Air-side Heat Transfer and Friction Characteristics of Finned Tube Beat Exchangers with Slit Fin or Plain Fin

슬릿과 평판 핀-관 열교환기의 공기측 열전달 및 마찰특성

  • Published : 2007.02.28

Abstract

An experimental study is performed to investigate the effect of air-side heat transfer and friction on characteristics of finned tube heat exchanger under dry surface and wet surface conditions (RH 50%, 70%). Air enthalpy calorimeter is used to obtain the performance evaluation and analysis of a fined tube heat exchanger. Four finned tube heat exchangers with slit fin or plain fin are tested. The number of tube rows are 2 and 3, and the tube diameter is 7 mm. Air-side heat transfer and friction are presented in terms of j factor and friction factor. At dry surface condition, j factor decreases with increasing Re and j factor of 3 row is lower than that of 2 row. Also, the friction factor of a slit fin is larger than that of a plain fin. At wet surface condition, the heat transfer effect is more significant in the case of the slit fin than the plain fin and 2 row than 3 row. The j factor and friction factor are affected by humidity, tube row and fin configuration.

본 연구는 핀-관 열교환기의 건표면과 습표면 조건에서의 공기측 열전달 및 마찰특성을 실험을 통해 이해하고자 수행하였다. 핀-관 열교환기의 성능평가 및 해석기술을 확보하기 위하여 공기엔탈피식 칼로리 미터를 이용하였다. 핀형상은 슬릿과 평판이며, 관경은 7.0mm로 2열과 3열 핀-관 열교환기 4종에 대해 실험하여, 건표면과 습표면의 공기측 열전달 및 마찰특성을 조사하였다. 습표면에서 습도변화(RH 50%, 70%)에 따른 습도영향도 조사하였다. 건표면 조건에서 Re 수가 증가할수록 j 계수는 감소하며, 2열이 3열보다 높았다. 마찰계수는 슬릿 핀이 평판 핀보다 높았다. 습표면 조건에서 슬릿 핀이 평판 핀보다 그리고 2열이 3열보다 우수한 열전달효과를 나타내었다. j 계수와 마찰계수는 습도변화, 열수, 핀 형상에 따라 달라짐을 확인하였다.

Keywords

References

  1. Nakayama, W.; Xu. L.P. Enhanced fin for air cooled heat exchangers-heat transfer and friction correlation. 1st ASME/JSME. Thermal Engineering Joint Conference, 1983, 495-502
  2. Wang, C.C.; Tao, W.H.; Chang, C.J. An investigation of the air side performance of the slit fin-and-tube heat exchangers, Int. J. of Refrigeration, 1999, 22, 595-603 https://doi.org/10.1016/S0140-7007(99)00031-6
  3. 김내현; 김정석; 조진표; 윤재호; 백종현; 이순구; 남 승백; 권형진. 고성능 핀 관 열교환기의 습표면 성능 실험, 공기조화냉동공학회 동계학술발표대회, 1996, 15-23
  4. 김내현; 오왕규; 조진표; 박환영; 윤백. 제습이 수반된 공조용 증발기 습표면의 열전달계수 데이터 리덕션, 설비공학논문집, 2003, 15, 73-85
  5. 김용배; 윤린; 김용찬; 문동수; 홍기수; 진심원. 응축 수 맺힘조건에서 슬릿형상을 갖는 핀-튜브 열교환기 의 공기측 열전달 특성, 대한기계학회 2005년도 춘계 학술대회, 2005, 2583-2588
  6. Halici, F.; Taymaz, I.; Gunduz, M. The effect of the number of tube rows on heat, mass and momentum transfer in flat-plate finned tube heat exchangers, Energy, 2001, 26, 963-972 https://doi.org/10.1016/S0360-5442(01)00048-2
  7. Wang, C.C.; Hsieh, Y.C.; Lin, Y.T. Performance of plate finned tube heat exchangers under dehumidifying conditions, Trans. of ASME. J. of Heat Transfer, 1997, 119, 109-117 https://doi.org/10.1115/1.2824075
  8. ASHRAE Guideline 2-86, Engineering analysis of experimental analysis, ASHRAE, 1986
  9. 윤백; 김영생; 박현연. 직교류 핀 관 열교환기의 성능 평가, 공기조화냉동공학회지, 1996, 25, 151-160
  10. Sawai, S.; Hayashi, T.; Ohtake, Y.; Takei, T. Effects of mechanical bond between fin and tube on heat transfer, Refrigeration, 1969, 41, 15-21
  11. Gnielinski, V. New equation for heat and mass transfer in turbulent pipe and channel flow, Int. Chem. Engineering, 1976, 16, 359-368
  12. Schmidt, T.E. Heat transfer calculation for extended surface, J of ASHRAE, Refrigerating Engineering, 1949, 4, 351-357
  13. 장근선; 김영재; 정지환. 공조기 성능해석기법 개발, 공조기술연구센터 보고서, 2005
  14. Bump, T.R. Average temperature in simple heat exchangers, ASME Journal of Heat Transfer, 1963, 85, 182-183 https://doi.org/10.1115/1.3686051
  15. Myers, R.J. Effect of the number of tube rows on heat transfer performance of smooth plate fin and tube heat exchanger, ASHRAE Transactions, 1967, 81, 307-317