A Numerical Study on the Smoke Control in Side-Platform Type Subway Station Fires (상대식 지하철 역사내 화재시 연기제어에 관한 수치해석적 연구)

  • Lee, Sung-Ryong;Ryou, Hong-Sun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.20 no.2
    • /
    • pp.81-86
    • /
    • 2008
  • In this study, numerical simulations were carried out to analyze the effect of the smoke extraction system and fire shutters in subway station fires using FDS 4.0. Subway station used in the experiment was 205 m long. Simulation results are validated by comparing with experimental results. Simulation results showed good agreement with experimental results within $20\;^{\circ}C$. 20 MW polystyrene was used as a fuel in the numerical prediction. Numerical predictions were performed in the side-platform type subway station in case of a train fire. Temperature and CO concentration were lowered by the operation of smoke extraction system.

A Numerical Study on the Smoke Control in Center-Platform Type Subway Station Fires (섬식 지하철역사내 화재시 연기제어에 관한 수치해석적 연구)

  • Lee, Sung-Ryong;Ryou, Hong-Sun
    • Journal of the Korean Society for Railway
    • /
    • v.10 no.3 s.40
    • /
    • pp.313-318
    • /
    • 2007
  • In this study, numerical simulations were carried out to analyze the effect of the smoke extraction system and fire shutters in subway station fires using FDS 4.0. Subway station used in the experiment was 145 m long. Simulation results are validated by comparing with experimental results. Simulation results showed good agreement with experimental results within $10^{\circ}C$. 10 MW polystyrene was used as a fuel in the numerical prediction. Numerical predictions were performed in the center-platform type subway station in case of a kiosk fire. Temperature and CO concentration were lowered by the operation of smoke extraction system. But, the operation of fire shutters had little effect on temperature and CO concentration in the platform level.

Evaluation of the Appropriateness of Smoke Control Conditions of Platform at the Subway Fire by using FDS (FDS를 이용한 지하철 객실 화재 시 승강장 제연조건의 적정성 평가)

  • Kim, Ki-Sung;Song, Dong-Woo;Lee, Su-Kyung
    • Fire Science and Engineering
    • /
    • v.27 no.5
    • /
    • pp.8-14
    • /
    • 2013
  • In the subway, various fires continue to take place across the world. In the Daegu subway accident in 2003, many people were damaged by shortened visibility range caused by toxic gas and smoke. This paper, assuming that a subway fire happens in the Mandeok Station of the subway system in Busan, analyzed different smoke-spreading situations depending on the ventilation situation at its platform (opening of the train doors, operation of ventilation facilities in the tunnel, and working of fire door), using FDS. The calculation proved that it would be more effective to secure evacuation route when the ventilation facilities of the tunnel are not operated, than when they are on. And, it was also found that the case where the doors of the platform to the escape route and only the platform-facing doors of the subway car on fire office are open would be more effective to ventilation than the case where all the doors are open. And, it was found to be important that the fire doors of the platform are working properly.

Visualization of Smoke Flow in the Subway Fire (지하철 화재발생시 역사내 화재연기 거동 가시화 연구)

  • Choi Chang Jin;Jung Hae Gon;Kim Sang Moon;Kim Kyung Chun
    • 한국가시화정보학회:학술대회논문집
    • /
    • 2005.12a
    • /
    • pp.64-68
    • /
    • 2005
  • In this study, the smoke flows of the inner subway station were visualized through a numerical analysis and visualization experiment in the subway fire. A transparent acrylic model was designed and installed as 1:25th scale-down as the actual subway station by using geometrical similarity The properties of subway fire were reconstructed according to Densimetric Froude Similarity. The 47 to 53 ratio of the mixed air and Helium was inputted in the inner acrylic model to describe 1MW fire intensity with reference to the experiment paper. For the same time, the fire smoke from a smoke generator was inputted in the inner acrylic model with the mixture. At this time, the buoyancy effect of Helium gas went up the smoke to the acrylic model. When the sheet beam of Ar-lon laser was given out to the top and stair of subway model, the digital camcorder took the images of the scattered cluster of smoke particles when applying the smoke management system and PSD.

  • PDF

A Numerical Study on Passengers' Evacuation in a subway station in case of Fire Occurrence (화재 발생 지하철 역사에서의 여객 대피 해석에 관한 연구)

  • Kim, Chi-Gyeom;Lee, Sung-Won;Hur, Nahm-Keon;Nam, Seong-Won
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.142-147
    • /
    • 2009
  • In the present study, a numerical simulation of passenger evacuation in a subway station was performed. Algorithm for passenger flow analysis based on DEM(Discrete Element Method) has been improved to simulate passenger flow in detailed geometry. The effect of grid density was assessed in the present study to show the advantage of using finer grid in the simulation. The method of coupling passenger flow and fire simulation has also been investigated to analyze passenger evacuation flow under fire. In this method the CO distributions in the subway station was used to assess fire hazards of passenger by means of FED(Fractional Effective Dose) model. Using the coupled algorithm a simulation for passenger evacuation flow and fire analysis were performed simultaneously in the simplified subway station. This algorithm could be used in the design of subway station for the purpose of passengers' safety in case of fire.

  • PDF

A Study on the fire Safety Plan in downtown underground Space (I) (도심지하공간의 화재안전계획에 관한 연구 (I))

  • Seo, Dong-Goo;Hwang, Hyun-Bae;Kwon, Young-Jin
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2008.11a
    • /
    • pp.348-355
    • /
    • 2008
  • In Korea, the Seoul subway line 1 was opened in 1974 and the subway service is being operated in Seoul, Pusan, Daegu, Daejeon, and Inchon. The subway station is related to a underground shopping mall that was developed as complex spaces. According to the time of people's stay at the underground space, the necessity about the safety countermeasure of the underground space has been enlarged. Therefore the result of this study is t propose guidelines for improving the evacuation safety performance in underground subway stations.

  • PDF

Study on Disaster Prevention in Case of Fire at Subway Platform with Platform Screen Door

  • Rie, Dong-Ho;Yoon, Sung-Wook;Ko, Jae-Woong;Lee, Keun-Oh
    • International Journal of Safety
    • /
    • v.4 no.2
    • /
    • pp.36-42
    • /
    • 2005
  • A study on fire phenomena in a subway transit mass station has been carried out as a part of disaster prevention plan at the subway station. The ventilation facilities installed in both the platform and the trackway are designed to convert into a smoke exhaust system in emergency situation, creating an environment necessary for evacuation. 3 dimensional Numerical Simulations based on the CFD are carried out using a simulation tool, Fire Dynamic Simulator. Total of six different cases are made and performances are compared each other to find optimal vents operation to ensure safer environment for evacuation at the platform area considering the installation of platform screen door.

The Heat Release Rate Comparison of Subway car's Interior Materials using Cone Calorimeter (콘칼로리미터를 이용한 도시철도차량 내장재료별 발열량 비교)

  • Lee Cheul-kyu;Lee Duck Hee;Jung Woo Sung
    • Proceedings of the KSR Conference
    • /
    • 2005.05a
    • /
    • pp.70-76
    • /
    • 2005
  • The interior materials of the urban subway car in operation are now being changed to new materials that meet the latest law in effect, the fire safety criteria of the urban railway vehicle. It was well known fact that the composite materials, that were applied to last subway car, were weak on the fire. Contrary to this materials, materials in work have good resistance to the fire. On the paper, To investigate the difference of fire safety level on the subway car, cone calorimeter was used to measure the heat release rate and total heat released according to the ISO 5660. A high radiative heat flux of 50kW/m2 was used to burn out all materials and to simulate the condition of fully developed fire case in the tests.

  • PDF

Numerical Predictions of Fire Characteristics of Passenger Train Fire in an Underground Subway Tunnel, Depending on Change of Location of Ventilation Facility (지하철 터널내의 객차 화재발생시 환기실 위치변화에 따른 화재특성의 수치적 연구)

  • Son, Bong-Sei;Chang, Hee-Chul
    • Fire Science and Engineering
    • /
    • v.22 no.5
    • /
    • pp.1-8
    • /
    • 2008
  • The study is to perform numerical analysis of train fire characteristics in an underground subway tunnel, depending the different locations of ventilation facility. To study the characteristics of train fire, two kinds of worst-case scenarios are selected, based on escape distance, escape time, and fire zone, and trends and thermal environments of tunnel are analyzed by changing the locations of ventilation facility for times. Fire characteristics is calculated by using FLUENT v.6.3.26, and turbulent flow is calculated by using the standard k-${\varepsilon}$ model. The numerical results show distribution of carbon monoxide concentration, temperature, and velocity. The results of this study will contribute to building the most suitable ventilation systems when designing subway stations and tunnels.

A study on safety evaluation by changing smoke ventilation mode in subway tunnels (지하철터널 환기변환모드에 따른 안전성 평가에 관한 연구)

  • Rie, Dong-Ho
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.5 no.4
    • /
    • pp.389-400
    • /
    • 2003
  • In order to recommend the mechanical smoke exhaust operation mode, Subway Environmental Simulation (SES) is used to predict the airflow of the inlet and outlet tunnel for the subway station. Fire Dynamic Simulation (FDS) is used the SES's velocity boundary conditions to clarity the smoke exhaust effectiveness by the variations with mechnical ventilation system. We compared each 6 types of smoke exhaust systems for the result of smoke density and temperature distributions for 1.5m height from the subway station base in order to clarify the safety evaluation for the heat and smoke exhaust on subway fire.

  • PDF