• Title/Summary/Keyword: Sewer Concrete

Search Result 40, Processing Time 0.019 seconds

Selection of concrete lining corrosion protection method for large sewer tunnels (하수터널의 콘크리트 라이닝 부식 방지공법 선정방법에 관한 고찰)

  • Moon, Joon-Shik;Lee, Sungjune
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.16 no.4
    • /
    • pp.347-360
    • /
    • 2014
  • Recently construction of large sewer tunnels used also as underground sluiceways/storages is increasing in order to prevent urban inundation, untreated sewage flow into rivers from combined sewer overflows and consequential river pollution due to climate change. Most of these large sewer tunnels are constructed with concrete and the concrete lining should be protected from corrosion caused by hydrogen sulfide($H_2S$). This paper introduced popular concrete corrosion protection methods for large sewer tunnels with 100-plus years of life cycle, and pros and cons of each corrosion protection methods were described by giving specific examples. However, it is difficult to objectively assess corrosion protection alternatives because of insufficient track record of corrosion protection methods applied to large sewer tunnels. In this paper, the evaluation process for selecting a corrosion protection alternative was introduced for large sewer tunnels using a case study.

Failure Risk Assessment of Reinforced Concrete Sewer Pipes on Crack-Related Defects (원심력철근콘크리관의 결함에 따른 심각도 평가 -균열 사례를 중심으로-)

  • Han, Sangjong;Shin, Hyunjun;Hwang, Hwankook
    • Journal of Korean Society of Water and Wastewater
    • /
    • v.27 no.6
    • /
    • pp.731-741
    • /
    • 2013
  • CCTV inspection method has been used in Korea for more than 20 years, but there is no proper assessment system for sewer failure severity that considers the domestic circumstances. This study classified the defects caused by the overburden load of reinforced concrete sewer pipes depending on severity and developed defect code by analyzing the domestic CCTV inspection videos. The defect score was assigned to each defect code, and it was classified into 5 grades for the decision-making of repair and rehabilitation. The result of this study is expected to be useful for domestic CCTV inspectors to assess the sewer condition and helpful for managers to make a decision of repair and rehabilitation.

Failure Risk Assessment of Reinforced Concrete Sewer Pipes on Joint-Related Defects (원심력철근콘크리트관의 결함에 따른 심각도 평가 -이음부 사례를 중심으로-)

  • Han, Sangjong;Shin, Hyunjun;Hwang, Hwankook
    • Journal of Korean Society of Water and Wastewater
    • /
    • v.27 no.6
    • /
    • pp.787-796
    • /
    • 2013
  • Sewer joint-related defect is one of the most common domestic sewer defects along with the lateral pipe problem. However, there are currently no criteria that precisely assess the joint-related sewer defects. Therefore, this study examined the joint-related sewer defects found in domestic circumstances, classified them according to the suggested defect code, and presented the examples of defect pictures. Each defect code was organized as the process of out of pipeline alignment (OPA) which shows the progress in deterioration. Each defect was classified into 5 grades depending on appropriate repair and rehabilitation method. The result of this study is expected to be useful for domestic CCTV inspectors to assess the sewer condition and helpful for managers to make a decision of repair and rehabilitation.

An Experimental Study on the Engineering Properties of Concrete Spread with Liquefied Antibiotics (액상 항균제를 도포한 하수시설용 콘크리트의 공학적 특성에 관한 실험적 연구)

  • Lee Eui-Bae;Kim Yong-Duk;Cho Bong-Suk;Kim Jae-Hwan;Khil Bae-Su;Kim Moo-Han
    • Proceedings of the Korea Concrete Institute Conference
    • /
    • 2005.05b
    • /
    • pp.233-236
    • /
    • 2005
  • Sewage facilities are positively necessary for environment improvement such as rainwater removal, sewage disposal, preservation of the quality of water and health of the citizens in present-day. Meanwhile, a deterioration of the concrete sewer facilities is increasing rapidly due to the chemical and physical attack and especially biochemical attack that is to say biodeterioration. In this study, to prevent biochemical corrosion of the sewer concrete, surface of the concrete was spread with liquefied organic and inorganic complex antibiotics and then its engineering properties were experimentally investigated

  • PDF

Risk analysis of road cave-in of storm sewer lateral using zoom camera (줌카메라를 활용한 빗물받이 연결관의 도로함몰 리스크 분석)

  • Han, Sangjong;Hwang, Hwankook
    • Journal of Korean Society of Water and Wastewater
    • /
    • v.28 no.6
    • /
    • pp.681-690
    • /
    • 2014
  • It is known that sewer problems are the major causes of road cave-in. The objective of this study is to analyze the risk of road cave-in due to storm sewer laterals. We investigated 174 storm sewer laterals using a zoom camera at O-dong area in Seoul. The causes of road cave-in were classified into five cases: breakage of rigid pipe, deformation of flexible pipe, out of pipeline alignment, changing pipe material or changing pipe diameter, and a poor linkage between lateral and sewer. In addition, all defects were sorted into five grades based on the severity rating at storm sewer laterals. In this study, the most fragile pipe materials were found to be concrete pipe and polyethylene pipe, which recorded 2.3 and 1.69 defect rates. With regard to the causes of road cave-in, deformation of flexible pipe has a large influence on road cave-in at present. On a long-term basis, the two causes, out of pipeline alignment and a poor linkage between lateral and sewer, could have more influence on road cave-in.

An Experimental Study on the Durability Properties of Repair Mortar for Sewer Spread with Liquefied Antibiotic (액상 항균제를 도포한 하수시설용 단면복구재의 내구특성에 관한 실험적 연구)

  • Lee Dong-Heck;Jang Jae-bong;Na Chul-Sung;Cho Bong-Suk;Kim Jae-hwan;Kim Moo-Han
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2005.05a
    • /
    • pp.211-214
    • /
    • 2005
  • Recently, Deterioration of the concrete sewer concrete structures by biochemical corrosion has been issued and a development of the inhibition system of corrosion that has been demanded. The sulfuric acid may react with the hardened cement paste and originate expansive products which can induce swelling and breakless of concrete. Also, a sulphuric acid reacts with calcium hydroxide to from $CaSO_4\;\cdot\;2H_2O$. This reaction accounts for consumption of the calcium hydroxide present in hardened cement paste. In this study, To present from biochemical corrosion of the sewer repair mortar that was spread with liquefied antibiotic and then its experimental properties were experimentally investigated and to estimate the effect of absorbed condition of restorative mortar, the number of coating times and coating contents with antibiotic on the durability properties of restorative mortar spread with antibiotics. Also, testing items such as carbonation depth, choloride ion penetration depth and chemical resistance was tested to estimate the durability properties in third study. In results, the novellus bacillus inhabiting in sewer concrete structures was restrained by antibiotics developed in this study. And carbonation depth, choloride ion penetration depth and chemical resistance of restorative mortar spread with antibiotics was superior to that of plain mortar.

  • PDF

An Experimental Study on Development of Physical Properties and Durability of Concrete Spread with Inorganic Antibiotics (무기질 항균제 도포에 의한 콘크리트의 경화성상 및 내구성상 향상에 관한 실험적 연구)

  • Kim, Moo-Han;Khil, Bae-Su;Kim, Jae-Hwan;Cho, Bong-Suk;Lee, Eui-Bae
    • Journal of the Korea Institute of Building Construction
    • /
    • v.5 no.3 s.17
    • /
    • pp.75-82
    • /
    • 2005
  • Sewage facilities are positively necessary for environment improvement such as rainwater removal, sewage disposal, preservation of the quality of water and health of the citizens in present-day. Meanwhile, a deterioration of the concrete sewer pipe is increasing rapidly due to the chemical and physical attack and especially biochemical attack that is to say biodeterioration. So, in advanced countries, prediction techniques and corrosion inhibition system for sewer concrete are developed and are being applied. Also, antibiotics were developed already but application of that is low because it is not economical and has no practical use. But, in domestic, countermeasures for the corrosion of sewage concrete are not sufficient and biochemical attack is not reflected in those essentially. In this study, to prevent biochemical corrosion of the sewer concrete, surface of the concrete was spread with liquefied inorganic antibiotics and then its engineering properties were experimentally investigated. As a result, compressive strength of the specimen spread with antibiotics were similar to those of non spread, Both bond strength and abrasion amount of the specimen spread with antibiotics were inferior to non spread. Properties of absorption and air permeability of the specimen spread with antibiotics were superior to non spread. Finally, carbonation depth, chloride ion penetration depth and weight change ration of the specimen spread with antibiotics were smaller than non spread.

An Experimental study on the Fundamental Properties of Restorative Mortar Spread with Liquefied Antibiotics for Repair of Sewer Concrete (액상 항균제를 도포한 단면복구용 모르타르의 기초물성에 관한 실험적 연구)

  • Lee Dong-Heck;Jang Jae Bong;Cho Bong-Suk;Kim Jae-Hwan;Lee Byoung-Ky;Kim Moo-Han
    • Proceedings of the Korea Concrete Institute Conference
    • /
    • 2005.05b
    • /
    • pp.305-308
    • /
    • 2005
  • The sulfuric acid may react with the hardened cement paste and originate expansive products which can induce swelling and disaggregation of concrete. The purpose of this study is to estimate the antibacterial performance of antibiotics and the effect of absorbed condition of restorative mortar, the number of coating times and coating contents with antibiotic on the fundamental properties of restorative mortar spead with antibiotics. Also, testing items such as bonding strength, abrasion contents, contents of water absorption, contents of air permeability was tested to estimate the fundamental properties in this study. In results, the novellus bacillus inhabiting in sewer concrete structures was restrained by antibiotics developed in this study. And bonding strength of restorative mortar spread with antibiotics was similla to that of plain mortar. But, resistance to abrasion, water absorption and air permeability of restorative mortar spread with antibiotics was superior to that of plain mortar.

  • PDF

A Study for Drainage Pipe Construction Method using a Boring Machine (천공장치를 이용한 배수설비 연결관 시공 기술에 관한 연구)

  • Chang, Jae-Goo;Kang, Seon-Hong;Kim, Dong-Eun;Jung, Tae-Ho
    • Journal of Korean Society of Water and Wastewater
    • /
    • v.25 no.6
    • /
    • pp.869-875
    • /
    • 2011
  • Ministry of Environment has been promoting BTL business of the sewer rehabilitation which continues from 2005 up to now. Sewer rehabilitation is classified into three parts : wastewater pipe rehabilitation, rainwater pipe rehabilitation and drainage equipment rehabilitation. Drainage equipment rehabilitation is that drainage pipe connects wastewater pipe directly without water-purifier. In the drainage equipment construction, it is inevitable to have the damage of ground structures(wall, gate and U drain, etc) when an open excavation method is used. Therefore it is necessary to develop non-excavation method to connect drainage pipe and wastewater pipe like jacking method to avoid the damage of ground structure. This paper has conducted an analysis of the non-excavation method using a boring machine attached to backhoe, which is issued the verification certificate of environmental technology according to the Development of and Support for Environmental Technology Act, article.7. The index set in this analysis was sectionalized to the condition of construction, the grade of drainage pipe, the size of excavated hole, the amount of waste cement concrete and asphalt concrete and the benefit effect compared to open excavation method.