• Title/Summary/Keyword: Superconducting Fault Current Limiter

Search Result 493, Processing Time 0.024 seconds

Operating Characteristics of Capacity Increase in a Flux-Lock Type Superconducting Fault Current Limiter (자속구속형 초전도 전류제한기의 용량증대를 위한 동작특성)

  • Nam, Gueng-Hyun;Choi, Hyo-Sang;Park, Hyoung-Min;Cho, Yong-Sun;Lee, Na-Young;Han, Tae-Hee
    • Proceedings of the KIEE Conference
    • /
    • 2006.04b
    • /
    • pp.200-202
    • /
    • 2006
  • We investigated the operating characteristics of a flux-lock type superconducting fault current limiters according to the number of the serial connection each the superconducting element at the additive polarity winding of a transformer. This SFCL consists of two coils wound in parallel on the same iron core, and the secondary coil is connected to the elements in series. Operating characteristics can be controlled by adjusting the inductances and the winding directions of the coils. It turns ratio between the primary and the secondary coils is 63:21. The analysis of voltage, current, and resistance in serial connection each element was performed to increase the applied voltage of flux-lock type SFCL. When the applied voltage was 200/$\sqrt{3}[V_{rms}]$ with three elements connected in seres, the peak value of the line current increased up to 26,24[A]. On the other hands, resistive SFCL increased up to 36.35[A], under the same conditions. This enabled the flux-lock type SFCL to be easy to increase the capacity of power system.

  • PDF

Transient Characteristics of a Transformer Type SFCL Applying the Superconductor and the Normal-conductor into the Secondary Winding (초전도체 및 상전도체의 변압기 2차측 적용에 따른 변압기형 SFCL 특성 비교)

  • Jung, Byung-Ik;Choi, Hyo-Sang
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.65 no.5
    • /
    • pp.873-877
    • /
    • 2016
  • This paper proposed the structure that applied superconductors to the neutral line of a transformer and applied the normal conductors to the third line. The superconductor applied to the neutral line of a transformer limited the peak value of initial fault current, while the normal conductor finally limited the fault current. In order to secure the operating reliability of transformer type Superconducting Fault Current Limiter (SFCL) of previously proposed structure, we analyzed the operating characteristics according to the fault types. We tested a line-to-ground fault and a line-to-line fault. As a result of the experiment, all the faults showed that the superconductor stably limited the peak-value of initial fault current. Also, the normal conductor finally limited the fault current. Based on this research results, We thought that if the structure of inserting superconductor into the neutral line is applied to the real system, it could improve the reliability and stability of the power system.

Investigation on the inductive and resistive fault current limiting HTS power cable

  • Lee, Sangyoon;Choi, Jongho;Kim, Dongmin;Kwon, Yonghyun;Kim, Seokho;Sim, Kideok;Cho, Jeonwook
    • Progress in Superconductivity and Cryogenics
    • /
    • v.16 no.2
    • /
    • pp.59-63
    • /
    • 2014
  • HTS power cable bypass the fault current through the former to protect superconducting tapes. On the other hand, the fault current limiting (FCL) power cable can be considered to mitigate the fault current using its increased inductance and resistance. Using the increased resistance of the cable is similar to the conventional resistive fault current limiter. In case of HTS power cable, the magnetic field of HTS power cable is mostly shielded by the induced current on the shield layer during normal operation. However, quench occurs at the shield layer and its current is kept below its critical current at the fault condition. Consequently, the magnetic field starts to spread out and it generates additional inductive impedance of the cable. The inductive impedance can be enhanced more by installing materials of high magnetic susceptibility around the HTS power cable. It is a concept of SFCL power cable. In this paper, a sample SFCL power cable is suggested and experimental results are presented to investigate the effect of iron cover on the impedance generation. The tests results are analyzed to verify the generation of the inductive and resistive impedance. The analysis results suggest the possible applications of the SFCL power cable to reduce the fault current in a real grid.

Analysis on Operating Characteristics according to Applied Location of SFCL in a Power Transmission System (모의송전계통에서 고장전류 저감을 위한 초전도한류기 적용위치에 따른 동작특성 분석)

  • Lee, Hyeong-Jin;Park, Han-Min;Kim, Jin-Seok;Sung, In-Je;Lim, Sung-Hun;Kim, Jae-Chul
    • Proceedings of the KIEE Conference
    • /
    • 2015.07a
    • /
    • pp.1104-1105
    • /
    • 2015
  • Recently, electric power demand increase due to the rapid industrial development. As a result, a power system has been expanded and fault currents are raised. Fault current is detriment effect on protective equipment. Superconducting fault current limiter(SFCL) is one of the solution to solve the fault current reduction. This paper analyzed operating characteristics according to applied location of SFCL in a transmission power system through the PSCAD/EMTDC simulation.

  • PDF

Bus-tie application scheme of 154 kV class SFCLs in Korean power systems

  • Lee, Seung-Ryul;Yoon, Jae-Young;Park, Jong-Young;Lee, Byong-Jun
    • Progress in Superconductivity and Cryogenics
    • /
    • v.11 no.4
    • /
    • pp.29-32
    • /
    • 2009
  • This paper proposes the bus-tie application scheme of 154 kV SFCL (superconducting fault current limiter) in Korean power system. The reduced amount of fault current by SFCL is different by where the SFCL is installed. Therefore the inflow ratio of fault current (IRFC) is suggested to consider the effect of an SFCL's location. The proposed scheme was applied to the Korean Power System of 2010, and fault currents were calculated and analyzed with this coefficient. Simulations show that the location with high IRFC is adequate to install SFCL but more consideration of other things is required to determine the location and capacity of SFCL.

design of shielded inductive SFCL made of high $T_c$ superconductor (고온초전도체를 이용한 차폐유도형 전류제한기의 설계)

  • Lim, Sung-Hun;Kang, Hyeong-Gon;Park, Kyung-Kuk;Han, Tae-Hee;Cho, Dong-Eon;Han, Byoung-Sung
    • Proceedings of the KIEE Conference
    • /
    • 1998.07d
    • /
    • pp.1531-1533
    • /
    • 1998
  • In this paper, the characteristics of the shielded inductive superconducting fault current limiter was designed and simulated. Parameters of design for superconducting tube, core and primary coil were first determined. And then according to the system characteristics such as load resistance, fault angle and source voltage, the simple power system composed of shielded inductive FCL was simulated by computer-aided numerical analysis. The flowing currents under the fault condition can be limited to about 10 A.

  • PDF

Current and voltage loading tests off resistive SFCL

  • 최효상;현옥배;김혜림;황시돌;박권배
    • Progress in Superconductivity
    • /
    • v.3 no.2
    • /
    • pp.241-246
    • /
    • 2002
  • We have performed the current and voltage loading tests of resistive superconducting fault current limiters (SFCLS) based on $YBa_2$$Cu_3$$O_{7}$(YBCO) films with the diameter of 2 inch. The SFCL consists of meander-type YBCO stripes covered with 200 nm Au layer grown in situ for current shunt and heat dispersion at hot spots. The minimum quench current of an SFCL unit was about 25 Apeak. Seven SFCL units were connected in parallel fur the current load ing tests at power source of 100 $V_{rms}$ $/2,000A_{rms}$. This SFCL units had maximum limiting current of 170 Apeak during the fault instant and then successfully controlled the fault current below 100 Apeak within 1~2 msec after short circuit. Increased short current also reduced the quench completion time with little change of current limiting characterization. We connected six SFCL units in series fur the voltage loading tests at power source of $1,200 V_{rms}$/170 $A_{rms}$ at this time. The shunt resistors were inserted into each SFCL unit to eliminate power imbalance originated from serial connection of SFCL units. Each SFCL unit was quenched simultaneously during the fault condition. The current increased up to 40 $A_{peak}$ and decreased to 14 $A_{peak}$ after 3 cycles. Quench was completed within 1 msec after the fault. We confirmed operating characteristics of 140 kVA($120 A_{rms}$ $\times$ 1,200 $V_{rms}$) SFCL and presented the manufacturing possibility of 3.3 kV SFCL using 4 inch YBCO films.BCO films.lms.

  • PDF

Characteristics of Sub-cooled Nitrogen Cryogenic System for Applied High-Tc Superconducting Devices (고온초전도 응용기기용 과냉질소 냉각시스템의 냉각특성)

  • 강형구;김형진;배덕권;안민철;윤용수;장호명;고태국
    • Progress in Superconductivity and Cryogenics
    • /
    • v.6 no.1
    • /
    • pp.38-42
    • /
    • 2004
  • The cryogenic system for 6.6 kV/200 A inductive superconducting fault current limiter (SFCL) was developed at Yonsei university in 2003. The sub-cooled nitrogen cryogenic system could be applied to not only SFCL but also many other applied high-Tc superconducting (HTS) devices like superconducting motor, superconducting generator and superconducting magnetic energy storage (SMES). Generally, the cooling capacity of GM-cryocooler depends on the load temperature. Therefore it is necessary to perform the cooling capacity test at no load condition to calculate the exact cooling power and heat load of cryogenic system. In this research, the cooling capacity test of GM-cryocooler was executed and the heat load of developed cryogenic system was calculated. The long run operation test results of sub-cooled nitrogen cryogenic system were successful in pressure and temperature condition. Moreover, the design and fabrication method of cryogenic system were introduced and the test results were described.

Experimental and Analytical Studies on the Characteristics of Fast Switch in Combinations of Various Superconducting Tapes (다양한 선재 조합에 따른 이종 초전도 스위치의 특성 실험 및 분석)

  • Lee, Ji-Ho;Kim, Young-Jae;Na, Jin-Bae;Choi, Suk-Jin;Jang, Jae-Young;Hwang, Young-Jin;Kim, Jin-Sub;Ko, Tae-Kuk
    • Progress in Superconductivity and Cryogenics
    • /
    • v.13 no.1
    • /
    • pp.31-35
    • /
    • 2011
  • A Hybrid Fault Current Limiter(FCL) which has more advantages in fast response and thermal characteristics than a simple resistive FCL had been proposed by our group. The Hybrid FCL consists of a resistive FCL for the magnitude of the first peak of fault current, and a fast switch for detecting fault current and generating the repulsive force within a cycle in fault situation. In ideal case, the impedance of the fast switch wound with two other kinds of HTS tape is negligibly zero in normal operation. But, during the fault situation, each HTS tape has different quench characteristics because of asymmetric current distribution. And this phenomenon causes effective flux and this flux opens the switch through the repulsive force applied to a metal plate of the fast switch. The magnitude of the repulsive force affects the switching characteristics of the fast switch. It should be large enough to raise the metal plate up. Otherwise the arc re-out break which are caused by not enough repulsive force to raise the metal plate up can cause unintended operation of the fast switch. In this paper, the numerical calculation of the repulsive force applied to the metal plate of the fast switch in various combinations of HTS tapes was performed by using the short-circuit test and finite element method.

Quench Characteristics of HTSC Elements according to fault types in Integrated Three-Phase (삼상일체화된 자속구속형 SFCL의 사고종류에 따른 소자들의 퀜치 특성)

  • Park, Chung-Ryul;Lee, Jong-Hwa;Park, Sig;Du, Ho-Ik;Lim, Sung-Hun;Choi, Hyo-Sang;Han, Byoung-Sung
    • Proceedings of the KIEE Conference
    • /
    • 2005.07b
    • /
    • pp.960-962
    • /
    • 2005
  • In this paper, we investigated the quench characteristics of high-Tc superconducting(HTSC) elements in the integrated three-phase flux-lock type superconducting fault current limiter(SFCL) according to fault types such as the single-line-to-ground fault, the double-line-to-ground fault, the line-to-line fault and the triple-line-to-ground fault. The integrated three-phase flux-lock type SFCL is an upgrade version of single-phase flux-lock type SFCL. The structure of the integrated three-phase flux-lock type SFCL consisted of a three-phase flux-lock reactor wound on an iron core with the ratio of the same turn between coil 1 and coil 2 in each phase. When the SFCL is under the normal condition, the flux generated in the iron core is zero because the flux generated between two coils of each single phase is canceled out. Therefore, the SFCL's impedance is zero, and the SFCL has negligible influence on the power system. However, if a fault occurs in any single one of three phases, the flux generated in the iron core is not zero any more. The flux makes HTSC elements of all phases to quench irrespective of the fault type, which reduces the current in fault phase as well as the current of sound phase. It was obtained that the fault current limiting characteristics of the suggested SFCL were dependent on the quench characteristics of HTSC elements in all three phases.

  • PDF