• 제목/요약/키워드: Single-loop robust voltage controller

검색결과 8건 처리시간 0.022초

Low Cost and High Performance Single Phase UPS Using a Single-Loop Robust Voltage Controller

  • Ji, Jun-Keun;Ku, Dae-Kwan;Lim, Seung-Beom
    • Journal of Power Electronics
    • /
    • 제15권3호
    • /
    • pp.695-701
    • /
    • 2015
  • Uninterruptible Power Supplies (UPSs) can be largely divided into the passive-standby, line-interactive and double-conversion methods. This paper proposes a double-conversion UPS with a low cost and high performance. This single phase UPS uses a single-loop robust voltage controller and 1-switch voltage doubler strategy PFC. The proposed UPS is composed of a single phase PFC, a half-bridge inverter, a battery charger and a battery discharger. Finally, the validity of proposed UPS was verified by various experimental tests.

단상 UPS용 인버터의 강인제어기 설계 (Design of Robust Controller of Inverter for Single UPS)

  • 김제홍;김재식
    • 대한전자공학회:학술대회논문집
    • /
    • 대한전자공학회 2001년도 하계종합학술대회 논문집(5)
    • /
    • pp.233-236
    • /
    • 2001
  • In this paper, a robust controller for UPS inverter is designed using CDM (Coefficient Diagram Method) developed by S. Manabe, by which a low order controller guaranteeing the stability and robustness is easily designed. The proposed controller consists of two control loops, the inner current control loop and the outer voltage control loop. The robustness of the proposed controller is verified through the theoretic evolution and its simulation.

  • PDF

Lyapunov Based Adaptive-Robust Control of the Non-Minimum phase DC-DC Converters Using Input-Output Linearization

  • Salimi, Mahdi;Zakipour, Adel
    • Journal of Power Electronics
    • /
    • 제15권6호
    • /
    • pp.1577-1583
    • /
    • 2015
  • In this research, a combined adaptive-robust current controller is developed for non-minimum-phase DC-DC converters in a wide range of operations. In the proposed nonlinear controller, load resistance, input voltage and zero interval of the inductor current are estimated using developed adaptation rules and knowing the operating mode of the converter for the closed-loop control is not required; hence, a single controller can be employed for a wide load and line changes in discontinuous and continuous conduction operations. Using the TMS320F2810 digital signal processor, the experimental response of the proposed controller is presented in different operating points of the buck/boost converter. During transition between different modes of the converter, the developed controller has a better dynamic response compared with previously reported adaptive nonlinear approach. Moreover, output voltage steady-state error is zero in different conditions.

단상 전압 소스 인버터의 고조파 왜곡 보상을 위한 비례 다중 공진 제어기에 관한 연구 (A study on proportional multiple-resonance controller for harmonic distortion compensation of single phase VSIs)

  • 곽봉우
    • 전기전자학회논문지
    • /
    • 제27권3호
    • /
    • pp.319-326
    • /
    • 2023
  • 본 논문에서는 단상 전압 소스 인버터 (VSIs)의 강인한 출력 전압 제어를 위한 디지털 제어기 구현과 총 고조파 왜곡(T.H.D.v) 분석을 포함한 시뮬레이션 및 실험 결과를 제시한다. 일반적으로 VSI는 내부 루프의 전류 제어기에 비례 적분(PI) 제어기를 사용하고 외부 루프의 전압 제어기에 비례 공진 (PR) 제어기가 사용된다. 그러나, 비선형 부하에서 여전히 3차, 5차 및 7차와 같은 고차 고조파 왜곡이 발생한다. 따라서 본 논문에서는 고조파 왜곡을 억제하기 위해 홀수 고조파 주파수에 대한 공진 제어기를 포함한 비례 다중 공진 (PMR) 제어기를 제안한다. VSI 플랜트용 컨트롤러의 주파수 응답을 분석하고 PMR 컨트롤러를 설계합니다. 시뮬레이션을 통해 PI와 PMR을 전압 제어기로 사용할 때 출력 전압의 총 고조파 왜곡 특성을 비교 검증합니다. 선형 및 비선형 하중 조건이 모두 고려되었습니다. 마지막으로 PMR 제어기를 3kW급 VSIs 프로토 타입에 적용하여 그 유효성을 입증하였다.

단일 루프 강인 전압 제어기를 이용한 단상 UPS 인버터의 비통신선 방식 병렬 운전 (A Wireless Parallel Operation of Single-phase UPS Inverter using Single-loop Robust Voltage Controller)

  • 구대관;지준근;차귀수
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2011년도 추계학술대회
    • /
    • pp.203-204
    • /
    • 2011
  • 단일 루프 강인 전압 제어기를 이용한 단상 3kVA UPS 인버터의 비통신선 방식 병렬 운전 결과를 기술한다. 단상 UPS 인버터 2대로 병렬운전 실험 환경을 구축하였고, 주파수-전압 강하 방식의 수하 제어를 이용하여 저항 부하, 비선형 부하에 대한 전력분담을 실험을 통하여 확인하였다.

  • PDF

동적변화에 강인한 연료전지 발전시스템의 저주파 리플전류 제거 알고리즘 개발 (Development of Robust Algorithm to Eliminate Low Frequency Current Ripples in Fuel Cell Generation System)

  • 김종수;강현수;최규영;이병국
    • 전기학회논문지
    • /
    • 제58권9호
    • /
    • pp.1720-1727
    • /
    • 2009
  • This paper presents that generation and propagation mechanism of low frequency current ripples generated by a rectification effect of an inverter in fuel cell generation system is analyzed. The ripple reduction methode using hardware components such as capacitors and inductors is examined to reduce low frequency current ripples. A new fast and robust low frequency current ripple elimination algorithm is then proposed to incorporate a single loop current controller, which directly controls fuel cell current, without any extra hardware. The proposed algorithm can completely eliminate this current ripple as well as an overshoot or undershoot is significantly reduced. And the de link voltage and output current are well regulated by inverter controller. The validity of proposed algorithm is verified both computer simulation using PSIM 6.0 and experiment with a 1kW laboratory prototype.

디지털 록인 앰프를 이용한 비정현 계통 전압 하에서 강인한 단상계통 연계 인 버터용 고조파 보상법 (A Robust Harmonic Compensation Technique using Digital Lock-in Amplifier under the Non-Sinusoidal Grid Voltage Conditions for the Single Phase Grid Connected Inverters)

  • 칸 아마드 레이안;아쉬라프 모하마드 노만;최우진
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2018년도 추계학술대회
    • /
    • pp.95-97
    • /
    • 2018
  • The power quality of Single Phase Grid-Connected Inverters (GCIs) has received much attention with the increasing number of Distributed Generation (DG) systems. However, the performance of single phase GCIs get degraded due to several factors such as the grid voltage harmonics, the dead time effect, and the turn ON/OFF of the switches, which causes the harmonics at the output of GCIs. Therefore, it is not easy to satisfy the harmonic standards such as IEEE 519 and P1547 without the help of harmonic compensator. To meet the harmonic standards a certain kind of harmonic controller needs to be added to the current control loop to effectively mitigate the low order harmonics. In this paper, the harmonic compensation is performed using a novel robust harmonic compensation method based on Digital Lock-in Amplifier (DLA). In the proposed technique, DLAs are used to extract the amplitude and phase information of the harmonics from the output current and compensate it by using a simple PI controller in the feedforward manner. In order to show the superior performance of the proposed harmonic compensation technique, it is compared with those of conventional harmonic compensation methods in terms of the effectiveness of harmonic elimination, complexity, and implementation. The validity of the proposed harmonic compensation techniques for the single phase GCIs is verified through the experimental results with a 5kW single phase GCI. Index Terms -Single Phase Grid Connected Inverter (SPGCI), Harmonic Compensation Method, Total Harmonic Distortion (THD) and Harmonic Standard.

  • PDF

전기차 배터리 충전기용 강인한 단위 입력 역률 제어장치 (Robust and Unity Input Power Factor Control Scheme for Electric Vehicle Battery Charger)

  • 웬콩롱;이홍희
    • 전력전자학회논문지
    • /
    • 제20권2호
    • /
    • pp.182-192
    • /
    • 2015
  • This study develops a digital control scheme with power factor correction for a front-end converter in an electric vehicle battery charger. The front-end converter acts as the boost-type switching-mode rectifier. The converter assumes the two roles of the battery charger, which include power factor control and robust charging performance. The proposed control scheme consists of a charging control algorithm and a grid current control algorithm. The scheme aims to obtain unity input power factor and robust performance. Based on the linear average model of the converter, a constant-current constant-voltage charging control algorithm that passes through only one proportional-integral controller and a current feed-forward path is proposed. In the current control algorithm, we utilized a second band pass filter, a single-phase phase-locked loop technique, and a duty-ratio feed-forward term to control the grid current to be in phase with the grid voltage and achieve pure sinusoidal waveform. Simulations and experiments were conducted to verify the effectiveness of the proposed control scheme, both simulations and experiments.