Performance Analysis of Cooling Tower-Assisted Hybrid Ground-Coupled Heat Pump (HGCHP) System (냉각탑 병용 하이브리드 지열 히트펌프 시스템의 성능 분석)

  • Sohn, Byonghu;Lee, Doo-Young;Choi, Jae-Ho;Min, Kyong-Chon
    • Transactions of the KSME C: Technology and Education
    • /
    • v.4 no.1
    • /
    • pp.19-26
    • /
    • 2016
  • This paper presents the measurement and analysis results for the performance of HGCHP system using a cooling tower as a supplemental heat rejector. In order to demonstrate the performance of the hybrid approach, we installed the monitoring equipments including sensors for measuring temperature and power consumption, and measured operation parameters from February 1, 2014 to February 28, 2015. Leaving load temperatures to building showed an average value of $11.7^{\circ}C$ for cooling and $39.5^{\circ}C$ for heating, respectively. From the analysis, the daily PF of hybrid GCHP system varied from 2.6 to 6.6 over the measurement period.

Cooling Performance of Cooling Tower-Assisted Ground-Coupled Heat Pump (GCHP) System Applied in Hospital Building (병원 건물에 설치된 냉각탑 병용 지열 히트펌프 시스템의 냉방 성능)

  • Sohn, Byonghu;Lee, Doo-Young;Min, Kyung-Chon
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.12 no.1
    • /
    • pp.7-16
    • /
    • 2016
  • This paper presents the measurement and analysis results for the cooling performance of ground-coupled heat pump (GCHP) system using a cooling tower as a supplemental heat rejector. In order to demonstrate the performance of the hybrid approach, we installed the monitoring equipments including sensors for measuring temperature and power consumption, and measured operation parameters from May 1 to October 30, 2014. The results showed that the entering source temperature of brine returning from the ground heat exchanger was in a range of design target temperature. Leaving load temperatures to building showed an average value of $11.4^{\circ}C$ for cooling season. From the analysis, the daily performance factor (PF) of geothermal heat pumps ranged from 4.4 to 5.2, while the daily PF of hybrid GCHP system varied from 3.0 to 4.0 over the entire cooling season.