• Title/Summary/Keyword: Smooth tube

Search Result 222, Processing Time 0.029 seconds

An Exprimental Study on the Heat Transfer Performance in a Fluidized Bed Double Pipe Heat Exchanger (수직이중관식(垂直二重管式) 유동층형(流動層形) 열교환기(熱交換器)의 전열성능(傳熱性能)에 관한 실험적(實驗的) 연구(硏究))

  • Yoo, Ji-Oh;Seo, Jeong-Yun
    • Solar Energy
    • /
    • v.14 no.2
    • /
    • pp.39-50
    • /
    • 1994
  • Experiments have been conducted to measure the heat transfer coefficient and pressure drop in fluidized bed double pope heat exchangers with smooth tube and longitudinal finned tube. The effect of particle size(alumina beads; do=0.41, 0.54, 0.65, 0.77 mm) and static bed height on the heat transfer coefficient has been evaluated in terms of pumping power. The heat transfer coefficient for the smooth tube and finned tube heat exchangers has been compared with single phase double pipe heat exchanger. Results show that the heat transfer coefficients for the finned tube in $2.96{\sim}3.45$ times higher than the smooth tube. The heat transfer coefficients for the fluidized bed heat exchanger is higher than the single phase heat exchanger for the most of pumping power range tested. The maximum increase in the heat transfer coefficient for fluidized bed is 91.3% for the smooth tube and 127.1% for the finned tube.

  • PDF

An Experimental Study on Laminar Heat Transfer in Flat Aluminum Extruded Tubes Having Small Hydraulic Diameter

  • Kim, Nae-Hyun;Ham, Jung-Ho;Kim, Do-Young
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.15 no.2
    • /
    • pp.47-53
    • /
    • 2007
  • Laminar heat transfer experiments were conducted in flat extruded aluminum tubes. Three different flat tubes-two with smooth inner channel, one with micro-finned inner channel-were tested. Smooth tube data were in reasonable agreement with the predictions by simplified theoretical models. The heat transfer coefficients of the micro-fin tube were significantly smaller than those of the smooth tube. The reason was attributed to the decelerating flow in the inter-fin region. Heat transfer correlations were developed from the data.

Condensing Heat Transfer of Natural Refrigerants with Nanoparticles in Enhanced Tube (나노입자를 포함한 자연냉매의 마이크로 휜관 응축 열전달 특성)

  • Lee, H.S.
    • Journal of Power System Engineering
    • /
    • v.12 no.3
    • /
    • pp.19-25
    • /
    • 2008
  • This paper deals with the heat transfer and pressure drop characteristics of R-290 (Propane), R-600a (Iso-butane) and R-1270 (Propylene) as an environment friendly refrigerant and R-22 as a HCFC's refrigerant for condensing. The test section is a horizontal double pipe heat exchanger. Condensing heat transfer and pressure drop measurements were Peformed for 12.70 mm micro-fin tube and compared with the results in smooth tube. The local condensing heat transfer coefficients of hydrocarbon refrigerants were superior to those of R-22 and the maximum increasing rate of heat transfer coefficient was found in R-600a. The average condensing heat transfer coefficients in hydrocarbon refrigerants showed 20 to 28% higher values than those of R-22. Hydrocarbon refrigerants have a higher pressure drop than that of R-22 with respect to refrigerant qualify and mass flux. Also, the condensing heat transfer coefficient and pressure drop of working fluids in smooth and micro-fin tube were compared. The heat transfer enhancement factor (EF) between smooth and micro-fin tube varied from 2.2 to 2.6 in all experimental conditions.

  • PDF

Condensing Performance Evaluation in Smooth and Micro-Fin Tubes for Natural Mixture Refrigerant (Propane/Butane) (프로판/부탄 혼합자연냉매의 평활관과 마이크로핀관 내의 응축성능평가)

  • Lee Sang-Mu;Lee Joo-Dong;Park Byung-Duck
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.9
    • /
    • pp.816-823
    • /
    • 2005
  • This paper deals with the heat exchange performance prediction of a counter flow type double-tube condenser for natural refrigerant mixtures composed of Propane/n-Butane or Propane/i-Butane in a smooth tube and a micro-fin tube. The local characteristics of heat transfer, mass transfer and pressure drop are calculated using a prediction method developed by the authors. The total pressure drop and the overall heat transfer coefficient are also evaluated on various heat exchange conditions. The calculated results of the natural refrigerant mixtures are compared with HCFC22. In conclusion, natural refrigerant mixtures composed of Propane/n-Butane or Propane/i-Butane are appropriate candidates for alternative refrigerant from the viewpoint of heat transfer characteristics.

R-22 and R-410A Condensation in Flat Aluminum Multi-Channel Tubes (알루미늄 다채널 평판관내 R-22 및 R-410A 응축에 관한 연구)

  • Jung, Ho-Jong;Kim, Nae-Hyun;Yoon, Baek;Kim, Man-Hoi
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.7
    • /
    • pp.575-583
    • /
    • 2002
  • In this study, condensation heat transfer tests were conducted in flat aluminum multi-channel tubes using R-410A, and the results are compared with those of R-22. Two internal geometries were tested; one with a smooth inner surface and the other with micro-fins. Data are presented for the following range of variables; vapor quality (0.1~0.9), mass flux (200~600 kg/$m^2$s) and heat flux (5~15 ㎾/$m^2$). Results show that the effect of surface tension drainage on the fin surface is more pronounced for R-22 than R-410A. The smaller Weber number for R-22 may be responsible. For the smooth tube, the heat transfer coefficient of R-410A is slightly larger than that of R-22. For the micro-fin tube, however, the reverse is true. Possible reasoning is provided considering the physical properties of the refrigerants. For the smooth tube, a correlation of Akers et at. type predicts the data reasonably well. For the micro-fin tube, the Yang and Webb model was modified to correlate the present data.

Evaporation heat transfer and Pressure loss in micro-fin tubes and a smooth tube (마이크로핀관과 평활관에서의 증발열전달과 압력손실 특성)

  • 장세환;정시영;홍영기
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.11 no.2
    • /
    • pp.215-223
    • /
    • 1999
  • Evaporation heat transfer coefficient and pressure loss were measured for three different micro-fin tubes and a smooth tube. The experiments were carried out with R-22 over a wide range of vapor Quality, mass velocity and heat flux. Heat transfer coefficient of the tube with slightly modified fin shape was found to be higher than that of the commercial reference tube by 60%. The improvement of heat transfer has been achieved without noticeable increase of pressure loss. Heat transfer coefficient was increased with increasing quality, refrigerant mass flux, and heat flux. However, the effect of refrigerant mass flux and heat flux was not great. Heat transfer coefficient at bottom was lower than that at top of the tube in low quality region, which suggested the existence of stratification in the micro-fin tube. Pressure drop was linearly increased with increasing refrigerant quality and was proportional to about square of mass flux.

  • PDF

Evaporation heat transfer characteristics inside the U-bend of the smooth and the microfin tube using alternative refrigerant (대체냉매를 사용한 평활관 및 마이크로핀관 곡관부내 증발 열전달 특성)

  • Jo, Geum-Nam;Kim, Byeong-Gi
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.21 no.9
    • /
    • pp.1207-1217
    • /
    • 1997
  • The present work experimentally investigated the effects of mass flux, heat flux, inlet quality on the heat transfer performance inside the U-bend of smooth and microfin tube using R-22 and R-407C refrigerants. The parameters were 200 and 400 kg/m$^{2}$ s for mass flux, 6 and 12 kw/m$^{2}$ for heat flux, 0.1 and 0.2 for inlet quality under the pressure of 0.65 MPa. The apparatus consisted of the test section of four straight sections and three U-bends, preheater, condenser, refrigerant pump, mass flow meter etc. The average heat transfer coefficient at the downstream straight section after U-bend was affected by U-bend due to the centrifugal force and mixing of two-phase flow in the U-bend. The average heat transfer coefficient at the U-bend was 4 ~ 33 % higher than that at the straight section. The average heat transfer coefficients were affected in the order of mass flux, heat flux and inlet quality. The average heat transfer coefficients in the microfin tube were lager by 19 ~ 49% and 33 ~ 69% than that in the smooth tube at the straight section and at the U-bend separately. The average heat transfer coefficients for R-407C were larger by 33 ~ 41% and 17 ~ 29% than that for R-22 in the smooth tube and the microfin tube separately.

A study on the characteristics of evaporation heat transfer of carbon dioxide flowing upward in a vertical smooth tube (이산화탄소의 수직원관 내 상향유동 증발열전달 특성에 관한 연구)

  • Kim, Yong-Jin;Cho, Jin-Min;Kim, Min-Soo
    • Proceedings of the KSME Conference
    • /
    • 2007.05b
    • /
    • pp.2217-2221
    • /
    • 2007
  • Because of the ozone layer depletion and global warming, new alternative refrigerants are being developed. In this study, evaporation heat transfer characteristics of carbon dioxide flowing upward in a vertical tube have been investigated by experiment. Before the test section, a pre-heater is installed to adjust the inlet quality of the refrigerant to a desired value. A smooth tube with outer diameter of 5 mm and length of 1.44 m was selected as a test tube. The test was conducted at mass fluxes of 212 to 530 kg/$m^2s$, saturation temperature of -5 to 20$^{\circ}C$, and heat fluxes of 20 to 45 kW/$m^2$. As the vapor quality and mass fluxes increase, the heat transfer coefficients of carbon dioxide are decreased, and the heat transfer coefficients increase when the heat fluxes and saturation temperatures increase.

  • PDF

R-22 Condensation in Flat Aluminum Multi-Channel Tubes (알루미늄 다채널 평판관내 R-22 응축에 관한 연구)

  • Kim, Jung-Oh;Cho, Jin-Pyo;Kim, Nae-Hyun
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.24 no.2
    • /
    • pp.241-250
    • /
    • 2000
  • In this study, condensation heat transfer tests were conducted in flat aluminum multi-channel tubes using R-22. Two internal geometries were tested ; one with smooth inner surface and the other with micro-fins. Data are presented for the followin~ range of variables ; vapor quality($0.1{\sim}0.9$), mass flux($200{\sim}600kg/m^2s$) and heat flux($5{\sim}15kW/m^2$). The micro-fin tube showed higher heat transfer coefficients compared with those of the smooth tube. The difference increased as the vapor quality increased. Surface tension force acting on the micro-fin surface at the high vapor quality is believed to be responsible. Different from the trends of the smooth tube, where the heat transfer coefficient increased as the mass flux increased, the heat transfer coefficient of the micro-fin tube was independent of the mass flux at high vapor quality, which implies that the surface tension effect on the fin overwhelms the vapor shear effect at the high vapor quality. Present data(except those at low mass flux and high quality) were well correlated by equivalent Reynolds number, Existing correlations overpredicted the present data at high mass flux.

An Experimental study on Heat Characteristics of Horizontal Tubes with Fin in Fluidized Bed Combustor (유동층 연소로 내에서 수평 휜 전열관의 열전달 특성에 관한 실험적 연구)

  • Kang, Hyung-Soo;Chung, Tae-Yong
    • Journal of the Korean Society of Combustion
    • /
    • v.1 no.1
    • /
    • pp.19-29
    • /
    • 1996
  • This study is to investigate the characteristics of heat transfer of a horizontal tube, with radial fins of various configuration, immersed in a high temperature fluidized bed. The experimental heat transfer variation is compared with that of a smooth tube. The finned tubes and smooth tube, with outside and inside diameter of 48.6mm and 30.6mm, are made of steel tubes. The depth of the fin is 5mm, the rake angles of fin are $25^{\circ},\;35^{\circ},\;45^{\circ}$ and the widthes of fin for each rake angle are 0mm, 1mm, 2mm and 3mm. A bed temperature is fixed at $880\;{\pm}\;10^{\circ}C$. A granular refractory(silica sand) is used as a bed material with mean particle diameters of 1.22mm and 1.54mm. The maximum heat transfer coefficient is achieved with the rake angle of $25^{\circ}$ and the width of 0mm for the mean particle size 1.22mm. The coefficient is 2.14 times larger than that for a smooth tube. The rake angle for the maximum heat transfer coefficient depends on the particle size of bed material. Also the transfer coefficient decreases as the width of fin increases.

  • PDF