전주의 구조체접지효과가 접지저항 측정에 미치는 영향 연구 (A Study on the Effect of Concrete Pole Foundation on Ground Resistance Measurement)

  • 최종기;유희영;강문호;황갑철;심건보;이형수;김경철
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.464-465
    • /
    • 2008
  • Concrete poles(CP) are popular supports for distribution lines. Various types of grounding electrode, such as copper-clad rods, have been used to maintain CP's ground resistance under the required value. The buried part of CP can also have structural grounding effect because of its iron reinforcing rods inside CPs. In this paper, we measured the total ground current injected into CP ground while measuring the ground current splitting to the metal electrode as well as the total injecting current. By this, it was able to measure the ground current splitting to CP structure. Based on the measured results, interrelationship between ground resistance of metal electrodes and current split factor to CP structure was analyzed.

  • PDF

22.9kV 배전선로 중성선 설치 구조에 따른 유도뢰 차폐효과 분석 (Analysis on the Induced Lightning Shielding Effect According to the Neutral Wire Installation Structure of a 22.9kV Distribution Line)

  • 김점식;김도영;박용범
    • 전기학회논문지P
    • /
    • 제59권2호
    • /
    • pp.191-196
    • /
    • 2010
  • The electricity distribution system in Korea is adopting a multi-grounding system. Protection of this distribution system against lightning is performed by installing overhead ground wires over the high voltage wires, and connecting the overhead ground wires to the ground every 200 m. The ground resistance in this system is limited not to exceed $50\Omega$ and overhead ground wire and neutral wire are multiple parallel lines. Although overhead ground wire and neutral wire are installed in different locations on the same pole, this circuit configuration has duplicated functions of providing a return path for unbalanced currents and protecting the distribution system against induced lightning. Therefore, the purpose of this study is to analyze the induced lightning shielding effect according to the neutral wire installation structure of a 22.9kV distribution line in order to present a new 22.9kV distribution line structure model and characteristics. This study calculated induced lightning voltage by performing numerical analysis when an overhead ground wire is present in the multi-grounding type 22.9kV distribution line structure, and calculated the induced lightning shielding effect based on this calculated induced lightning voltage. In addition, this study proposed and analyzed an improved distribution line model allowing the use of both overhead wire and neutral wire to be installed in the current distribution lines. The result of MATLAB simulation using the conditions applied by Yokoyama showed almost no difference between the induced lightning voltage developed in the current line and that developed in the proposed line. This signifies that shielding the induced lightning voltage through overhead wire makes no difference between current and proposed distribution line structures. That is, this study found that the ground resistance of the overhead wire had an effect on the induced lightning voltage, and that the induced lightning shielding effect of overhead wire is small.

기준신호용 그리드와 절연/독립접지방식의 비교 (Performance Comparison of Signal Reference Grid and Insulated/Isolated Ground Using HIFREQ Simulator)

  • 백승현;김경철;최종기
    • 조명전기설비학회논문지
    • /
    • 제18권5호
    • /
    • pp.69-73
    • /
    • 2004
  • 본 논문은 낙뢰나 스위칭 등에 의해 건물 내에서 발생할 수 있는 과도 현상에 대하여, 기준신호그리드와 절연/독립접지 방식을 비교한 것이다. 전자계 해석프로그램인 HIFREQ을 이용함으로써 정량적인 해석결과에 근거하여 건물내 접지방식의 차이에 따라 접지점에서 어떠한 과도현상이 발생하는지의 고찰이 가능하였다. 본 논문에서 시도한 건축물 내 과도현상 해석방법 및 사례연구 결과는 정보화 건축물에 필요한 접지 방식의 선정을 위한 자료로 활용될 것으로 기대된다.

다층 대지비저항 해석에 의한 최적 접지설계 (DESIGN OF OPTIMUM GROUNDING BY THE RESISTIVITY ANALYSIS OF MULTI-LAYERED SUBSURFACE)

  • 김형수
    • 지구물리
    • /
    • 제6권3호
    • /
    • pp.179-188
    • /
    • 2003
  • 전기설비의 접지는 시설과 인명피해를 방지하기 위한 시설로서 고압전선의 지락사고시 대용량의 전류를 대지속으로 흘려보냄으로서 주변대지의 전위상승을 억제하는데 있다 이와 같은 위험전위는 접지계의 대지구조의 성분 및 균질성 지락전류의 크기 및 지속시간 인체의 전기적 특성 등과 같이 변수가 많아 해석이 매우 어렵다 최근 고장 전류 유입시 대지전위분포를 최대한 균일하게 하기위하여 접지저항을 낮추는 GPR(ground Potential Rise) 저감 방향으로 접지시스템 설계가 이루어졌으며 지상공간의 전위변동의 최소화 균등화함으로써 보안 및 기능 접지를 동시에 만족하는 접지시스템의 해석과 설계가 이루어지고 있다 본 연구에서는 전기비저항 탐사를 통해 밝혀진 지하의 대지비저항 분포를 통해 접지 설계를 수행한 사례를 보여준다

  • PDF

수직으로 전이되는 마이크로스트립의 접지용 방사형 스터브 (Grounding Radial Stub for the Vertical Microstrip Transition)

  • 권덕규;이종호;이해영
    • 대한전자공학회논문지TC
    • /
    • 제37권3호
    • /
    • pp.58-63
    • /
    • 2000
  • 본 논문에서는 고집적 3차원 초고주파 소자 및 모듈에서 발생되는 수직 전이 구조의 효과적인 연결을 위하여 방사형 스터브 (radial stub)를 사용한 접지 방법을 제시하였다. 제안된 구조는 완전 해석법 (full-wave analysis)인 유한 요소법 (finite element method)을 이용하여 해석하였고 제작을 통하여 그 결과를 검증하였다. 해석결과, 2.S~6.3 GHB 주파수 범위에서 반사손실 (return loss) IS dB 이상, 삽입손 실 (insertion loss) 0.5 dB 이하의 특성을 가짐을 확인하였다. 본 해석 결과는 고집적, 소형화를 위한 3차 원 구조를 갖는 초고주파 소자 및 모듈의 공통 접지 연결을 위해 유용하게 사용될 수 있다.

  • PDF

다양한 측정방법을 적용한 대지의 전기적 구조해석 (Electrical Structure Analysis of Ground using Various Methods for Resistivity Measurement)

  • 조성철;이태형;엄주홍;이복희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 C
    • /
    • pp.1492-1493
    • /
    • 2006
  • Wenner 4-probe arrangement is used most widely by the method to measure soil resistivity and the measured data with the Wenner method are apparent resistivities of the soil. Therefore, the soil structure can be analyzed easily from the measured apparent resistivity, but the real soil resistivity is difficult to know correctly at a particular depth or at a specific location on earth surface. This paper introduces a method that can be used to decide the suitable burial depth and the electrode scale of a grounding rod effectively using soil structure analysis equipment based on the dipole-dipole method.

  • PDF

대지에 있어서의 겉보기 대지저항률의 해석동향 (Analysis of Apparent Resistivity in a Multi-Layer Earth Structure)

  • 신수한;김성삼;김주찬;고희석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 A
    • /
    • pp.461-463
    • /
    • 2004
  • This paper intends to compare the investigation of techniques, based on different methods, used to find the electrical grounding parameter of a multi-layered earth(resistivity and thickness) corresponding to model, A technique for estimating earth parameters is presented and shown to be effective based on two case studies. This techni벼e can be applied to an earth structure with an arbitrary number of layer, and since it is not performed manually, can significantly reduce the amount of error involved.

  • PDF

저압용 누전차단기의 차단특성 및 그라파이트 분석에 관한 연구 (A Study on the Cut Off Characteristics and Graphite Analysis of Residual Current Protective Devices for Low Voltage)

  • 최충석;이경섭;정재희;박수홍;김병수;이덕출
    • 한국안전학회지
    • /
    • 제14권1호
    • /
    • pp.49-54
    • /
    • 1999
  • In this paper. we studied cut off characteristics and fire hazard of residual current protective devices(RCD or ELB) for low voltage. The operative time of RCD with grounding resistance was analyzed by using RCD operating tester. The surface structure and composition of insulator were analyzed by using scanning electron microscope(SEM) and energy dispersive x-ray spectroscopy(EDX). The surface of phenol resin showed network structure and void. The spectra shown in EDX analysis are composed not only of the corresponding elements but also of several new spectra, as CK. OK$\alpha$. MgK, SiK. and CaK, which were absent in original material.

  • PDF

도시철도 전식방지 조사보고 현황 (Investigation for the Report of DC Traction Stray Current Protection)

  • 이현구;하태현;정호성;한문섭;배정효
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2008년도 추계학술대회 논문집
    • /
    • pp.281-285
    • /
    • 2008
  • Corrosion of metallic structures arises when an electric current flows from the metal into the electrolyte such as soil and water. The potential difference across the metal-electrolyte interface, the driving force for the corrosion current, can emerge due to a variety of temperature, pH, humidity and resistivity etc.. With respect to a given structure, a stray current is to be defined as a current flowing on a structure that is not part of the intended electrical circuit. Stray currents are caused by other cathodic protection installations, grounding systems and welding posts, referred to as steady state stray currents. But most often traction systems like railroads and tramlines are responsible for large dynamic stray currents. This type of stray current is generally results from the leakage of return currents from large DC traction systems that are grounded or have a bad earth-insulated return path. This paper investigates the reports, which is made for protecting the electrical corrosion by the DC traction stray current before the construction period.

  • PDF

심매설 접지봉의 위치결정을 위한 대지구조 분석 방법들의 비교분석 (Comparison Analysis of Soil Structure Methods for Deciding the Position of a Deeply Driven Ground Rod)

  • 엄주홍;조성철;이태형;이복희
    • 조명전기설비학회논문지
    • /
    • 제21권7호
    • /
    • pp.37-45
    • /
    • 2007
  • 최근 뇌보호용 접지시스템 심매설 봉전극을 사용하는 경우가 늘고 있다. 심매설 봉전극의 경우에는 수직으로 깊게 봉전극을 시설하기 때문에 메시그리드 전극에 비해 장소의 제약을 덜 받는 장점이 있지만 국지적인 대지저항률에 의해 접지임피던스가 크게 변동하므로 설계시에 세밀한 대지구조의 분석이 필요하다. 기존의 Wenner법에 의한 대지저항률 측정은 널리 사용되는 방법이지만 국지적인 대지저항률의 변화를 알아내기가 불가능하였고 또한 겉보기 대지저항률로 측정결과가 나타나므로 정확한 깊이를 예측하기가 어렵다. 따라서 본 연구에서는 96채널 측정설비를 이용하여 대지구조를 2-D 이미지로 분석하였으며, 뇌보호용 심매설 전극을 효과적으로 설계하기 위해 국지적인 대지저항률 변동 및 대지층 깊이의 분석을 시도하였다. 대지저항률의 2-D 이미지 분석은 Wenner alpha법, Dipole-dipole법, Schlumberger법을 사용하였으며, 분석결과를 토대로 기존의 Wenner 1-D법으로 측정한 결과를 CDEGS로 분석한 대지구조와 비교하였다.