energy recovered by heat exchanger is almost 20% of total heating load.

  • PDF

TRNSYS 기반 무창기공형 공기식 집열 시스템 부프로그램 개발에 관한 연구 (Study on Development of Subroutine based on TRNSYS for Unglazed Transpired Air Collector System)

  • 박준언;이의준;정모
    • 한국태양에너지학회 논문집
    • /
    • 제23권2호
    • /
    • pp.81-90
    • /
    • 2003
  • UTAC(unglazed transpired air collector) system has unique advantage for space heating and tempering ventilation air over the conventional collector system such as flat plate and vacuum collector. UTAC can improve radiative and convective loss due to nonglazed component and enhanced plate surface configuration. and heating energy and its equivalent green house emission performance can be improved from the use of this like collector in building application. The Option D Calibration simulation approach of IPMVP(International Performance Measurement and Verification Protocol) in ESCO businesses has been recommended to use of the calibrated computer modules like these Energy-10. DOE2.1E and TRNSYS(transient system simulation). This study is to develop subroutine type-203 of TRNSYS15.2 program and appraise thermal performance of UTAC. With newely addeded subroutine type-203. 1) Thermal performance of unglazed transpired collector could be possible based on dimensionless variables such as efficiency and heat exchanger effectiveness. and 2) Assessement of energy consists of solar useful and insulation saving for UTAC could be possible.

태양열 외기 난방 시스템의 열성능 시뮬레이션 및 검증 연구 (Solar Air Heating System Thermal Performance Simulation and Verification)

  • 강동언;이의준;현명택
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2001년도 춘계학술대회논문집D
    • /
    • pp.152-157
    • /
    • 2001
  • UTC(Unglazed Transpired Collector) system has recently emerged as a new solar air heating technology. It is relatively inexpensive because it has not a glazed material. And it demonstrates efficient particularly for the applications in which larger wall area facilities with a high outdoor air requirement. Mathematical algorithm for UTC thermal modeling has been understood for further improvement of the system. EES and TRNSYS model of actual solar wall panel could be developed for computer simulations under other conditions. Computer models could be validated with the measured data from fixed outdoor test cell in KIER(Korea Institute of Energy Research). Major design parameters could be identified such as panel configuration and absorptivity and emissivity values for UTC design.

  • PDF

대형마트의 조명 및 냉방 에너지 분석 및 에너지 절감 연구 (Analysis of Energy Consumption and Research on Energy Saving of Lighting and Coo1ing Energy of a Superstore)

  • 배창환;김영일;정광섭
    • 설비공학논문집
    • /
    • 제23권5호
    • /
    • pp.342-348
    • /
    • 2011
  • This study analyzes the current and after retrofit energy consumption of lighting and cooling system of a superstore in Seoul. Energy consumption data were measured and collected with a measurement system. Annual energy consumption was calculated using TRNSYS program. After replacing lighting and chiller with higher efficiencies, annual TOE consumption decreased from 1,066 before retrofit to 832 after retrofit, saving 234 TOE (22%) in total. Similarly, total annual $TCO_2$ consumption decreased from 2,214 to 1,721, reducing 493 $TCO_2$ (22%) during this pilot study.

지역난방 시스템에서 제어방법에 따른 공급열량의 해석적 연구 (The Analysis Study on Supplying Heat by Various Control Methods in District Heating System)

  • 김성수;정상훈;문연진;조성환;유재성
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.1008-1013
    • /
    • 2009
  • The theoretical simulation to predict the variation of supplying heat according to control methods of DHS(District Heating System) have been done by TRNSYS(A Transient System Simulation Program) 16. The physical system for DHS consists of primary and secondary supplying heating loop which is divided by based on heat exchanger for heating demand of building. The simulation results showed that control of secondary supplying heat had influenced more than primary supplying heat control to total energy consumption of DHS. And the outside temperature reset control of primary supplying heating loop could be reduced until about 4% overheating of each zone.

  • PDF

태양열 난방의 계절에 따른 에너지 저장

  • BRAUN J. E.;KEEIN S. A.;MITCHELL J. W.
    • 대한설비공학회지:설비저널
    • /
    • 제12권2호
    • /
    • pp.101-113
    • /
    • 1983
  • 논문은 물을 저장물질로 사용하는 공간난방에 있어서의 seasonal storage의 몇 가지 중요한 문제연구하고 있다. 집열기 면적과 저장체적 그리고 시스템 성능간의 관계를 transient simulation program(TRNSYS)을 사용하여 조사하였다. 여기서 seasonal storage의 가장 일어나기 쉬운 상태가 나타내어지는데 seasonal storage system의 설계에 특히 역점을 두고 있다. 이러한 설계방법은 몇 일간에서 seasonal storage에 이르는 seasonal pacity (저장용량)에 대하여 적용되어진다. 비용과 관련하여 이러한 설계방법은 seasonal storage system 경제성 (economic viability)을 추정하는데 유용할 것이다. 또한 시스템 설계에서 부하 열기의 크기 탱크단열 집열기 경사 매년 기후변화의 중요성이 조사되고 있다.

  • PDF

Modeling of Solar/Hydrogen/DEGS Hybrid System for Stand Alone Applications of a Large Store

  • Hong, Won-Pyo
    • 조명전기설비학회논문지
    • /
    • 제27권11호
    • /
    • pp.57-68
    • /
    • 2013
  • The market for distributed power generation based on renewable energy is increasing, particularly for standalone mini-grid applications in developing countries with limited energy resources. Stand-alone power systems (SAPS) are of special interest combined with renewable energy design in areas not connected to the electric grid. Traditionally, such systems have been powered by diesel engine generator sets (DEGS), but also hybrid systems with photovoltaic and/or wind energy conversion systems (WECS) are becoming quite common nowadays. Hybrid energy systems can now be used to generate energy consumed in remote areas and stand-alone microgrids. This paper describes the design, simulation and feasibility study of a hybrid energy system for a stand-alone power system. A simulated model is developed to investigate the design and performance of stand-alone hydrogen renewable energy systems. The analysis presented here is based on transient system simulation program (TRNSYS) with realistic ventilation load of a large store. Design of a hybrid energy system is site specific and depends on the resources available and the load demand.

Analysis on the Effect of Thermal Performance with Various Load Patterns for Solar Hot Water Heating System

  • Kim, Byoung-Gi;Jang, Hwan-Young;Chung, Kyung-Taek;Suh, Jeong-Se
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제15권3호
    • /
    • pp.108-113
    • /
    • 2007
  • The performance of a solar water heater incorporating evacuated tubes was evaluated using a transient simulation program, TRNSYS. Simulations were performed for $60^{\circ}C$ of hot water load temperature and for 280 liter of daily hot water volumes and three 400 liter of storage tank volumes. Three patterns of daily hot water consumption profile were used in the present study (morning, lunch and evening). The results show that the increase in solar fraction depends on the load profile, as well as the collector efficiency coefficient. Hot water draw profile has a large effect on the performance of the SDHWS, the morning load profile has the highest solar fraction. The annual solar fraction of the system, at the weather conditions of Jinju is approximately 84% at lunch load pattern, the 280 kg of load volume, 400 kg of tank volume and the $60^{\circ}C$ of load temperature.

태양열에 의한 냉방 및 난방시스템의 성능향상(I) - TRNSYS에 의한 동직열부하 계산과 태양열 시스템의 최적화 - (Improvement of the Performance of Solar Cooling Heating Systems(I) - Dynamic Load Calculation Using TRNSYS and an Optimization of Solar Systems -)

  • 강용태;김효경;노승탁
    • 대한설비공학회지:설비저널
    • /
    • 제17권6호
    • /
    • pp.696-707
    • /
    • 1988
  • This study simulates a typical solar system using the transient simulation program TRNSYS, and calculates the maximum cooling load of the model room of $50m^2$. In this study, energy rate control method is used in calculating a maximum cooling load. On the ground of the maximum cooling load of the model room, the variables that have an effect on the solar collection performance of the solar system are made a selection. Also in this study the trend of the solar collection performance is shown as the variables change. The results show that the variables which have an effect on the collection performance are collector area, collector mass flow rate, collector slope and the volume of storage tank, and the optimal value of Ac/Vt is not constant but varies as the collector area and the collector mass flow rate. Also the results show that for cooling system the optimal value of the collector slope is latitude minus $15^{\circ}$ during the seasonal operations, and twenty percent of the maximum cooling load is saved with the aid of the solar energy.

  • PDF

수직밀폐형 지중열교환기의 회로 과도해석 상사모델 개발 (Development of an Electric Circuit Transient Analogy Model in a Vertical Closed Loop Ground Heat Exchanger)

  • 김원욱;박홍희;김용찬
    • 설비공학논문집
    • /
    • 제24권4호
    • /
    • pp.306-314
    • /
    • 2012
  • Several numerical or analytical models have been proposed to analyze the thermal response of vertical ground heat exchangers (GHEX). However, most models are valid only after several hours of operation since they neglect the heat capacity of the borehole. Recently, the short time response of the GHEX became important in system simulation to improve efficiency. In this paper, a simple new method to evaluate the short time response of the GHEX by using an analogy model of electric circuit transient analysis was presented. The new transient heat exchanger model adopting the concept of thermal capacitance of the borehole as well as the steady-state thermal resistance showed the transient thermal resistance of the borehole. The model was validated by in-situ thermal response test and then compared with the DST model of the TRNSYS program.