• 제목/요약/키워드: Static Transfer Switch(STS)

검색결과 6건 처리시간 0.019초

AC SSCB를 이용한 새로운 3상 Static Transfer Switch (New Three-Phase Static Transfer Switch using AC SSCB)

  • 송승민;김진영;김인동
    • 전기학회논문지
    • /
    • 제67권5호
    • /
    • pp.626-634
    • /
    • 2018
  • These days, widespread use of sensitive loads and distributed generators makes static transfer switch (STS) an essential component in power circuits to achieve a good power quality for AC Grids. In case of a short-circuit fault, previous STS cannot break the fault current. However, the proposed STS has the capability of breaking it quickly as a circuit breaker. Also if there are power quality problems such as Sag/Swell, the proposed STS can quickly transfers the load to the good quality source. Furthermore it is proved that the transfer time of the proposed STS is within one half of period of 3-phase source frequency regardless of the type of load. It is anticipated that the proposed STS may be utilized to realize many stable and reliable AC grid systems.

통신용 전원공급 신뢰성 증진을 위한 ISC-STS 제안 (ISC-STS Proposal for Reliability Improvement of Communication System's)

  • 정현철;현동석
    • 전력전자학회논문지
    • /
    • 제13권5호
    • /
    • pp.383-390
    • /
    • 2008
  • 본 논문은 산업현장에서 중요부하에 안정적인 전원공급을 하기 위하여 설치한 Static Transfer Switch (STS)의 사이리스터(SCR)가 평균 2%대의 고장으로 문제가 되고 있어 이를 방지하고자 SCR 양단에 기계적인 접점스위치를 병렬로 연결시키고 SCR은 병렬스위치가 동작 가능한 구간인 $12{\sim}208$[mS] 구간에만 기능을 수행하도록 구성하였다. 또한 두 개의 입력 중 어느 한쪽이 단락 또는 지락 사고가 발생되더라도 다른 한쪽의 경로와 부하에 영향을 주지 않도록, 두 개의 입력이 동시 투입되는 시간을 차단하는 ISC (Ideal State Conditioning Interlock Device) - STS 시스템을 제안하였다. 이 제안으로 년간 0.89회의 전환 동작 시에만 SCR이 역할을 하고 전환시점 이후에는 병렬스위치가 전원공급계통의 역할을 함으로서 SCR의 피로도를 현저히 감소시켜 고장률을 감소시킬 뿐만 아니라 고장이 발생된 경우라도 부하에는 영향을 미치지 않아 중요부하의 전원공급에 대한 신뢰성을 높이는데 기여할 수 있다.

첨두부하 저감을 위한 비상발전기 연계형 STS 운영 방안에 관한 연구 (A Study on Operation Scheme of STS with Emergency Generator for Peak Shedding)

  • 김창환;이상봉;김규호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2015년도 제46회 하계학술대회
    • /
    • pp.155-156
    • /
    • 2015
  • Recently, electricity consumption has rapidly increased along with economic growth. The operating strategy using emergency generator is aimed, to resolve a demand response management. For strategy of peak shedding using emergency generator, it is essential to introduce the fast transfer switching device. One of the most effective solutions is to use a static transfer switch (STS) based on thyristor. However, the characteristic of natural commutated SCR thyristor should anticipate short duration voltage sag. STS system thus requires more than a quarter cycle to successfully complete transfer process. This paper proposes the operation scheme of the STS system using the forced-commutation technique to mitigate instantaneous voltage sag during peak transfer process. Proposed STS system improved turn-off characteristic thus accomplishes the peak load shedding satisfied power quality. Performance of the proposed STS system is evaluated using electromagnetic transient program (EMTP) to confirm the effectiveness.

  • PDF

상용2회선 수전방식을 적용한 무정전 수변전설비 구축방안 검토·제안연구 (Construction of Uninterruptible Power System by Reliable Incoming Dual-Power Line)

  • 최진성;이상중
    • 조명전기설비학회논문지
    • /
    • 제24권12호
    • /
    • pp.64-70
    • /
    • 2010
  • High capacity UPS and emergency generators are commonly employed at facilities where power interruption is not allowed. Nowadays, combinations of existing commercial incoming power and an emergency generator or combination of multiple generators and CTTS(Closed Transition Transfer Switch) is adopted sometimes for more reliable power supply. In this paper, application of CTTS and STS(Static Transfer Switch) to dual-power line is suggested for highly reliable uninterruptible power. By realizing such a system, construction of incoming power facilities, installation of emergency generator and large capacity UPS can be omitted, through which saving of the installation space and corresponding capital investment can be expected.

비상전원 기능을 갖는 하이브리드 에너지저장시스템 표준화 기술 (Hybrid Energy Storage System with Emergency Power Function of Standardization Technology)

  • 홍경진
    • 한국인터넷방송통신학회논문지
    • /
    • 제19권2호
    • /
    • pp.187-192
    • /
    • 2019
  • 수요관리와 정전에 대한 비상전원 기능을 갖춘 하이브리드 전력저장시스템으로 비상발전설비가 필요한 빌딩 및 공장건축 시에 투자비를 최소화하고, 상시 전력비를 절감함으로서 경제성을 확보할 수 있 기술을 개발함으로써 새로운 비즈니스 모델을 제시한다. 평상시에 STS(Static Transfer Switch)를 통해 부하에 계통 전력을 공급하고 PCS는 계통에 병렬로 연계되어 수요관리를 수행한다. EMS는 수요예측을 통한 전력의 효율적 운용을 위해 ESS에 충방전 지령을 PMS(Power Management System)로 하달하고 PMS는 다시 PCS 제어기로 지령을 전달하여 시스템을 운용한다. 정전시에는 STS가 계통으로부터 빠르게 이탈되면서 PCS는 독립 전원이 되어 부하 측에 정전압/정주파수의 전력을 공급할수 있는 구조이다. 따라서 하이브리드 ESS에 대한 실 계통 연계 및 독립 운전 성능 검증을 통한 신뢰성을 확보할수 있고, 저탄소 녹색성장 기술의 효율적 전력망과 연계 운영이 가능하게 함으로써 ESS 연계를 통한 신재생에너지 발전에 의한 불규칙한 전력 품질개선, 피크부하 기여도 제고가 가능하다. 또한 현재 석탄 화력이 담당하고 있는 주파수추종 예비력을 ESS로 대체함에 따라 연료비가 높은 LNG 발전기 가동비용을 절감할 수 있는 기대효과가 있다.

저가격 고 신뢰성의 400Hz 전원의 무순단 전력절환용 개선된 동기화 기법 (An Improved Synchronization Control Scheme of a Low Cost 400Hz Power Supply for No-Break Power Transfer)

  • 정석언;현동석
    • 전력전자학회논문지
    • /
    • 제19권5호
    • /
    • pp.470-474
    • /
    • 2014
  • This study proposes an improved synchronization control scheme for a low-cost 400Hz power supply for a no-break power transfer system. In the case of aircraft applications, the 400Hz power supply called ground power units is accepted and used as the external electrical power system during stopovers on ground. A momentary break in the supply occurs when shifting from one power source to another. To allow shifting without a break in the supply, the two power sources are momentarily connected in parallel. The proposed synchronization control is achieved by connecting an existing synchronization bus to the voltage zero-crossing signal of a generator power with discrete logic ICs and analog circuits. Therefore, unlike expensive controllers, such as DSP and CAN, the proposed control scheme is rather simple and may decrease operational cost. The practical feasibility of the proposed control scheme is proven by experimental results.