• 제목/요약/키워드: Small capacitive current

검색결과 21건 처리시간 0.02초

초고압 $SF_6$ 가스차단기의 소전류 차단성능 해석기술 I (Evaluation Method I of the Small Current Breaking Performance for SF(sub)6-Blown High-Voltage Gas Circuit Breakers)

  • 송기동;이병운;박경엽;박정후
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제50권7호
    • /
    • pp.331-337
    • /
    • 2001
  • With the increasing reliability of analysis schemes and the dramatically increased calculating speed, the computer simulation has become and indispensable process to predict the interruption capacity of circuit breakers. Generally, circuit breakers have to possess both the small current and large current interruption abilities and the circuit breaker designers need to evaluate its capacities to save the time and the expense. The analysis of small current and the large current interruption performances have been considered separately because the phenomena occurring in a interrupter are quite different. To analyze the dielectric recovery after large current interruption many physical phenomena such as heat transfer, convection and arc radiation, the nozzle ablation, the ionization of high temperature SF(sub)6 gas, the electric and themagnetic forces and so forth mush be considered. However, in the analysis of small current interruption performance only the cold gas flow analysis needs to be carried out because the capacitive current is to small that the influence from the current can be neglected. In this paper, an empirical equation which is obtained from a series of tests to estimate the dielectric recovery strength has been applied to a real circuit breaker. The results of analysis have been compared with the test results and the reliability has been investigated.

  • PDF

초고압 $SF_6$가스차단기의 소전류 차단성능 해석기술 II (Evaluation Method II of the Small Current Breaking Performance of SF$_6$-Blown High-Voltage Gas Circuit Breakers)

  • 송기동;이병윤;박경엽;박정후
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제50권8호
    • /
    • pp.384-391
    • /
    • 2001
  • The insulation strength between contacts after current interruption to the transient recovery voltage i.e., the dielectric recovery strength should be estimated for the evaluation of the small capacitive current interruption capability. Many authors have used theoretical and semi-experimental approaches to evaluate the transient breakdown voltage after the current interruption. Moreover, an empirical equation, which is obtained from a series of tests, has been used to estimated the dielectric recovery strength. Un this paper, the theoretical method which is generated from the streamer theory has been applied to real circuit breakers in order to evaluated the interruption capability. The results of analysis have been compared with the test results and the reliability has been investigated.

  • PDF

High Efficiency Alternating Current Driver for Capacitive Loads Using a Current-Balance Transformer

  • Baek, Jong-Bok;Cho, Bo-Hyung;Park, Joung-Hu
    • Journal of Power Electronics
    • /
    • 제11권1호
    • /
    • pp.97-104
    • /
    • 2011
  • This paper proposes a new alternating current driving method for highly capacitive loads such as plasma display panels or piezoelectric actuators, etc. In the proposed scheme, a current balance transformer, which has two windings with the same turn-ratio, provides not only a resonance inductance for energy recovery but also a current balance among all of the switching devices of the driver for current stress reduction. The smaller conduction loss than conventional circuits occurs due to the dual conduction paths which are parallel each other in the current balance transformer. Also, the leakage inductances of the transformer are utilized as resonant inductors for energy recovery by the series resonance to the capacitive load. Furthermore, the resonance contributes to the small switching losses of the switching devices by soft-switching operation. To confirm the validity of the proposed circuit, prototype hardware with a 12-inch mercury-free flat fluorescent lamp is implemented. The experimental results are compared with a conventional energy-recovery circuit from the perspective of luminance performances.

커패시터 필터를 갖는 3상 다이오드 정류회로의 불형전원에서의 입력전류 특성 (Input Current Characteristics of a Three-Phase Diode Rectifier with Capacitive Filter under Line Voltage Unbalance Condition)

  • 정승기;이동기;박기원
    • 전력전자학회논문지
    • /
    • 제6권4호
    • /
    • pp.38-38
    • /
    • 2001
  • The three-phase diode rectifier with capacitive filter is highly sensitive to line voltage unbalance. Because of its inherent nonlinear characteristics, small line voltage unbalance may cause highly unbalanced line current, causing detrimental effects on power quality. This paper presents a theoretical basis on this ′unbalance amplification effect′ and derives an analytical model of line current characteristics under unbalanced line voltage condition for various modes of operation. The results provide a basic guideline for optimal design of a three-phase diode rectifier with capacitive filter that is most commonly used for interfacing various power conversion equipments to power lines.

커패시터 필터를 갖는 3상 다이오드 정류회로의 불평형전원에서의 입력전류 특성 (Input Current Characteristics of a Three-Phase Diode Rectifier with Capacitive Filter Under Line Voltage Unbalance Condition)

  • 이동기;박기원;정승기
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2001년도 전력전자학술대회 논문집
    • /
    • pp.569-575
    • /
    • 2001
  • The three-phase diode rectifier with capacitive Inter is highly sensitive to line voltage unbalance. Because of its inherent nonlinear characteristics small line voltage unbalance may cause highly unbalanced line current causing detrimental effects on power quality. This paper presents a theoretical basis on this 'unbalance amplification effect' and derives an analytical model of line current characteristics under unbalanced line voltage condition for various modes of operation. The results provide a basic and important guideline for optimal design of a three-phase diode rectifier with capacitive filter that is most commonly used for interfacing various power conversion equipments to power lines.

  • PDF

커패시터 필터를 갖는 3상 다이오드 정류회로의 불평형전원에서의 입력전류 특성 (Input Current Characteristics of a Three-Phase Diode Rectifier with Capacitive Filter under Line Voltage Unbalance Condition)

  • 정승기;이동기;박기원
    • 전력전자학회논문지
    • /
    • 제6권4호
    • /
    • pp.348-361
    • /
    • 2001
  • 커패시터 필터를 갖는 3 상 다이오드 정류회로는 입력전압의 불평형에 매우 민감한 특성을 가지고 있다. 이러한 정류회로는 그 동작의 비선형성으로 인해 작은 전압의 불평형에도 입력전류에는 큰 불평형이 나타날 수 있으며 이로 인해 전원품질에 악영향을 미친다. 본 논문에서는 이러한 불평형 증폭특성을 이론적으로 규명하고 불평형 정도에 따른 정류회로의 동작모드에 따라 재반 입력전류의 특성에 대한 모델을 도출하였다. 본 논문의 결과는 각종 전력변환 장치의 입력부로서 널리 사용되는 커패시터 필터형 3상 다이오드 정류회로를 최적 설계하는 데에 중요한 해석적 기초를 제공하고 있다.

  • PDF

차단부 형태에 따른 소전류 차단성능 비교 (Comparison of Small Current Interruption Capability Depending on the Type of Interrupter)

  • 송기동;정진교;김홍규
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제55권7호
    • /
    • pp.362-368
    • /
    • 2006
  • This paper presents the results of a small capacitive current interruption test for the three types of interrupter which are called 'serial type', 'parallel/separated type' and 'puffer type' according to the arrangement of the thermal expansion chamber and the puffer cylinder. After the preconditioning test the small current interruption capability of the 'puffer type' decreased, on the contrary, that of the hybrid interrupters increased. A number of reignition have been occurred in the 'serial type' hybrid interrupter and the change of small current interruption capability after preconditioning test is mainly influenced by the structure of interrupter. Finally it has been proved that the 'parallel/separated type' hybrid interrupter has the best interruption performance through the verification tests.

Comparison of Evaluation Methods of the Small Current Breaking Performance for $SF_{6}$ Gas Circuit Breakers

  • Song, Ki-Dong;Lee, Byeong-Yoon;Park, Kyong-Yop;Park, Jung-Hoo
    • KIEE International Transaction on Electrical Machinery and Energy Conversion Systems
    • /
    • 제11B권4호
    • /
    • pp.129-136
    • /
    • 2001
  • In order to evaluate the dielectric recovery strength for GCBs, two equations have been usually utilized. One is the empirical formula obtained from a series of tests and the other is the theoretical formula obtained from the streamer theory. In this paper, both methods were applied to predict the small capacitive current interruption capability of model circuit breakers and were investigated in terms of the reliability by comparing the simulation results with test ones.

  • PDF

정전기 방전시의 소나무목분의 최소착화에너지 측정에 관한 연구 (A Study of Measurement of Minimum Ignition Energy for Pine Tree Dust on Electrostatic Discharges)

  • 이동훈;박한석
    • 한국안전학회지
    • /
    • 제13권3호
    • /
    • pp.74-79
    • /
    • 1998
  • To establish measuring method for minimum ignition energy of explosive powders caused by electrostatic discharge, A measuring method(Hartman) using a very small quantity of pine tree testing powder was proposed, and the influence of discharge current limiting resistance connected in series into a capacitive discharge circuit on ignition energies of explosive powders was investigated. As a result the minimum ignition energy was 42.25mJ when discharge current limiting resistance 300 $k\Omega$.

  • PDF

신차단방식 SF$_{6}$ 가스 차단기의 소전류 차단성능 연구 (Investigation of Small Current Interruption Performance for New Type of Interrupting Chamber in SF$_{6}$ Gas Circuit Breaker)

  • 송원표;권기영;이재성;송기동;김맹헌;고희석
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제54권11호
    • /
    • pp.519-526
    • /
    • 2005
  • This paper presents computer simulation results for developing new type of SF$_{6}$ Circuit Breaker in terms of cold gas flow after small current interruption. This cold gas flows down a nozzle into the chamber of a circuit breaker. There are many difficult problems in analyzing the gas flow due to complex geometry, moving boundary, shock wave and so on. When predicting the dielectric capability of a gas circuit breaker after interruption, the gas pressure and density distributions due to the cold gas must be considered in addition to the electrical field imposed across the gas. A self-coded computational fluid dynamics (CFD) program is used for the simulation of cold gas flow in order to evaluate the electrical field characteristic across open contacts and transient characteristics of insulations after small current interruption.