• 제목/요약/키워드: Suspension Clamp

검색결과 6건 처리시간 0.021초

Metallurgical Failure Analysis on a Suspension Clamp in 154kV Electric Power Transmission Tower

  • 이재홍;정남근
    • KEPCO Journal on Electric Power and Energy
    • /
    • 제7권2호
    • /
    • pp.237-240
    • /
    • 2021
  • Failure of a suspension clamp made of hot dip galvanized cast iron in 154kV transmission tower was investigated. Metallurgical analysis of a crack of the clamp was performed using a digital microscope, an optical microscope, and a scanning electron microscope. It was revealed that the crack surface was covered by continuous zinc layer. Distinctive casting skin was found underneath both the outer surface and crack surface. The result showed that pre-existing crack had been formed in the fabrication, and liquid metal embrittlement during hot dip galvanization may assist crack propagation.

V련 현수애자장치의 클램프 횡진 특성 (A Characteristics of Horizontal Swing Angle of Suspension Clamp in V type Suspension String Sets)

  • 손홍관;이형권;민병욱
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제54권3호
    • /
    • pp.133-138
    • /
    • 2005
  • This paper presents a characteristics of horizontal swing angle in V type suspension string sets for 765kV T/L. The design of V type suspension string set does not differ from that of general string set for general towers, but it prevents instabilities from swing motion by the horizontal angle and by the wind pressure. We were designed specially 6 conductor yoke, arcing horn and earth horn. And we were decided to 550mm for a distance of strings. We were carried out characteristics of horizontal swing test and movement of mass center test for V-string sets of 400kN single, 300kN double and 400kN double. This products will be used for 765kV T/L of 1 circuit in suspension towers.

Beach-chair lateral traction position using a lateral decubitus distracter in shoulder arthroscopy

  • 김경천;이광진;신현대;변기용
    • 대한견주관절학회:학술대회논문집
    • /
    • 대한견주관절학회 2008년도 제16차 학술대회
    • /
    • pp.164-164
    • /
    • 2008
  • The beach-chair traction position is designed to allow the use of traction while allowing the surgeon to orient the shoulder in an upright position and convert to an open procedure, if necessary. The patient is placed in the beach-chair position under general anesthesia. A three-point shoulder holder (Arthrex, Naples, Florida) is attached to the rail of the operating table on the same side as the surgeon, whereas it is placed on the side opposite the surgeon in the lateral decubitus position. A shoulder traction and rotation sleeve (Arthrex) are affixed to the arm following the manufacturer's instructions. Positioning the thumb toward the closed side of the sleeve ensures a field for the anterior portion of the rotator cuff and prevents the tendency of the suspension apparatus to place the arm in internal rotation. The arm is maintained in 30 to 40 degree abduction and 30 to 40 degree flexion by controlling the length and height of the bar and the location of the universal clamp. The universal clamp allows multiple planes of adjustment to control abduction and forward movement of the arm. The sleeve is attached to the longitudinal traction cable using a sterile hook, and a lateral strap is secured around the proximal portion of the sleeve to the overhead traction cable to ensure a field for glenohumeral reconstruction. The use of a lateral strap permits ideal shoulder positioning for improved access to the anterior and inferior glenohumeral joint. The lateral strap can be released or removed to widen the subacromial space during subacromial decompression or rotator cuff repair. A 10-lb weight is attached to the longitudinal traction cable for an average-sized person.

  • PDF

진동기반의 SI 기법을 이용한 현수교 행어의 장력 추정 : III. 실험적 검증 (Estimating Tensile Force of Hangers in Suspension Bridges Using Frequency Based SI Technique : III. Experimental Verification)

  • 장한택;김병화;박대효
    • 대한토목학회논문집
    • /
    • 제28권2A호
    • /
    • pp.215-222
    • /
    • 2008
  • 본 논문은 현수교 이중 행어 시스템에 대한 진동기반 SI 장력추정기법의 실험적 검증을 소개한다. 현수교 이중 행어 시스템을 모사한 실험 모델을 제작되었으며, 세가지 경우의 클램프 위치에 대한 세가지 경우의 행어장력에 대해서 총 9회의 진동실험이 반복 수행되었다. 각각의 계측된 가속도 응답 데이터에 대해서, 모달분석을 통한 고유진동수와 모드 형상이 추출되었다. 추출된 일련의 동특성치들에 대하여 기존의 장력추정 이론인 현이론과 선형회기법을 적용하여 장력을 추정하였다. 또한 진동기반 SI 장력추정기법을 적용하여 장력을 추정하였는데, 추정된 장력은 수치모델과 계측모델의 동적 특성치들이 동일하게 될 때, 수치모델의 케이블 장력을 인식함으로써 추정되었다. 추정결과, 클램프의 위치에 따라서 기존의 이론을 이용한 추정장력의 오차는 최대 53.1%까지 보이는 반면, 진동기반 SI기법을 이용한 추정장력기법의 장력추정 오차는 모든 경우에 대하여 3% 이내 이다.

송전선로 폴리머애자 공사용 장비 개발 (Development of Working Platform for the Polymer Insulator String)

  • 민병욱;위화복;방항권;최한열;백수곤;박재웅
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 A
    • /
    • pp.438-439
    • /
    • 2006
  • Porcelain insulators have generally been used in Korea to insulate a transmission line from the tower, and a highly polymerized compound polymer insulator which has superior stain proof characteristics, has also been used widely. Currently, a worker rides on the suspension insulator string for installation on towers and conductors but in case of polymer insulators, this will pollute and scratch the housing result in durability reduction by deterioration and corona. This study developed a high strength aluminum compound metal lauder designed to work on polymer insulators without riding, and a clamp type connecting device and safety gear for easy installation on the tower and conductor. These polymer insulator work device can be used for 154kV and 345kV polymer insulators through a strength and load test to secure safety. This paper presents field usage.

  • PDF

유한요소모델 기반 장력추정 기법의 비교 연구 (A Comparative Study of Finite Element Model-Based Tension Estimation Techniques)

  • 박규식;이정휘;성택룡;윤태양;김병화
    • 한국강구조학회 논문집
    • /
    • 제21권2호
    • /
    • pp.165-173
    • /
    • 2009
  • 현수교 행어케이블은 일부가 클램프로 구속되어 있어 단일 케이블 모델을 기반으로 한 기존의 장력추정 방법들은 휨감성의 영향이 큰 짧은 케이블 일수록 오차가 커지게 된다. 따라서 최근에 유한요소모델 기반의 역해석 기법 및 시스템인식 기법을 이용한 장력추정 방법이 제안되었다. 본 논문은 광안대교 행어케이블을 대상으로 역해석 기법 및 시스템인식 기법을 이용한 장력추정 방법의 적용성을 비교 검토 하였다. 장력추정결과 유한요소모델을 기반으로 한 역해석 기법 및 시스템인식 기법은 기존의 현이론 및 선형회귀법에 의한 장력추정 방법에 비해 고유진동수 오차를 기준으로 보다 높은 신뢰성을 가지고 장력을 추정하였다. 하지만 모델기반의 장력추정 방법은 유한요소모델의 정확도에 따라 그 오차가 다르게 나타날 수 있다. 특히, 짧은 케이블 일수록 경계조건의 영향을 많이 받기 때문에 가능하다면 실험을 통해 경계조건을 명확히 파악하는 것이 중요하다. 시스템인식 기법을 이용한 장력추정 방법은 다양한 경계조건을 용이하게 고려할 수 있으며, 또한 입력되는 계측 고유진동수의 개수에 민감하지 않기 때문에 그 효용성이 높다고 할 수 있다.