• 제목/요약/키워드: Supply air temperature

검색결과 475건 처리시간 0.025초

데이터센터의 급기온도 변화가 서버 냉각 성능에 미치는 영향에 대한 연구 (A Study on the Effects of Supply Air Temperature on the Server Cooling Performance in a Data Center)

  • 장현재
    • 설비공학논문집
    • /
    • 제30권2호
    • /
    • pp.83-91
    • /
    • 2018
  • A datacenter is a high energy consuming facility whose cooling energy consumption rate is 10~20 times larger than general office buildings. The higher the temperature of supply air from a CRAC (computer room air-conditioner) is supplied, the more energy efficient cooling is possible because of improving the COP of a chiller and advanced range of outdoor air temperature available for the economizer cycles. However, because the temperature of cold air flowing into server computers varies depending on air mixing configurations in a computer room, the proper supply air temperature must be considered based on the investigation of air mixing and heat dissipation. By these, this study aims to understand the effects of variation of the supply air temperature on the air flow distributions, temperature distributions and rack cooling efficiencies. Computational fluid dynamics (CFD) aided in conducting the investigation. As a result, the variation of the supply air temperature does not affect the air flow distributions. However, it mainly affects the temperature distribution. From the results of CFD simulations, Rack cooling indices (RCIHI and RCILO) were evaluated and showed the ideal state set at $19^{\circ}C$ of the supply air temperature.

급기환기량에 따른 공조기의 설정온도 도달특성 분석 연구 (A Study on the Reaching Time of Setting Temperature with Ventilation Air)

  • 강태욱
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제30권1호
    • /
    • pp.50-57
    • /
    • 2006
  • This study describes to analyze the cooling load characteristics for a room air conditioner as a function of supply ventilation air when an air conditioner is running An experimental apparatus consists of a test room, a room air conditioner, a humidifier, an electrical heater a supply fan and a controller The reaching time to the inside setting temperature of the room air conditioner with is evaluated theoretically and experimentally in a conditioned space cooling loads such as supply ventilation air, lighting, occupancy and infiltration. In the conditions of cooling loads for the supply ventilation air of 9.5 L/s(0.98 ACH). lights. one Person, and infiltration, the reaching time to the inside setting temperature ($27\;^{\circ}C$ dry-bulb) increases up to $35\%$ more than for no supply ventilation air condition. Theoretical modelling of the reaching time shows good agreement with experimental results.

A PID Control of Supply Duct Outlet Air Temperature in Personal Environment Module

  • Park, Young-Chil
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제11권2호
    • /
    • pp.82-90
    • /
    • 2003
  • The work presented here is a design and an implementation of PID control system to regulate a supply duct outlet air temperature in PEM (Personal Environment Module). In PEM, the air is heated to the required temperature while it flows through the supply duct without any mixing chamber. This makes the control of air temperature in PEM difficult. A simulation is done first to understand the relationship between a temperature distribution in working area, flow rate and the outlet air temperature of PEM. Then a linear dynamic model of heating process in PEM is derived. P, PD and PID type control systems, to provide the rapid response without overshoot and saturation in heater command voltage, are designed using a linear model obtained. Experimentally obtained data shows that the control system satisfies the design criteria and works properly in controlling the supply duct outlet air temperature.

사무실 공간의 냉방시 천장 및 바닥 급기 공조 방식에 따른 열환경 평가 실험 (Experimental Analysis of Thermal Comfort of an Office Space for Ceiling and Floor Supply Air Conditioning Systems)

  • 조용;권혁승;김성현;김영일
    • 설비공학논문집
    • /
    • 제12권9호
    • /
    • pp.810-816
    • /
    • 2000
  • Thermal comfort plays an important role in modern office buildings. Four major factors affecting thermal comfort are air temperature, velocity, humidity and radiation temperature. Distribution of these thermal factors in indoor space depends largely on the air flow which is related to the method of supplying and extracting air. In this study, an experimental analysis on indoor thermal comfort is conducted to study the difference between a ceiling supply cooling system and a floor supply one. The two cooling systems are applied to an office space during summer season and the distributions of temperature, velocity, radiation temperature and PMV are measured. Results show that the floor supply cooling system is superior in terms of thermal comfort and energy saving. Studies need to be done, however, to reduce the vertical temperature difference of a floor supply air conditioning system.

  • PDF

콘덴싱가스보일러 제어를 위한 공급수알고리즘 (The Supply Water Algorithm for a Condensing Gas Boiler Control)

  • 한도영;유병강
    • 설비공학논문집
    • /
    • 제23권6호
    • /
    • pp.441-448
    • /
    • 2011
  • The energy consumption of a condensing gas boiler may be greatly reduced by the effective operation of the unit. In this study, the supply water algorithm for a condensing gas boiler control was developed by using the fuzzy logic. This includes the supply water set temperature algorithm, and the control algorithms of a gas valve, a blower and a pump. For the set temperature algorithm, the outside air temperature and the return water temperature were used as input variables. The supply water temperature difference and its slope were used as input variables of the gas valve and blower control algorithm. And the supply water temperature and the return water temperature were used as input variables of the pump control algorithm. In order to analyse performances of these algorithms, the dynamic model of a condensing gas boiler was used. The initial start-up test, the supply water set temperature change test, the outside air temperature change test, and the return water temperature change test were performed. Simulation results showed that algorithms developed in this study may be practically applied for the effective control of a condensing gas boiler.

외기온도 변화에 따른 집단에너지 공동주택의 최적 열공급제어 알고리즘 개발에 관한 연구 (Study on the Development of Optimal Heat Supply Control Algorithm in Group Energy Apartment Building According to the Variation of Outdoor Air Temperature)

  • 변재기;이규호;최영돈;신종근
    • 설비공학논문집
    • /
    • 제23권5호
    • /
    • pp.334-341
    • /
    • 2011
  • In the present study, optimal heat supply algorithm which minimize the heat loss through the distribution pipe line in group energy apartment was developed. Variation of heating load of group energy apartment building in accord with the outdoor air temperature was predicted by the heating load-outdoor temperature correlation. Supply water temperature and mass flow rate were controlled to minimize the heat loss through distribution pipe line. District heating apartment building located in Hwaseong city, which has 1,473 households, was selected as the object building for testing the present heat supply a1gorithm. Compared to the previous heat supply system, 10.4% heat loss reduction can be accomplished by employing the present method.

바닥복사 난방시스템의 공급온수온도가 실내 열환경에 미치는 영향 (The Effects of Hot Water Supply Temperature on Indoor Thermal Characteristics for Floor Radiant Heating System)

  • 안병천
    • 한국지열·수열에너지학회논문집
    • /
    • 제14권4호
    • /
    • pp.13-19
    • /
    • 2018
  • The Effects of hot water supply temperature on indoor thermal characteristics for floor radiant heating system in residential apartment were researched by computer simulation. The parametric study on hot water supply temperatures with different outdoor air temperatures was done with regard to energy performance and control characteristics, respectively. As a result, the maximum overshoot of indoor air temperature and energy consumption were reduced by adjusting the hot water supply temperatures with outdoor air temperatures.

바닥온돌 매립형 환기덕트시스템의 온도변화에 대한 고찰 (The Changes of Temperature for Embedded Duct Ventilation System in Ondol)

  • 김옥;박진철;김남규;오재근
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.375-380
    • /
    • 2006
  • Embedded Duct Ventilation System in Ondol is embedded supply duct in Ondol. This system allows heat up outside air to inside temperature with out using heat exchanger and electric heating coiling in winter season. In this research, we measured temperature of inside and surface of Ondol, supply duct, and supply air temperature incorporate embedded duct ventilation system in Ondol in model house($110m^2$) & one room($23m^2$)

  • PDF

급기각도가 사무실 공간의 냉방 및 난방 성능에 미치는 영향 (The Effect of Supply Angle on Cooling and Heating Performances of Office Space)

  • 김묘선;김영일;정광섭
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.497-501
    • /
    • 2009
  • Effect of angle of supply air on cooling and heating performances of office space is studied by numerical simulation. For a constant air volume(CAV) air-conditioning system, air is supplied vertically($90^{\circ}$) and horizontally($10^{\circ}$). Due to buoyancy, the supply angle affects the performance of cooling and heating. In cooling, since the cold supply air tends to move downward due to its high density, horizontal supply angle is better for uniform temperature distribution. In heating, however, vertical supply angle is preferred for better mean and uniform temperature distribution.

  • PDF

실험동물 사육실용 바이오 크린룸(BCR)의 급기 온도 및 풍속 변화 특성에 관한 수치해석적 연구 (A Study on the Variation of Airflow Velocity and Temperature upon the Design of Bio Clean Room(BCR) for Laboratory Animal Facilities by Numerical Simulation)

  • 박동일;정광섭;김영일;김성민
    • 설비공학논문집
    • /
    • 제24권7호
    • /
    • pp.578-584
    • /
    • 2012
  • In this study, the analysis on the distribution of indoor airflow velocity and temperature by using numerical simulation has carried out to make fundamental data for establishing the optimum design of laboratory animal facilities. From the results, it was found that replacement of cage lacks, air supply and exhaust system, supply air temperature, supply air velocity affect to the optimum design of laboratory animal facilities as a important element.