• 제목/요약/키워드: Slit fin

검색결과 42건 처리시간 0.022초

확대모델을 이용한 특성화된 핀형상의 열전달평가 (An Evaluation of Heat Transfer Characteristics of Individualized Fin Type Using Large Scale Model)

  • 윤점열;강희찬;이관수;김무환
    • 설비공학논문집
    • /
    • 제8권1호
    • /
    • pp.166-175
    • /
    • 1996
  • In recent years, air-conditioning units designed with higher efficiency and more compactness are required due to emphasis on energy efficiency in home electrical appliances. This trend in the air-conditioning industries has accelerated the development of improved heat exchanger with a better performance in heat transfer aspects. In this study, experiments were performed to investigate the shape and configuration of fins affecting on the performance of the conventional fin-and-tube type heat exchanger equipped in a commercial air conditioners. The geometry similtude method was employed to measure the heat transfer coefficient and pressure drop. Experimental results show that this method is very useful to analyze the heat transfer characteristics of the fin-and-tube type heat exchanger. It is also found that the slit fin has better performance than the conventional fin type in the air conditioners. The present results indicate that heat transfer from the fin si influenced by the parameters such as the forming area of the slit fin, the type of interrupted surfaces like a louver or slit, slit patterns and slit raised direction, and it also affects the overall heat exchanger performance.

  • PDF

휜-관 열교환기에 있어서 각종 휜 형상의 성능 특성에 관한 실험적 연구 (Experimental study of performance characteristics of various fin types for fin-tube heat exchanger)

  • 윤백;김영생;박환영;박현연
    • 설비공학논문집
    • /
    • 제11권4호
    • /
    • pp.484-491
    • /
    • 1999
  • Air side heat transfer and pressure drop for ø9.52 fin-tube heat exchanger with various types of slit and louver fins were measured, and compared with wave-slit fin. Longitudinal and transverse tube spacings of the heat exchangers are 21.65mm and 25mm respectively. Actual heat exchanger was tested using water, and the tests were performed for 2 row heat exchangers with 3 different fin spacings, 1.3, 1.5 and 1.7mm. The overall performance of the enhanced fins was evaluated by comparing heat transfer coefficient with respect to fan power.

  • PDF

Experimental Study of Performance Characteristics of Various Fin Types for Fin-Tube Heat Exchanger

  • Youn, Baek;Kim, Young-Saeng;Park, Hwan-Young;Park, Hyun-Yeon
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제8권2호
    • /
    • pp.29-38
    • /
    • 2000
  • Air side heat transfer and pressure drop for f 9.52 fin-tube heat exchanger with various types of slit and louver fins were measured, and compared with wave-slit fin. Longitudinal and transverse tube spacings of the heat exchangers are 21.65 mm and 25mm respectively. Actual heat exchanger was tested using water, and the tests were performed for 2 row heat exchangers with 3 different fin spacings, 1.3, 1.5 and 1.7 mm. The overall performance of the enhanced fins was evaluated by comparing heat transfer coefficient with respect to fan power

  • PDF

비대칭형 슬릿 핀이 적용된 핀-관 열교환기의 습표면 성능 (Air-Side Performance of Fin-and-Tube Heat Exchangers Having Non-Symmetric Slit Fins Under Wet Condition)

  • 김내현
    • 한국산학기술학회논문지
    • /
    • 제16권6호
    • /
    • pp.3698-3707
    • /
    • 2015
  • 본 연구에서는 비대칭형 슬릿 핀 열교환기의 습표면 열전달 및 압력손실에 대하여 실험적으로 검토하였다. 비교를 위하여 널리 사용되는 루버 핀 열교환기에 대한 실험도 수행하였다. 실험범위에서 핀 핏치가 j와 f 인자에 미치는 영향은 크지 않았다. 또한 루버 핀 시료의 j와 f 인자가 슬릿 핀 시료의 값들보다 크게 나타났다. 1열의 경우 평균 j 인자와 f 인자는 27%, 31% 크고, 2열에서는 15%, 30% 크게 나타났다. 슬릿 핀과 루버 핀 모두 열수가 증가하면 j와 f 인자가 감소하였다. 슬릿 핀의 평균 j/f가 루버 핀보다 1열에서 3.4%, 2열에서 11.5% 크게 나타났다. 본 데이터로부터 새로운 상관식을 도출하였다.

An Experimental Study on Air-side Performance of Fin-and-Tube Heat Exchangers with Slit Fin

  • Chang, Keun-Sun;Phan, Thanh-Long
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.627-632
    • /
    • 2006
  • An experimental study is conducted to investigate the effect of the tube row and fin spacing on the air-side heat transfer and friction characteristics of fin-tube heat exchangers with slit fin pattern. A total of twelve samples of fin-tube heat exchangers with the nominal tube diameter of 7 mm, transverse tube pitch of 19 mm and longitudinal tube pitch of 12.5 mm are tested. The thermal fluid measurements are made using a psychometric calorimeter. The raw data are reduced to the desired heat transfer coefficient in terms of j-factor and friction factor of f for various frontal air velocities, fin pitches and number of tube rows.

  • PDF

웨이브 및 웨이브-슬릿 열전달촉진 휜-관 열교환기의 공기측 압력강하 및 열전달 특성에 관한 실험 (Experimental study of air side pressure drop and heat transfer characteristics of wave and wave-slit fin-tube heat exchangers)

  • 윤백;길용현;박현연;유국철;김영생
    • 설비공학논문집
    • /
    • 제10권5호
    • /
    • pp.589-599
    • /
    • 1998
  • Air side heat transfer and pressure drop for fin-tube heat exchanger with wave and wave-slit fins were measured for various fin spacings and number of tube rows. Outer diameter of the tube including fin collar is 10.07mm, and experiments were done with dry surface condition. Longitudinal and transverse tube spacings of the heat exchangers are 21.65mm and 25mm respectively, and wave depth of the wave fin is 2mm. Experiments were conducted for 1, 2 and 3 rows and 3 different fin spacings, 1.3, 1.5 and 1.7mm. An attempt was made to demonstrate advantage of the enhanced fins over the plane fin by introducing the concept of fan power, Effect of the number of tube rows on heat transfer was discussed in connection with general mechanisms of heat transfer enhancement for fin-tube heat exchanger. Also the effect of hydrophilic coating was investigated. Lastly, correlations for Colburn j-factor and friction factor were developed.

  • PDF

습표면 조건에서 슬릿 핀-튜브 열교환기의 열전달 및 압력강하 특성 (Heat Transfer and Friction Characteristics of Slit Fin and Tube Heat Exchangers in Wet Conditions)

  • 장근선
    • 설비공학논문집
    • /
    • 제19권1호
    • /
    • pp.1-9
    • /
    • 2007
  • Water condensate accumulated on the surface of a fin-and-tube heat exchanger significantly affects its thermal and hydraulic performance. The purpose of this study is to investigate the effect of condensate retention on the air-side heat transfer performance and flow friction. Total 12 samples of slit and plate fin-and-tube heat exchangers with varying fin spacing and number of tube rows are tested under dry and wet conditions. The thermal fluid measurements are made using a psychometric calorimeter. Frontal air velocity varies in the range from 0.7 m/s to 1.5 m/s. Using the experimental data, presented are the heat transfer coefficients in terms of Colburn j-factor and friction factor.

An Experimental Study of the Airside Performance of Slit Fin-and-Tube Heat Exchangers under Dry and Wet Conditions

  • Chang, Keun-Sun;Long, Phan-Than
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제17권1호
    • /
    • pp.7-14
    • /
    • 2009
  • Water condensate accumulated on the surface of a fin-and-tube heat exchanger significantly affects its thermal and hydraulic performances. The purpose of this study is to investigate the effects of condensate retention on the air-side heat transfer performance and flow friction for various flow and geometric conditions. Total of twelve samples of slit and plate fin-and-tube heat exchangers are tested under dry and wet conditions. The thermal fluid measurements are made using a psychrometric calorimeter. Frontal air velocity varies in the range from 0.7 m/s to 1.5 m/s. Using the experimental data, presented are heat transfer coefficients in terms of Colburn j-factors and friction factors, and these data are compared with the existing correlations.

슬릿과 평판 핀-관 열교환기의 공기측 열전달 및 마찰특성 (Air-side Heat Transfer and Friction Characteristics of Finned Tube Beat Exchangers with Slit Fin or Plain Fin)

  • 권영철;장근선;박병권;권정태;정지환
    • 에너지공학
    • /
    • 제16권1호
    • /
    • pp.7-14
    • /
    • 2007
  • 본 연구는 핀-관 열교환기의 건표면과 습표면 조건에서의 공기측 열전달 및 마찰특성을 실험을 통해 이해하고자 수행하였다. 핀-관 열교환기의 성능평가 및 해석기술을 확보하기 위하여 공기엔탈피식 칼로리 미터를 이용하였다. 핀형상은 슬릿과 평판이며, 관경은 7.0mm로 2열과 3열 핀-관 열교환기 4종에 대해 실험하여, 건표면과 습표면의 공기측 열전달 및 마찰특성을 조사하였다. 습표면에서 습도변화(RH 50%, 70%)에 따른 습도영향도 조사하였다. 건표면 조건에서 Re 수가 증가할수록 j 계수는 감소하며, 2열이 3열보다 높았다. 마찰계수는 슬릿 핀이 평판 핀보다 높았다. 습표면 조건에서 슬릿 핀이 평판 핀보다 그리고 2열이 3열보다 우수한 열전달효과를 나타내었다. j 계수와 마찰계수는 습도변화, 열수, 핀 형상에 따라 달라짐을 확인하였다.

물결형 슬릿핀이 장착된 핀-관 열교환기의 습표면 성능 실험 (Wet surface performance test of fin-tube heat exchangers with slit-wavy fin)

  • 김내현;김정식;조진표;윤재호;백종현;이순구;남승백;권형진
    • 설비공학논문집
    • /
    • 제9권2호
    • /
    • pp.153-162
    • /
    • 1997
  • In this study, the wet surface heat transfer coefficients and friction factors of the heat exchanger with slit-wavy fin were measured. Four sample cores of two or three row with fins of 12 fpi or 16 fpi were tested. Tests were conducted in a closed loop wind tunnel, where the heat exchanger was mounted at 45 degree inclination angle. The wet surface heat transfer coefficient was reduced following the procedure given in ARI 420-81. During the course, new definitions of the $\varepsilon$-NTU applicable to enthalpy driving system were introduced. The wet surface heat transfer coefficients were approximately equal to the dry surface values. However, the friction factors were approximately 120% to 170% higher than those of the dry surface. Both the heat transfer coefficient and the friction factor of the wet surface increased as the relative humidity increased, fin pitch decreased, and the number of row decreased, although the difference was not large.

  • PDF