Abstract
An experimental study is performed to investigate the effect of air-side heat transfer and friction on characteristics of finned tube heat exchanger under dry surface and wet surface conditions (RH 50%, 70%). Air enthalpy calorimeter is used to obtain the performance evaluation and analysis of a fined tube heat exchanger. Four finned tube heat exchangers with slit fin or plain fin are tested. The number of tube rows are 2 and 3, and the tube diameter is 7 mm. Air-side heat transfer and friction are presented in terms of j factor and friction factor. At dry surface condition, j factor decreases with increasing Re and j factor of 3 row is lower than that of 2 row. Also, the friction factor of a slit fin is larger than that of a plain fin. At wet surface condition, the heat transfer effect is more significant in the case of the slit fin than the plain fin and 2 row than 3 row. The j factor and friction factor are affected by humidity, tube row and fin configuration.
본 연구는 핀-관 열교환기의 건표면과 습표면 조건에서의 공기측 열전달 및 마찰특성을 실험을 통해 이해하고자 수행하였다. 핀-관 열교환기의 성능평가 및 해석기술을 확보하기 위하여 공기엔탈피식 칼로리 미터를 이용하였다. 핀형상은 슬릿과 평판이며, 관경은 7.0mm로 2열과 3열 핀-관 열교환기 4종에 대해 실험하여, 건표면과 습표면의 공기측 열전달 및 마찰특성을 조사하였다. 습표면에서 습도변화(RH 50%, 70%)에 따른 습도영향도 조사하였다. 건표면 조건에서 Re 수가 증가할수록 j 계수는 감소하며, 2열이 3열보다 높았다. 마찰계수는 슬릿 핀이 평판 핀보다 높았다. 습표면 조건에서 슬릿 핀이 평판 핀보다 그리고 2열이 3열보다 우수한 열전달효과를 나타내었다. j 계수와 마찰계수는 습도변화, 열수, 핀 형상에 따라 달라짐을 확인하였다.