• Title/Summary/Keyword: Spray fire

Search Result 193, Processing Time 0.022 seconds

Numerical Analysis on Interaction between Fire Flame and Water Mist according to the Variation of Nozzle Performance (노즐 특성 변화에 따른 미분무수와 화염과의 상호작용에 관한 수치해석)

  • Bae, Kang-Youl;Chung, Hee-Taeg;Kim, Hyoung-Bum
    • Proceedings of the KSME Conference
    • /
    • 2007.05b
    • /
    • pp.2983-2988
    • /
    • 2007
  • In the present study, the numerical investigation on the effects of water-mist characteristics has been carried out for the fire suppression mechanism. The FDS are used to simulate the interaction of fire plume and water mists, and program describes the fire-driven flows using LES turbulence model, the mixture fraction combustion model, the finite volume method of radiation transport for a non-scattering gray gas, and conjugate heat transfer between wall and gas flow. The numerical model is consisted of a rectangular enclosure of $L{\times}W{\times}H=1.5{\times}1.5{\times}2.0m$ and a water mist nozzle that be installed 1.8m from fire pool. In the study, the parameters of nozzle for simulation are the droplet size and the spray velocity. Finally, the droplet size influences to fire flume on fire suppression than spray velocity because of the effect of terminal velocity, and the optimal condition for fire suppression is that the droplet size and the spray velocity are $100{\mu}m$ and 20m/s, respectively.

  • PDF

Study on Spray Angle of a Throttleable Pintle Injector according to Total Momentum Ratio based on Hot Fire Test Conditions (연소시험 조건 기반 총운동량비에 따른 가변추력 핀틀 분사기의 분무각 분석)

  • Heo, Subeom;Kim, Dae Hwan;Lee, Suji;Yoon, Youngbin
    • Journal of ILASS-Korea
    • /
    • v.25 no.3
    • /
    • pp.126-131
    • /
    • 2020
  • Throttleable rocket engines are in high demand due to the diversification of space missions. Pintle injector is known to be suitable for throttleable rocket engines, because of its high efficiency in overall thrust zone. In this study, the relationship between spray angle of a throttleable pintle injector and total momentum ratio based on hot fire test conditions was investigated. As a result, the spray angle in 100% and 60% throttling level is higher than the spray angle obtained by the case which considers only propellant mass flow rate, owing to higher total momentum ratio (TMR). The results of this study may be useful for predicting spray angle in hot fire test.

Analysis of Water Flux Uniformity for Various Fire Sprinkler Head Type (화재 진압용 스프링클러 헤드 유형에 따른 살수 균일도 분석)

  • Saemi Bang;Chanseob Ahn;Taehoon Kim
    • Journal of ILASS-Korea
    • /
    • v.28 no.2
    • /
    • pp.97-104
    • /
    • 2023
  • A sprinkler is a fire suppression system that extinguishes combustible materials in the early stages of a fire, creating a spray. However, spray formation method of the sprinkler can result in an uneven distribution of water spray on the surface of combustible materials. It is necessary to ensure a consistent water flux density regardless of the spray direction and angle. In this study, the water flux distribution was analyzed for the various types of sprinkler head: circular, flush, pendent, and upright types. All sprinkler heads have a K-factor of 80 LPM/(0.1MPa)0.5. In this study, water collection cubes were used to examine the water flux distribution. The upright type sprinkler head showed a low standard deviation in total sprayed area, indicating a high level of uniformity. The upright type head showed the lowest standard deviation in the radial direction, and also showed the lowest standard deviation in the azimuthal direction. Upright sprinkler head has no obstructing structure along the path of droplets after they are generated. For this reason, upright sprinkler head showed the most uniform water flux distribution on the floor.

A Study on Smoke Movement Characteristics for Water spray system Installation in Tunnel (터널내 수분무 시설 설치시 연기유동 특성 연구)

  • Lim, Kyung-Bum;Kim, Ha-Young;Yoo, Ji-Oh;Rie, Dong-Ho
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2008.04a
    • /
    • pp.230-233
    • /
    • 2008
  • In this study, we conducted an FDS simulation for the purpose of carrying out a basic assessment of the usefulness of the water spray for fire extinguishing. We analyzed the effect of securing the stability in temperature and smoke density in case of fire according to fire intensities and changes in wind speed. When there was no wind speed in tunnels, it was effective in securing the safety of people because the cooling effect of the water spray system had an excellent effect on reducing temperatures and smoke densities there.

  • PDF

Numerical Analysis of the Effects of Droplets Characteristics of Water Spray on Fire Suppression (물 분무 액적 특성이 화재진압에 미치는 영향에 대한 수치해석)

  • Lee, Jaiho
    • Fire Science and Engineering
    • /
    • v.33 no.6
    • /
    • pp.1-8
    • /
    • 2019
  • In this study, the effects of the characteristics of droplets of water spray on suppression of fire were analyzed numerically using fire dynamics simulator (FDS) 6.5.2. Additionally, the fire suppression characteristics by the water spray nozzle, including the extinguishing coefficient (EC), droplet size distribution function (SDF), median volumetric diameter (MVD), and droplets per second (DPS), were evaluated in terms of the decreasing normalized heat release rate (HRR) curve and cooling time. It was observed that with increase in the EC, the normalized HRR curve decreased rapidly, and the changing MVD affected the suppression of fire. In case of mono-disperse, the normalized HRR curve decreased slowly with the increase in DPS. On the contrary, in case of multi-disperse, the normalized HRR curve decreased rapidly even with a small increase in DPS.

APPLICATION OF CFD TECHNIQUE TO PERFORMANCE PREDICTION OF SPRAY CHARACTERISTICS OF WATER-MIST FIRE SUPPRESSION NOZZLES (미분무수 소화 노즐의 분무 특성 예측을 위한 CFD기법의 적용)

  • Chung, H.T.;Lee, C.H.;Cho, B.I.;Han, Y.S.;Ock, Y.W.
    • Journal of computational fluids engineering
    • /
    • v.11 no.4 s.35
    • /
    • pp.56-61
    • /
    • 2006
  • Numerical simulation has been performed to investigate the characteristics of the mist flow through the fire suppression nozzles. The commercial CFD software, FLUENT with the proper modeling was applied for analyzing both the internal and external flow of the spray nozzles. Computations were made for the full cone nozzle in the operation range of the low pressure and high flow-rate. To validate the present computational procedure, numerical results are compared with measurements in terms of K-factor, SMD, axial spray velocity and spray angles. Numerical results suggested that the present numerical model can be used as an adequate tool for a design purpose of mist-spray nozzles.

Assessment of the Usefulness of the Water Spray for Fire Extinguishing in Case of Fire in Tunnels (터널 화재시 수분무 소화설비의 효용성 평가)

  • Rie, Dong-Ho;Lim, Kyung-Bum;Yoo, Ji-Oh
    • Fire Science and Engineering
    • /
    • v.22 no.5
    • /
    • pp.55-60
    • /
    • 2008
  • In this study, we conducted an FDS numerical simulation for the purpose of carrying out a basic assessment of the usefulness of the water spray for fire extinguishing. We analyzed the effect of securing the stability in temperature and smoke density in case of fire according to fire intensities (20MW, 50MW) and changes in wind speed. When there was no wind speed in tunnels, it was effective in securing the safety of people because the cooling effect of the water spray system had an excellent effect on reducing temperatures and smoke densities there. The higher a fire intensity is, the less effect it has on reducing smoke flows. When an air current exists in tunnels, its cooling effect disturbs the smoke stratification and lowers the visibility degree during evacuation. Therefore, the water spray for fire extinguishing should be put into action only after people take shelter during fire.

A study on the Water Mist Fire Suppression Performance (미세 물 분무 소화 성능에 관한 연구)

  • 김봉환;김용판;문철진;홍철현;이형욱
    • Proceedings of the Korean Society of Marine Engineers Conference
    • /
    • 2002.05a
    • /
    • pp.61-65
    • /
    • 2002
  • The present study was numerically and experimentally performed to investigate the fire suppression performance of water mist spray subjected to thermal radiation in closed space. Downward-directed water mist sprays to interact with an under kerosine pool fire were investigated in test facility. The mass mean diameters of water mist droplet were measured by PMAS under various flow conditions. The developed water mist spray nozzle was satisfied to the criteria of NFPA 750, Class 1. The mechanism of the fire suppression by water mist was concluded to be cooling of the fire surface which lead to suppressed of fuel evaporation. It was proved that the water mist spray system under lower pressures could be applied to underground fire protection system.

  • PDF

Experimental study of extinguishment of the pure diffusion flame using water spray (수분무를 이용한 순수확산화염의 소화에 관한 실험적 연구)

  • Jang, Yong-Jae;Kim, Myeong-Bae;Kim, Jin-Guk
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.20 no.2
    • /
    • pp.624-631
    • /
    • 1996
  • This study describes extinguishment mechanism of the purely buoyant diffusion flame using the water spray. Experiments are systematically carried out for the oul pool fire with the six different atomizing nozzles. From the measurement of burning rate which represents the combustion intensity of fire, it is observed that the water spray is able to act to enhance fire rather than to extinguish fire. The air entertainment due to the water spray is visualized to understand this phenomenon, acting to enhance fire. In order to observe effects of droplet size on fire extinguishment, and amount of water which reaches the flame base, fuel surface, and mean diameter of droplets are measured. When water droplets are too small, they do not reach the flame base because they can the water spray having too small doplets is ineffective for extinguishment of the oil fire.

A Validation Study of Temperature Field Predicted by Computational Fire Model for Spray Fire in a Multi-Compartment (다중구획공간내 분무화재시 화재해석모델의 온도장 검증연구)

  • Kim, Sugn-Chan
    • Fire Science and Engineering
    • /
    • v.28 no.5
    • /
    • pp.23-29
    • /
    • 2014
  • The present study has been conducted to investigate the validity of the computational fire model and the results predicted by BRANZFIRE zone model and FDS field model are compared with a real scale fire test with spray fire in a multi-compartment. The liquid spray fires fueled with toluene and methanol are used as the fire source and the quantitative measurement of heat release rate is performed in an isolated ISO-9705 compartment with a standard door opening. The temperature field predicted by FDS model showed good agreement with the measurement in the fire room and the corridor, and BRANZFIRE model also gave acceptable result in spite of its simplicity and roughness. The mean temperature predicted by FDS model corresponds with measurement within maximum discrepancy range of 25% and the overall mean value of FDS model matched well with experimental data less than 10%. This study can contribute to establish the limitation and application scope of computational fire model and provide reference data for applying to reliable fire risk assessment.